SPEC 26335
HVTECK AL 1/C 175TRXLPE CB PVC AIA PVC 15kV 100% CSA
Single Conductor, 175 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:175 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 175 TRXLPE AIA 15kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 2 | 7 | 0.268 | 0.656 | 175 | 0.716 | 5x12 | 80 | 1.376 | 50 | 1.476 | 140 | 1124 | 4 |
| 1 | 19 | 0.299 | 0.687 | 175 | 0.747 | 5x12 | 80 | 1.407 | 50 | 1.507 | 143 | 1175 | 4 |
| 1/0 | 19 | 0.336 | 0.724 | 175 | 0.784 | 5x12 | 80 | 1.444 | 50 | 1.544 | 146 | 1237 | 4 |
| 2/0 | 19 | 0.376 | 0.764 | 175 | 0.824 | 7x12 | 80 | 1.584 | 60 | 1.704 | 197 | 1532 | 4.5 |
| 3/0 | 19 | 0.423 | 0.811 | 175 | 0.871 | 7x12 | 80 | 1.631 | 60 | 1.751 | 201 | 1624 | 4.5 |
| 4/0 | 19 | 0.475 | 0.863 | 175 | 0.923 | 7x12 | 80 | 1.683 | 60 | 1.803 | 205 | 1729 | 4.5 |
| 250 | 37 | 0.52 | 0.916 | 175 | 0.976 | 9x12 | 80 | 1.736 | 60 | 1.856 | 247 | 1874 | 5 |
| 350 | 37 | 0.616 | 1.012 | 175 | 1.072 | 11x12 | 80 | 1.832 | 60 | 1.952 | 293 | 2126 | 5 |
| 500 | 37 | 0.736 | 1.132 | 175 | 1.192 | 13x12 | 80 | 1.952 | 60 | 2.072 | 357 | 2473 | 5.5 |
| 750 | 61 | 0.908 | 1.314 | 175 | 1.374 | 17x12 | 110 | 2.194 | 60 | 2.314 | 439 | 3135 | 6 |
| 1000 | 61 | 1.117 | 1.523 | 175 | 1.583 | 17x12 | 110 | 2.403 | 75 | 2.553 | 456 | 3713 | 6.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 10.3 | 398 | 0.266 | 0.365 | 0.052 | 0.061 | 0.664+j0.198 | 0.368+j0.066 | 2770 | 169 | 176 |
| 1 | 10.5 | 502 | 0.211 | 0.289 | 0.048 | 0.059 | 0.588+j0.195 | 0.292+j0.062 | 2770 | 194 | 198 |
| 1/0 | 10.8 | 633 | 0.167 | 0.229 | 0.045 | 0.057 | 0.527+j0.194 | 0.232+j0.060 | 2770 | 222 | 223 |
| 2/0 | 11.9 | 798 | 0.133 | 0.182 | 0.042 | 0.056 | 0.425+j0.124 | 0.186+j0.060 | 3879 | 255 | 250 |
| 3/0 | 12.3 | 1006 | 0.105 | 0.144 | 0.038 | 0.054 | 0.386+j0.123 | 0.148+j0.058 | 3879 | 290 | 278 |
| 4/0 | 12.6 | 1269 | 0.084 | 0.115 | 0.035 | 0.052 | 0.357+j0.121 | 0.119+j0.056 | 3879 | 329 | 309 |
| 250 | 13 | 1500 | 0.07 | 0.096 | 0.033 | 0.051 | 0.297+j0.086 | 0.101+j0.054 | 4987 | 370 | 347 |
| 350 | 13.7 | 2100 | 0.051 | 0.07 | 0.029 | 0.048 | 0.240+j0.064 | 0.076+j0.051 | 6095 | 446 | 402 |
| 500 | 14.5 | 3000 | 0.036 | 0.05 | 0.025 | 0.045 | 0.197+j0.051 | 0.056+j0.048 | 7203 | 533 | 451 |
| 750 | 16.2 | 4500 | 0.023 | 0.033 | 0.021 | 0.043 | 0.148+j0.035 | 0.041+j0.045 | 9420 | 631 | 500 |
| 1000 | 17.9 | 6000 | 0.017 | 0.025 | 0.018 | 0.041 | 0.140+j0.036 | 0.033+j0.044 | 9420 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch |
| 2 | 7 | 6.81 | 16.66 | 4.44 | 18.19 | 5x12 | 2.03 | 34.95 | 1.27 | 37.49 | 208 | 1673 | 4 |
| 1 | 19 | 7.59 | 17.45 | 4.44 | 18.97 | 5x12 | 2.03 | 35.74 | 1.27 | 38.28 | 213 | 1749 | 4 |
| 1/0 | 19 | 8.53 | 18.39 | 4.44 | 19.91 | 5x12 | 2.03 | 36.68 | 1.27 | 39.22 | 217 | 1841 | 4 |
| 2/0 | 19 | 9.55 | 19.41 | 4.44 | 20.93 | 7x12 | 2.03 | 40.23 | 1.52 | 43.28 | 293 | 2280 | 4.5 |
| 3/0 | 19 | 10.74 | 20.60 | 4.44 | 22.12 | 7x12 | 2.03 | 41.43 | 1.52 | 44.48 | 299 | 2417 | 4.5 |
| 4/0 | 19 | 12.07 | 21.92 | 4.44 | 23.44 | 7x12 | 2.03 | 42.75 | 1.52 | 45.80 | 305 | 2573 | 4.5 |
| 250 | 37 | 13.21 | 23.27 | 4.44 | 24.79 | 9x12 | 2.03 | 44.09 | 1.52 | 47.14 | 368 | 2789 | 5 |
| 350 | 37 | 15.65 | 25.70 | 4.44 | 27.23 | 11x12 | 2.03 | 46.53 | 1.52 | 49.58 | 436 | 3164 | 5 |
| 500 | 37 | 18.69 | 28.75 | 4.44 | 30.28 | 13x12 | 2.03 | 49.58 | 1.52 | 52.63 | 531 | 3680 | 5.5 |
| 750 | 61 | 23.06 | 33.38 | 4.44 | 34.90 | 17x12 | 2.79 | 55.73 | 1.52 | 58.78 | 653 | 4665 | 6 |
| 1000 | 61 | 28.37 | 38.68 | 4.44 | 40.21 | 17x12 | 2.79 | 61.04 | 1.91 | 64.85 | 679 | 5526 | 6.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 261.62 | 1771 | 0.8727 | 1.20 | 0.0158 | 0.2001 | 0.664+j0.198 | 0.368+j0.066 | 2770 | 169 | 176 |
| 1 | 266.70 | 2234 | 0.6923 | 0.95 | 0.0146 | 0.1936 | 0.588+j0.195 | 0.292+j0.062 | 2770 | 194 | 198 |
| 1/0 | 274.32 | 2817 | 0.5479 | 0.75 | 0.0137 | 0.1870 | 0.527+j0.194 | 0.232+j0.060 | 2770 | 222 | 223 |
| 2/0 | 302.26 | 3551 | 0.4364 | 0.60 | 0.0128 | 0.1837 | 0.425+j0.124 | 0.186+j0.060 | 3879 | 255 | 250 |
| 3/0 | 312.42 | 4477 | 0.3445 | 0.47 | 0.0116 | 0.1772 | 0.386+j0.123 | 0.148+j0.058 | 3879 | 290 | 278 |
| 4/0 | 320.04 | 5647 | 0.2756 | 0.38 | 0.0107 | 0.1706 | 0.357+j0.121 | 0.119+j0.056 | 3879 | 329 | 309 |
| 250 | 330.20 | 6675 | 0.2297 | 0.31 | 0.0101 | 0.1673 | 0.297+j0.086 | 0.101+j0.054 | 4987 | 370 | 347 |
| 350 | 347.98 | 9345 | 0.1673 | 0.23 | 0.0088 | 0.1575 | 0.240+j0.064 | 0.076+j0.051 | 6095 | 446 | 402 |
| 500 | 368.30 | 13350 | 0.1181 | 0.16 | 0.0076 | 0.1476 | 0.197+j0.051 | 0.056+j0.048 | 7203 | 533 | 451 |
| 750 | 411.48 | 20025 | 0.0755 | 0.11 | 0.0064 | 0.1411 | 0.148+j0.035 | 0.041+j0.045 | 9420 | 631 | 500 |
| 1000 | 454.66 | 26700 | 0.0558 | 0.08 | 0.0055 | 0.1345 | 0.140+j0.036 | 0.033+j0.044 | 9420 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A