SPEC 26326

HVTECK AL 1/C 220NLEPR CB PVC AIA PVC 15kV 133% CSA

Single Conductor, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 220 NLEPR AIA 15kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    270.2680.7462200.8065x12801.566601.68614714244.5
    1190.2990.7772200.8375x12801.597601.71715014814.5
    1/0190.3360.8142200.8745x12801.634601.75415315504.5
    2/0190.3760.8542200.9147x12801.674601.79420416784.5
    3/0190.4230.9012200.9617x12801.721601.84120817735
    4/0190.4750.9532201.0137x12801.773601.89321218825
    250370.521.0062201.0669x12801.826601.94625520315
    350370.6161.1022201.16211x12801.922602.04230122915.5
    500370.7361.2222201.28213x121102.102602.22236427646
    750610.9081.4042201.46417x121102.284752.43444633936.5
    1000611.1171.6132201.67317x121102.493752.64346439267
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    211.83980.2660.3650.0460.0640.662+j0.2010.368+j0.0692770169176
    1125020.2110.2890.0440.0620.586+j0.1980.292+j0.0652770194198
    1/012.36330.1670.2290.0410.060.525+j0.1970.232+j0.0632770222223
    2/012.67980.1330.1820.0380.0580.424+j0.1270.186+j0.0613879255250
    3/012.910060.1050.1440.0350.0560.386+j0.1250.148+j0.0593879290278
    4/013.312690.0840.1150.0320.0530.356+j0.1240.119+j0.0573879329309
    25013.615000.070.0960.030.0520.296+j0.0880.101+j0.0554987370347
    35014.321000.0510.070.0270.0490.240+j0.0660.076+j0.0526095446402
    50015.630000.0360.050.0230.0470.197+j0.0520.056+j0.0507203533451
    7501745000.0230.0330.020.0440.148+j0.0370.041+j0.0469420631500
    100018.560000.0170.0250.0170.0410.140+j0.0370.032+j0.0459420707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    276.8118.955.5920.475x122.0339.781.5242.8221921194.5
    1197.5919.745.5921.265x122.0340.561.5243.6122322044.5
    1/0198.5320.685.5922.205x122.0341.501.5244.5522823074.5
    2/0199.5521.695.5923.227x122.0342.521.5245.5730424974.5
    3/01910.7422.895.5924.417x122.0343.711.5246.7631026395
    4/01912.0724.215.5925.737x122.0345.031.5248.0831528015
    2503713.2125.555.5927.089x122.0346.381.5249.4337930225
    3503715.6527.995.5929.5111x122.0348.821.5251.8744834095.5
    5003718.6931.045.5932.5613x122.7953.391.5256.4454241136
    7506123.0635.665.5937.1917x122.7958.011.9161.8266450496.5
    10006128.3740.975.5942.4917x122.7963.321.9167.1369158437
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2299.7217710.87271.200.01400.21000.662+j0.2010.368+j0.0692770169176
    1304.8022340.69230.950.01340.20340.586+j0.1980.292+j0.0652770194198
    1/0312.4228170.54790.750.01250.19690.525+j0.1970.232+j0.0632770222223
    2/0320.0435510.43640.600.01160.19030.424+j0.1270.186+j0.0613879255250
    3/0327.6644770.34450.470.01070.18370.386+j0.1250.148+j0.0593879290278
    4/0337.8256470.27560.380.00980.17390.356+j0.1240.119+j0.0573879329309
    250345.4466750.22970.310.00910.17060.296+j0.0880.101+j0.0554987370347
    350363.2293450.16730.230.00820.16080.240+j0.0660.076+j0.0526095446402
    500396.24133500.11810.160.00700.15420.197+j0.0520.056+j0.0507203533451
    750431.80200250.07550.110.00610.14440.148+j0.0370.041+j0.0469420631500
    1000469.90267000.05580.080.00520.13450.140+j0.0370.032+j0.0459420707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC