SPEC 26436

HVTECK AL 1/C 320TRXLPE CB PVC AIA PVC 25kV 133% CSA

Single Conductor, 320 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:320 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 320 TRXLPE AIA 25kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    1190.2990.9773201.0375x12801.797601.91716618165
    1/0190.3361.0143201.0745x12801.834601.95416918915
    2/0190.3761.0543201.1147x12801.874601.99422120265
    3/0190.4231.1013201.1617x12801.921602.04122521295.5
    4/0190.4751.1533201.2137x121102.033602.15322923615.5
    250370.521.2063201.2669x121102.086602.20627125226
    350370.6161.3023201.36211x121102.182602.30231728056
    500370.7361.4223201.48213x121102.302752.45238132536.5
    750610.9081.6043201.66417x121102.484752.63446338557
    1000611.1171.8133201.87317x121102.693752.84348044257.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    113.45020.2110.2890.0720.0640.583+j0.2040.292+j0.0682770193194
    1/013.76330.1670.2290.0680.0620.522+j0.2020.232+j0.0662770221219
    2/0147980.1330.1820.0640.060.423+j0.1320.186+j0.0633879253246
    3/014.310060.1050.1440.0590.0580.384+j0.1300.148+j0.0613879288275
    4/015.112690.0840.1150.0550.0560.355+j0.1290.119+j0.0603879327305
    25015.415000.070.0960.0510.0550.296+j0.0930.101+j0.0584987367343
    35016.121000.0510.070.0460.0520.239+j0.0700.075+j0.0556095443399
    50017.230000.0360.050.0410.0490.196+j0.0560.056+j0.0527203529451
    75018.445000.0230.0330.0350.0460.148+j0.0400.040+j0.0489420633505
    100019.960000.0170.0250.030.0430.140+j0.0400.032+j0.0479420711544
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    1197.5924.828.1326.345x122.0345.641.5248.6924727035
    1/0198.5325.768.1327.285x122.0346.581.5249.6325128145
    2/0199.5526.778.1328.307x122.0347.601.5250.6532930155
    3/01910.7427.978.1329.497x122.0348.791.5251.8433531685.5
    4/01912.0729.298.1330.817x122.7951.641.5254.6934135145.5
    2503713.2130.638.1332.169x122.7952.981.5256.0340337536
    3503715.6533.078.1334.5911x122.7955.421.5258.4747241746
    5003718.6936.128.1337.6413x122.7958.471.9162.2856748416.5
    7506123.0640.748.1342.2717x122.7963.091.9166.9068957377
    10006128.3746.058.1347.5717x122.7968.401.9172.2171465857.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1340.3622340.69230.950.02190.21000.583+j0.2040.292+j0.0682770193194
    1/0347.9828170.54790.750.02070.20340.522+j0.2020.232+j0.0662770221219
    2/0355.6035510.43640.600.01950.19690.423+j0.1320.186+j0.0633879253246
    3/0363.2244770.34450.470.01800.19030.384+j0.1300.148+j0.0613879288275
    4/0383.5456470.27560.380.01680.18370.355+j0.1290.119+j0.0603879327305
    250391.1666750.22970.310.01550.18040.296+j0.0930.101+j0.0584987367343
    350408.9493450.16730.230.01400.17060.239+j0.0700.075+j0.0556095443399
    500436.88133500.11810.160.01250.16080.196+j0.0560.056+j0.0527203529451
    750467.36200250.07550.110.01070.15090.148+j0.0400.040+j0.0489420633505
    1000505.46267000.05580.080.00910.14110.140+j0.0400.032+j0.0479420711544
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A