SPEC 26335

HVTECK AL 1/C 175TRXLPE CB PVC AIA PVC 15kV 100% CSA

Single Conductor, 175 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:175 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 175 TRXLPE AIA 15kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    270.2680.6561750.7165x12801.376501.47614011244
    1190.2990.6871750.7475x12801.407501.50714311754
    1/0190.3360.7241750.7845x12801.444501.54414612374
    2/0190.3760.7641750.8247x12801.584601.70419715324.5
    3/0190.4230.8111750.8717x12801.631601.75120116244.5
    4/0190.4750.8631750.9237x12801.683601.80320517294.5
    250370.520.9161750.9769x12801.736601.85624718745
    350370.6161.0121751.07211x12801.832601.95229321265
    500370.7361.1321751.19213x12801.952602.07235724735.5
    750610.9081.3141751.37417x121102.194602.31443931356
    1000611.1171.5231751.58317x121102.403752.55345637136.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    210.33980.2660.3650.0520.0610.664+j0.1980.368+j0.0662770169176
    110.55020.2110.2890.0480.0590.588+j0.1950.292+j0.0622770194198
    1/010.86330.1670.2290.0450.0570.527+j0.1940.232+j0.0602770222223
    2/011.97980.1330.1820.0420.0560.425+j0.1240.186+j0.0603879255250
    3/012.310060.1050.1440.0380.0540.386+j0.1230.148+j0.0583879290278
    4/012.612690.0840.1150.0350.0520.357+j0.1210.119+j0.0563879329309
    2501315000.070.0960.0330.0510.297+j0.0860.101+j0.0544987370347
    35013.721000.0510.070.0290.0480.240+j0.0640.076+j0.0516095446402
    50014.530000.0360.050.0250.0450.197+j0.0510.056+j0.0487203533451
    75016.245000.0230.0330.0210.0430.148+j0.0350.041+j0.0459420631500
    100017.960000.0170.0250.0180.0410.140+j0.0360.033+j0.0449420707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    276.8116.664.4418.195x122.0334.951.2737.4920816734
    1197.5917.454.4418.975x122.0335.741.2738.2821317494
    1/0198.5318.394.4419.915x122.0336.681.2739.2221718414
    2/0199.5519.414.4420.937x122.0340.231.5243.2829322804.5
    3/01910.7420.604.4422.127x122.0341.431.5244.4829924174.5
    4/01912.0721.924.4423.447x122.0342.751.5245.8030525734.5
    2503713.2123.274.4424.799x122.0344.091.5247.1436827895
    3503715.6525.704.4427.2311x122.0346.531.5249.5843631645
    5003718.6928.754.4430.2813x122.0349.581.5252.6353136805.5
    7506123.0633.384.4434.9017x122.7955.731.5258.7865346656
    10006128.3738.684.4440.2117x122.7961.041.9164.8567955266.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2261.6217710.87271.200.01580.20010.664+j0.1980.368+j0.0662770169176
    1266.7022340.69230.950.01460.19360.588+j0.1950.292+j0.0622770194198
    1/0274.3228170.54790.750.01370.18700.527+j0.1940.232+j0.0602770222223
    2/0302.2635510.43640.600.01280.18370.425+j0.1240.186+j0.0603879255250
    3/0312.4244770.34450.470.01160.17720.386+j0.1230.148+j0.0583879290278
    4/0320.0456470.27560.380.01070.17060.357+j0.1210.119+j0.0563879329309
    250330.2066750.22970.310.01010.16730.297+j0.0860.101+j0.0544987370347
    350347.9893450.16730.230.00880.15750.240+j0.0640.076+j0.0516095446402
    500368.30133500.11810.160.00760.14760.197+j0.0510.056+j0.0487203533451
    750411.48200250.07550.110.00640.14110.148+j0.0350.041+j0.0459420631500
    1000454.66267000.05580.080.00550.13450.140+j0.0360.033+j0.0449420707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC