SPEC 26326
HVTECK AL 1/C 220NLEPR CB PVC AIA PVC 15kV 133% CSA
Single Conductor, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 220 NLEPR AIA 15kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 2 | 7 | 0.268 | 0.746 | 220 | 0.806 | 5x12 | 80 | 1.566 | 60 | 1.686 | 147 | 1424 | 4.5 |
| 1 | 19 | 0.299 | 0.777 | 220 | 0.837 | 5x12 | 80 | 1.597 | 60 | 1.717 | 150 | 1481 | 4.5 |
| 1/0 | 19 | 0.336 | 0.814 | 220 | 0.874 | 5x12 | 80 | 1.634 | 60 | 1.754 | 153 | 1550 | 4.5 |
| 2/0 | 19 | 0.376 | 0.854 | 220 | 0.914 | 7x12 | 80 | 1.674 | 60 | 1.794 | 204 | 1678 | 4.5 |
| 3/0 | 19 | 0.423 | 0.901 | 220 | 0.961 | 7x12 | 80 | 1.721 | 60 | 1.841 | 208 | 1773 | 5 |
| 4/0 | 19 | 0.475 | 0.953 | 220 | 1.013 | 7x12 | 80 | 1.773 | 60 | 1.893 | 212 | 1882 | 5 |
| 250 | 37 | 0.52 | 1.006 | 220 | 1.066 | 9x12 | 80 | 1.826 | 60 | 1.946 | 255 | 2031 | 5 |
| 350 | 37 | 0.616 | 1.102 | 220 | 1.162 | 11x12 | 80 | 1.922 | 60 | 2.042 | 301 | 2291 | 5.5 |
| 500 | 37 | 0.736 | 1.222 | 220 | 1.282 | 13x12 | 110 | 2.102 | 60 | 2.222 | 364 | 2764 | 6 |
| 750 | 61 | 0.908 | 1.404 | 220 | 1.464 | 17x12 | 110 | 2.284 | 75 | 2.434 | 446 | 3393 | 6.5 |
| 1000 | 61 | 1.117 | 1.613 | 220 | 1.673 | 17x12 | 110 | 2.493 | 75 | 2.643 | 464 | 3926 | 7 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 11.8 | 398 | 0.266 | 0.365 | 0.046 | 0.064 | 0.662+j0.201 | 0.368+j0.069 | 2770 | 169 | 176 |
| 1 | 12 | 502 | 0.211 | 0.289 | 0.044 | 0.062 | 0.586+j0.198 | 0.292+j0.065 | 2770 | 194 | 198 |
| 1/0 | 12.3 | 633 | 0.167 | 0.229 | 0.041 | 0.06 | 0.525+j0.197 | 0.232+j0.063 | 2770 | 222 | 223 |
| 2/0 | 12.6 | 798 | 0.133 | 0.182 | 0.038 | 0.058 | 0.424+j0.127 | 0.186+j0.061 | 3879 | 255 | 250 |
| 3/0 | 12.9 | 1006 | 0.105 | 0.144 | 0.035 | 0.056 | 0.386+j0.125 | 0.148+j0.059 | 3879 | 290 | 278 |
| 4/0 | 13.3 | 1269 | 0.084 | 0.115 | 0.032 | 0.053 | 0.356+j0.124 | 0.119+j0.057 | 3879 | 329 | 309 |
| 250 | 13.6 | 1500 | 0.07 | 0.096 | 0.03 | 0.052 | 0.296+j0.088 | 0.101+j0.055 | 4987 | 370 | 347 |
| 350 | 14.3 | 2100 | 0.051 | 0.07 | 0.027 | 0.049 | 0.240+j0.066 | 0.076+j0.052 | 6095 | 446 | 402 |
| 500 | 15.6 | 3000 | 0.036 | 0.05 | 0.023 | 0.047 | 0.197+j0.052 | 0.056+j0.050 | 7203 | 533 | 451 |
| 750 | 17 | 4500 | 0.023 | 0.033 | 0.02 | 0.044 | 0.148+j0.037 | 0.041+j0.046 | 9420 | 631 | 500 |
| 1000 | 18.5 | 6000 | 0.017 | 0.025 | 0.017 | 0.041 | 0.140+j0.037 | 0.032+j0.045 | 9420 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch |
| 2 | 7 | 6.81 | 18.95 | 5.59 | 20.47 | 5x12 | 2.03 | 39.78 | 1.52 | 42.82 | 219 | 2119 | 4.5 |
| 1 | 19 | 7.59 | 19.74 | 5.59 | 21.26 | 5x12 | 2.03 | 40.56 | 1.52 | 43.61 | 223 | 2204 | 4.5 |
| 1/0 | 19 | 8.53 | 20.68 | 5.59 | 22.20 | 5x12 | 2.03 | 41.50 | 1.52 | 44.55 | 228 | 2307 | 4.5 |
| 2/0 | 19 | 9.55 | 21.69 | 5.59 | 23.22 | 7x12 | 2.03 | 42.52 | 1.52 | 45.57 | 304 | 2497 | 4.5 |
| 3/0 | 19 | 10.74 | 22.89 | 5.59 | 24.41 | 7x12 | 2.03 | 43.71 | 1.52 | 46.76 | 310 | 2639 | 5 |
| 4/0 | 19 | 12.07 | 24.21 | 5.59 | 25.73 | 7x12 | 2.03 | 45.03 | 1.52 | 48.08 | 315 | 2801 | 5 |
| 250 | 37 | 13.21 | 25.55 | 5.59 | 27.08 | 9x12 | 2.03 | 46.38 | 1.52 | 49.43 | 379 | 3022 | 5 |
| 350 | 37 | 15.65 | 27.99 | 5.59 | 29.51 | 11x12 | 2.03 | 48.82 | 1.52 | 51.87 | 448 | 3409 | 5.5 |
| 500 | 37 | 18.69 | 31.04 | 5.59 | 32.56 | 13x12 | 2.79 | 53.39 | 1.52 | 56.44 | 542 | 4113 | 6 |
| 750 | 61 | 23.06 | 35.66 | 5.59 | 37.19 | 17x12 | 2.79 | 58.01 | 1.91 | 61.82 | 664 | 5049 | 6.5 |
| 1000 | 61 | 28.37 | 40.97 | 5.59 | 42.49 | 17x12 | 2.79 | 63.32 | 1.91 | 67.13 | 691 | 5843 | 7 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 299.72 | 1771 | 0.8727 | 1.20 | 0.0140 | 0.2100 | 0.662+j0.201 | 0.368+j0.069 | 2770 | 169 | 176 |
| 1 | 304.80 | 2234 | 0.6923 | 0.95 | 0.0134 | 0.2034 | 0.586+j0.198 | 0.292+j0.065 | 2770 | 194 | 198 |
| 1/0 | 312.42 | 2817 | 0.5479 | 0.75 | 0.0125 | 0.1969 | 0.525+j0.197 | 0.232+j0.063 | 2770 | 222 | 223 |
| 2/0 | 320.04 | 3551 | 0.4364 | 0.60 | 0.0116 | 0.1903 | 0.424+j0.127 | 0.186+j0.061 | 3879 | 255 | 250 |
| 3/0 | 327.66 | 4477 | 0.3445 | 0.47 | 0.0107 | 0.1837 | 0.386+j0.125 | 0.148+j0.059 | 3879 | 290 | 278 |
| 4/0 | 337.82 | 5647 | 0.2756 | 0.38 | 0.0098 | 0.1739 | 0.356+j0.124 | 0.119+j0.057 | 3879 | 329 | 309 |
| 250 | 345.44 | 6675 | 0.2297 | 0.31 | 0.0091 | 0.1706 | 0.296+j0.088 | 0.101+j0.055 | 4987 | 370 | 347 |
| 350 | 363.22 | 9345 | 0.1673 | 0.23 | 0.0082 | 0.1608 | 0.240+j0.066 | 0.076+j0.052 | 6095 | 446 | 402 |
| 500 | 396.24 | 13350 | 0.1181 | 0.16 | 0.0070 | 0.1542 | 0.197+j0.052 | 0.056+j0.050 | 7203 | 533 | 451 |
| 750 | 431.80 | 20025 | 0.0755 | 0.11 | 0.0061 | 0.1444 | 0.148+j0.037 | 0.041+j0.046 | 9420 | 631 | 500 |
| 1000 | 469.90 | 26700 | 0.0558 | 0.08 | 0.0052 | 0.1345 | 0.140+j0.037 | 0.032+j0.045 | 9420 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A