SPEC 26415

HVTECK CU 1/C 260TRXLPE CB PVC AIA PVC 25kV 100% CSA

Single Conductor, 260 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:260 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 260 TRXLPE AIA 25kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    1190.3220.882600.947x12801.7601.8246418694.5
    1/0190.3620.922600.987x12801.74601.8653619935
    2/0190.4050.9632601.0237x12801.783601.90362421375
    3/0190.4561.0142601.0749x12801.834601.95476923495
    4/0190.5121.072601.139x12801.89602.0190925625.5
    250370.5581.1242601.18411x12801.944602.064107428025.5
    350370.6611.2272601.28713x121102.107602.227144534266
    500370.7891.3552601.41517x121102.235602.355198641426
    750610.9681.5442601.60421x121102.424752.574285953507
    1000611.1171.6932601.75321x121102.573752.723364363447
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    112.76690.1280.1750.0610.0620.417+j0.1330.179+j0.0673879245244
    1/0138440.1020.1390.0570.0590.381+j0.1310.143+j0.0643879278272
    2/013.310640.0820.1120.0530.0570.353+j0.1300.116+j0.0623879316303
    3/013.713420.0640.0870.0490.0550.287+j0.0930.092+j0.0604987356333
    4/014.116920.0510.070.0450.0530.270+j0.0920.075+j0.0584987403367
    25014.420000.0430.0590.0420.0520.229+j0.0710.064+j0.0566095455411
    35015.628000.0310.0430.0380.050.190+j0.0570.049+j0.0547203537459
    50016.540000.0210.030.0330.0470.145+j0.0410.038+j0.0509420616499
    7501860000.0140.0210.0280.0440.115+j0.0320.030+j0.04711636716557
    100019.180000.0110.0180.0250.0420.112+j0.0310.027+j0.04511636825608
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    1198.1822.356.6023.887x122.0343.181.5246.2369127814.5
    1/0199.1923.376.6024.897x122.0344.201.5247.2479829665
    2/01910.2924.466.6025.987x122.0345.291.5248.3492931805
    3/01911.5825.766.6027.289x122.0346.581.5249.63114434965
    4/01913.0027.186.6028.709x122.0348.011.5251.05135338135.5
    2503714.1728.556.6030.0711x122.0349.381.5252.43159841705.5
    3503716.7931.176.6032.6913x122.7953.521.5256.57215050986
    5003720.0434.426.6035.9417x122.7956.771.5259.82295561646
    7506124.5939.226.6040.7421x122.7961.571.9165.38425579627
    10006128.3743.006.6044.5321x122.7965.351.9169.16542194417
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1322.5829770.41990.570.01860.20340.417+j0.1330.179+j0.0673879245244
    1/0330.2037560.33460.460.01740.19360.381+j0.1310.143+j0.0643879278272
    2/0337.8247350.26900.370.01620.18700.353+j0.1300.116+j0.0623879316303
    3/0347.9859720.21000.290.01490.18040.287+j0.0930.092+j0.0604987356333
    4/0358.1475290.16730.230.01370.17390.270+j0.0920.075+j0.0584987403367
    250365.7689000.14110.190.01280.17060.229+j0.0710.064+j0.0566095455411
    350396.24124600.10170.140.01160.16400.190+j0.0570.049+j0.0547203537459
    500419.10178000.06890.100.01010.15420.145+j0.0410.038+j0.0509420616499
    750457.20267000.04590.070.00850.14440.115+j0.0320.030+j0.04711636716557
    1000485.14356000.03610.060.00760.13780.112+j0.0310.027+j0.04511636825608
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000