SPEC 26415
HVTECK CU 1/C 260TRXLPE CB PVC AIA PVC 25kV 100% CSA
Single Conductor, 260 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:260 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 260 TRXLPE AIA 25kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 1 | 19 | 0.322 | 0.88 | 260 | 0.94 | 7x12 | 80 | 1.39 | 1.7 | 60 | 1.82 | 464 | 1869 | 4.5 |
| 1/0 | 19 | 0.362 | 0.92 | 260 | 0.98 | 7x12 | 80 | 1.43 | 1.74 | 60 | 1.86 | 536 | 1993 | 5 |
| 2/0 | 19 | 0.405 | 0.963 | 260 | 1.023 | 7x12 | 80 | 1.473 | 1.783 | 60 | 1.903 | 624 | 2137 | 5 |
| 3/0 | 19 | 0.456 | 1.014 | 260 | 1.074 | 9x12 | 80 | 1.524 | 1.834 | 60 | 1.954 | 769 | 2349 | 5 |
| 4/0 | 19 | 0.512 | 1.07 | 260 | 1.13 | 9x12 | 80 | 1.58 | 1.89 | 60 | 2.01 | 909 | 2562 | 5.5 |
| 250 | 37 | 0.558 | 1.124 | 260 | 1.184 | 11x12 | 80 | 1.634 | 1.944 | 60 | 2.064 | 1074 | 2802 | 5.5 |
| 350 | 37 | 0.661 | 1.227 | 260 | 1.287 | 13x12 | 110 | 1.797 | 2.107 | 60 | 2.227 | 1445 | 3426 | 6 |
| 500 | 37 | 0.789 | 1.355 | 260 | 1.415 | 17x12 | 110 | 1.925 | 2.235 | 60 | 2.355 | 1986 | 4142 | 6 |
| 750 | 61 | 0.968 | 1.544 | 260 | 1.604 | 21x12 | 110 | 2.114 | 2.424 | 75 | 2.574 | 2859 | 5350 | 7 |
| 1000 | 61 | 1.117 | 1.693 | 260 | 1.753 | 21x12 | 110 | 2.263 | 2.573 | 75 | 2.723 | 3643 | 6344 | 7 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 12.7 | 669 | 0.128 | 0.175 | 0.061 | 0.062 | 0.417+j0.133 | 0.179+j0.067 | 3879 | 245 | 244 |
| 1/0 | 13 | 844 | 0.102 | 0.139 | 0.057 | 0.059 | 0.381+j0.131 | 0.143+j0.064 | 3879 | 278 | 272 |
| 2/0 | 13.3 | 1064 | 0.082 | 0.112 | 0.053 | 0.057 | 0.353+j0.130 | 0.116+j0.062 | 3879 | 316 | 303 |
| 3/0 | 13.7 | 1342 | 0.064 | 0.087 | 0.049 | 0.055 | 0.287+j0.093 | 0.092+j0.060 | 4987 | 356 | 333 |
| 4/0 | 14.1 | 1692 | 0.051 | 0.07 | 0.045 | 0.053 | 0.270+j0.092 | 0.075+j0.058 | 4987 | 403 | 367 |
| 250 | 14.4 | 2000 | 0.043 | 0.059 | 0.042 | 0.052 | 0.229+j0.071 | 0.064+j0.056 | 6095 | 455 | 411 |
| 350 | 15.6 | 2800 | 0.031 | 0.043 | 0.038 | 0.05 | 0.190+j0.057 | 0.049+j0.054 | 7203 | 537 | 459 |
| 500 | 16.5 | 4000 | 0.021 | 0.03 | 0.033 | 0.047 | 0.145+j0.041 | 0.038+j0.050 | 9420 | 616 | 499 |
| 750 | 18 | 6000 | 0.014 | 0.021 | 0.028 | 0.044 | 0.115+j0.032 | 0.030+j0.047 | 11636 | 716 | 557 |
| 1000 | 19.1 | 8000 | 0.011 | 0.018 | 0.025 | 0.042 | 0.112+j0.031 | 0.027+j0.045 | 11636 | 825 | 608 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | mm | kg/km | kg/km | inch |
| 1 | 19 | 8.18 | 22.35 | 6.60 | 23.88 | 7x12 | 2.03 | 35.31 | 43.18 | 1.52 | 46.23 | 691 | 2781 | 4.5 |
| 1/0 | 19 | 9.19 | 23.37 | 6.60 | 24.89 | 7x12 | 2.03 | 36.32 | 44.20 | 1.52 | 47.24 | 798 | 2966 | 5 |
| 2/0 | 19 | 10.29 | 24.46 | 6.60 | 25.98 | 7x12 | 2.03 | 37.41 | 45.29 | 1.52 | 48.34 | 929 | 3180 | 5 |
| 3/0 | 19 | 11.58 | 25.76 | 6.60 | 27.28 | 9x12 | 2.03 | 38.71 | 46.58 | 1.52 | 49.63 | 1144 | 3496 | 5 |
| 4/0 | 19 | 13.00 | 27.18 | 6.60 | 28.70 | 9x12 | 2.03 | 40.13 | 48.01 | 1.52 | 51.05 | 1353 | 3813 | 5.5 |
| 250 | 37 | 14.17 | 28.55 | 6.60 | 30.07 | 11x12 | 2.03 | 41.50 | 49.38 | 1.52 | 52.43 | 1598 | 4170 | 5.5 |
| 350 | 37 | 16.79 | 31.17 | 6.60 | 32.69 | 13x12 | 2.79 | 45.64 | 53.52 | 1.52 | 56.57 | 2150 | 5098 | 6 |
| 500 | 37 | 20.04 | 34.42 | 6.60 | 35.94 | 17x12 | 2.79 | 48.89 | 56.77 | 1.52 | 59.82 | 2955 | 6164 | 6 |
| 750 | 61 | 24.59 | 39.22 | 6.60 | 40.74 | 21x12 | 2.79 | 53.70 | 61.57 | 1.91 | 65.38 | 4255 | 7962 | 7 |
| 1000 | 61 | 28.37 | 43.00 | 6.60 | 44.53 | 21x12 | 2.79 | 57.48 | 65.35 | 1.91 | 69.16 | 5421 | 9441 | 7 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 322.58 | 2977 | 0.4199 | 0.57 | 0.0186 | 0.2034 | 0.417+j0.133 | 0.179+j0.067 | 3879 | 245 | 244 |
| 1/0 | 330.20 | 3756 | 0.3346 | 0.46 | 0.0174 | 0.1936 | 0.381+j0.131 | 0.143+j0.064 | 3879 | 278 | 272 |
| 2/0 | 337.82 | 4735 | 0.2690 | 0.37 | 0.0162 | 0.1870 | 0.353+j0.130 | 0.116+j0.062 | 3879 | 316 | 303 |
| 3/0 | 347.98 | 5972 | 0.2100 | 0.29 | 0.0149 | 0.1804 | 0.287+j0.093 | 0.092+j0.060 | 4987 | 356 | 333 |
| 4/0 | 358.14 | 7529 | 0.1673 | 0.23 | 0.0137 | 0.1739 | 0.270+j0.092 | 0.075+j0.058 | 4987 | 403 | 367 |
| 250 | 365.76 | 8900 | 0.1411 | 0.19 | 0.0128 | 0.1706 | 0.229+j0.071 | 0.064+j0.056 | 6095 | 455 | 411 |
| 350 | 396.24 | 12460 | 0.1017 | 0.14 | 0.0116 | 0.1640 | 0.190+j0.057 | 0.049+j0.054 | 7203 | 537 | 459 |
| 500 | 419.10 | 17800 | 0.0689 | 0.10 | 0.0101 | 0.1542 | 0.145+j0.041 | 0.038+j0.050 | 9420 | 616 | 499 |
| 750 | 457.20 | 26700 | 0.0459 | 0.07 | 0.0085 | 0.1444 | 0.115+j0.032 | 0.030+j0.047 | 11636 | 716 | 557 |
| 1000 | 485.14 | 35600 | 0.0361 | 0.06 | 0.0076 | 0.1378 | 0.112+j0.031 | 0.027+j0.045 | 11636 | 825 | 608 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC