SPEC 26436
HVTECK AL 1/C 320TRXLPE CB PVC AIA PVC 25kV 133% CSA
Single Conductor, 320 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:320 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 320 TRXLPE AIA 25kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 1 | 19 | 0.299 | 0.977 | 320 | 1.037 | 5x12 | 80 | 1.797 | 60 | 1.917 | 166 | 1816 | 5 |
| 1/0 | 19 | 0.336 | 1.014 | 320 | 1.074 | 5x12 | 80 | 1.834 | 60 | 1.954 | 169 | 1891 | 5 |
| 2/0 | 19 | 0.376 | 1.054 | 320 | 1.114 | 7x12 | 80 | 1.874 | 60 | 1.994 | 221 | 2026 | 5 |
| 3/0 | 19 | 0.423 | 1.101 | 320 | 1.161 | 7x12 | 80 | 1.921 | 60 | 2.041 | 225 | 2129 | 5.5 |
| 4/0 | 19 | 0.475 | 1.153 | 320 | 1.213 | 7x12 | 110 | 2.033 | 60 | 2.153 | 229 | 2361 | 5.5 |
| 250 | 37 | 0.52 | 1.206 | 320 | 1.266 | 9x12 | 110 | 2.086 | 60 | 2.206 | 271 | 2522 | 6 |
| 350 | 37 | 0.616 | 1.302 | 320 | 1.362 | 11x12 | 110 | 2.182 | 60 | 2.302 | 317 | 2805 | 6 |
| 500 | 37 | 0.736 | 1.422 | 320 | 1.482 | 13x12 | 110 | 2.302 | 75 | 2.452 | 381 | 3253 | 6.5 |
| 750 | 61 | 0.908 | 1.604 | 320 | 1.664 | 17x12 | 110 | 2.484 | 75 | 2.634 | 463 | 3855 | 7 |
| 1000 | 61 | 1.117 | 1.813 | 320 | 1.873 | 17x12 | 110 | 2.693 | 75 | 2.843 | 480 | 4425 | 7.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 13.4 | 502 | 0.211 | 0.289 | 0.072 | 0.064 | 0.583+j0.204 | 0.292+j0.068 | 2770 | 193 | 194 |
| 1/0 | 13.7 | 633 | 0.167 | 0.229 | 0.068 | 0.062 | 0.522+j0.202 | 0.232+j0.066 | 2770 | 221 | 219 |
| 2/0 | 14 | 798 | 0.133 | 0.182 | 0.064 | 0.06 | 0.423+j0.132 | 0.186+j0.063 | 3879 | 253 | 246 |
| 3/0 | 14.3 | 1006 | 0.105 | 0.144 | 0.059 | 0.058 | 0.384+j0.130 | 0.148+j0.061 | 3879 | 288 | 275 |
| 4/0 | 15.1 | 1269 | 0.084 | 0.115 | 0.055 | 0.056 | 0.355+j0.129 | 0.119+j0.060 | 3879 | 327 | 305 |
| 250 | 15.4 | 1500 | 0.07 | 0.096 | 0.051 | 0.055 | 0.296+j0.093 | 0.101+j0.058 | 4987 | 367 | 343 |
| 350 | 16.1 | 2100 | 0.051 | 0.07 | 0.046 | 0.052 | 0.239+j0.070 | 0.075+j0.055 | 6095 | 443 | 399 |
| 500 | 17.2 | 3000 | 0.036 | 0.05 | 0.041 | 0.049 | 0.196+j0.056 | 0.056+j0.052 | 7203 | 529 | 451 |
| 750 | 18.4 | 4500 | 0.023 | 0.033 | 0.035 | 0.046 | 0.148+j0.040 | 0.040+j0.048 | 9420 | 633 | 505 |
| 1000 | 19.9 | 6000 | 0.017 | 0.025 | 0.03 | 0.043 | 0.140+j0.040 | 0.032+j0.047 | 9420 | 711 | 544 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch |
| 1 | 19 | 7.59 | 24.82 | 8.13 | 26.34 | 5x12 | 2.03 | 45.64 | 1.52 | 48.69 | 247 | 2703 | 5 |
| 1/0 | 19 | 8.53 | 25.76 | 8.13 | 27.28 | 5x12 | 2.03 | 46.58 | 1.52 | 49.63 | 251 | 2814 | 5 |
| 2/0 | 19 | 9.55 | 26.77 | 8.13 | 28.30 | 7x12 | 2.03 | 47.60 | 1.52 | 50.65 | 329 | 3015 | 5 |
| 3/0 | 19 | 10.74 | 27.97 | 8.13 | 29.49 | 7x12 | 2.03 | 48.79 | 1.52 | 51.84 | 335 | 3168 | 5.5 |
| 4/0 | 19 | 12.07 | 29.29 | 8.13 | 30.81 | 7x12 | 2.79 | 51.64 | 1.52 | 54.69 | 341 | 3514 | 5.5 |
| 250 | 37 | 13.21 | 30.63 | 8.13 | 32.16 | 9x12 | 2.79 | 52.98 | 1.52 | 56.03 | 403 | 3753 | 6 |
| 350 | 37 | 15.65 | 33.07 | 8.13 | 34.59 | 11x12 | 2.79 | 55.42 | 1.52 | 58.47 | 472 | 4174 | 6 |
| 500 | 37 | 18.69 | 36.12 | 8.13 | 37.64 | 13x12 | 2.79 | 58.47 | 1.91 | 62.28 | 567 | 4841 | 6.5 |
| 750 | 61 | 23.06 | 40.74 | 8.13 | 42.27 | 17x12 | 2.79 | 63.09 | 1.91 | 66.90 | 689 | 5737 | 7 |
| 1000 | 61 | 28.37 | 46.05 | 8.13 | 47.57 | 17x12 | 2.79 | 68.40 | 1.91 | 72.21 | 714 | 6585 | 7.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 340.36 | 2234 | 0.6923 | 0.95 | 0.0219 | 0.2100 | 0.583+j0.204 | 0.292+j0.068 | 2770 | 193 | 194 |
| 1/0 | 347.98 | 2817 | 0.5479 | 0.75 | 0.0207 | 0.2034 | 0.522+j0.202 | 0.232+j0.066 | 2770 | 221 | 219 |
| 2/0 | 355.60 | 3551 | 0.4364 | 0.60 | 0.0195 | 0.1969 | 0.423+j0.132 | 0.186+j0.063 | 3879 | 253 | 246 |
| 3/0 | 363.22 | 4477 | 0.3445 | 0.47 | 0.0180 | 0.1903 | 0.384+j0.130 | 0.148+j0.061 | 3879 | 288 | 275 |
| 4/0 | 383.54 | 5647 | 0.2756 | 0.38 | 0.0168 | 0.1837 | 0.355+j0.129 | 0.119+j0.060 | 3879 | 327 | 305 |
| 250 | 391.16 | 6675 | 0.2297 | 0.31 | 0.0155 | 0.1804 | 0.296+j0.093 | 0.101+j0.058 | 4987 | 367 | 343 |
| 350 | 408.94 | 9345 | 0.1673 | 0.23 | 0.0140 | 0.1706 | 0.239+j0.070 | 0.075+j0.055 | 6095 | 443 | 399 |
| 500 | 436.88 | 13350 | 0.1181 | 0.16 | 0.0125 | 0.1608 | 0.196+j0.056 | 0.056+j0.052 | 7203 | 529 | 451 |
| 750 | 467.36 | 20025 | 0.0755 | 0.11 | 0.0107 | 0.1509 | 0.148+j0.040 | 0.040+j0.048 | 9420 | 633 | 505 |
| 1000 | 505.46 | 26700 | 0.0558 | 0.08 | 0.0091 | 0.1411 | 0.140+j0.040 | 0.032+j0.047 | 9420 | 711 | 544 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC