SPEC 26272

HVTECK AL 3/C 140TRXLPE TS PVC AIA PVC 8kV 133% CSA

3 Conductor, 140 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:140 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 140 TRXLPE AIA 8kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGAWGmilinchinchmilinchlb/1000ftlb/1000ftinch
    673689280.2680.5861400.6461x88801.5811.949602.06923417372.5
    6527781190.2990.6171400.6771x66801.6482.076602.19627119963
    6720791/0100.3360.6541400.7141x661101.7882.156602.27627921833
    6742492/0120.3760.6941400.7541x661101.8752.242602.36228823713
    TBA3/0190.4230.7411400.8011x661101.9762.286752.43628421213
    6720704/0190.4750.7931400.8531x661102.0882.456752.60631029093.5
    TBA250370.520.8461400.9061x441102.2032.513752.66335726253.5
    652787350370.6160.9421401.0021x441102.412.778752.92839337654
    674257500340.7361.0861401.1461x331102.7213.139853.30946047704.5
    TBA750610.9081.2441401.3041x221253.0933.403853.57353150384.5
    TBA1000611.1171.4531401.5131x221253.5443.854854.02458361915.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    214.511940.2660.3650.0440.0260.725+j0.5400.365+j0.0422033135157
    115.415060.2110.2890.0410.0250.652+j0.5220.289+j0.0402129154178
    1/015.919000.1670.2290.0380.0230.595+j0.5030.229+j0.0382243176202
    2/016.523950.1330.1820.0350.0220.550+j0.4830.182+j0.0372367204229
    3/017.130200.1050.1440.0320.0210.514+j0.4610.144+j0.0362513234260
    4/018.238080.0840.1150.030.0190.486+j0.4390.115+j0.0342674268294
    25018.645000.070.0960.0270.0190.467+j0.4170.096+j0.0332838296323
    35020.563000.0510.070.0240.0170.438+j0.3810.070+j0.0323136363386
    50023.290000.0360.050.0220.0160.411+j0.3340.050+j0.0313582447465
    75025135000.0230.0330.0170.0140.383+j0.2910.033+j0.0294071566563
    100028.2180000.0170.0250.0150.0130.358+j0.2460.025+j0.0294719661638
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGAWGmmmmmmmmmmkg/kmkg/kminch
    673689286.8114.883.5616.411x882.0340.1649.501.5252.5534825852.5
    6527781197.5915.673.5617.201x662.0341.8652.731.5255.7840329703
    6720791/0108.5316.613.5618.141x662.7945.4254.761.5257.8141532493
    6742492/0129.5517.633.5619.151x662.7947.6356.951.5259.9942935283
    TBA3/01910.7418.823.5620.351x662.7950.1958.061.9161.8742331563
    6720704/01912.0720.143.5621.671x662.7953.0462.381.9166.1946143293.5
    TBA2503713.2121.493.5623.011x442.7955.9663.831.9167.6453139063.5
    6527873503715.6523.933.5625.451x442.7961.2170.561.9174.3758556034
    6742575003418.6927.583.5629.111x332.7969.1179.732.1684.0568570994.5
    TBA7506123.0631.603.5633.121x223.1878.5686.442.1690.7579074974.5
    TBA10006128.3736.913.5638.431x223.1890.0297.892.16102.2186892135.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2368.3053130.87271.200.01340.08530.725+j0.5400.365+j0.0422033135157
    1391.1667020.69230.950.01250.08200.652+j0.5220.289+j0.0402129154178
    1/0403.8684550.54790.750.01160.07550.595+j0.5030.229+j0.0382243176202
    2/0419.10106580.43640.600.01070.07220.550+j0.4830.182+j0.0372367204229
    3/0434.34134390.34450.470.00980.06890.514+j0.4610.144+j0.0362513234260
    4/0462.28169460.27560.380.00910.06230.486+j0.4390.115+j0.0342674268294
    250472.44200250.22970.310.00820.06230.467+j0.4170.096+j0.0332838296323
    350520.70280350.16730.230.00730.05580.438+j0.3810.070+j0.0323136363386
    500589.28400500.11810.160.00670.05250.411+j0.3340.050+j0.0313582447465
    750635.00600750.07550.110.00520.04590.383+j0.2910.033+j0.0294071566563
    1000716.28801000.05580.080.00460.04270.358+j0.2460.025+j0.0294719661638
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC