SPEC 26272
HVTECK AL 3/C 140TRXLPE TS PVC AIA PVC 8kV 133% CSA
3 Conductor, 140 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:140 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 140 TRXLPE AIA 8kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch | |
| 673689 | 2 | 8 | 0.268 | 0.586 | 140 | 0.646 | 1x8 | 80 | 1.949 | 60 | 2.069 | 234 | 1737 | 2.5 |
| 652778 | 1 | 19 | 0.299 | 0.617 | 140 | 0.677 | 1x6 | 80 | 2.076 | 60 | 2.196 | 271 | 1996 | 3 |
| 672079 | 1/0 | 10 | 0.336 | 0.654 | 140 | 0.714 | 1x6 | 110 | 2.156 | 60 | 2.276 | 279 | 2183 | 3 |
| 674249 | 2/0 | 12 | 0.376 | 0.694 | 140 | 0.754 | 1x6 | 110 | 2.242 | 60 | 2.362 | 288 | 2371 | 3 |
| TBA | 3/0 | 19 | 0.423 | 0.741 | 140 | 0.801 | 1x6 | 110 | 2.286 | 75 | 2.436 | 284 | 2121 | 3 |
| 672070 | 4/0 | 19 | 0.475 | 0.793 | 140 | 0.853 | 1x6 | 110 | 2.456 | 75 | 2.606 | 310 | 2909 | 3.5 |
| TBA | 250 | 37 | 0.52 | 0.846 | 140 | 0.906 | 1x4 | 110 | 2.513 | 75 | 2.663 | 357 | 2625 | 3.5 |
| 652787 | 350 | 37 | 0.616 | 0.942 | 140 | 1.002 | 1x4 | 110 | 2.778 | 75 | 2.928 | 393 | 3765 | 4 |
| 674257 | 500 | 34 | 0.736 | 1.086 | 140 | 1.146 | 1x3 | 110 | 3.139 | 85 | 3.309 | 460 | 4770 | 4.5 |
| TBA | 750 | 61 | 0.908 | 1.244 | 140 | 1.304 | 1x2 | 125 | 3.403 | 85 | 3.573 | 531 | 5038 | 4.5 |
| TBA | 1000 | 61 | 1.117 | 1.453 | 140 | 1.513 | 1x2 | 125 | 3.854 | 85 | 4.024 | 583 | 6191 | 5.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 14.5 | 1194 | 0.266 | 0.365 | 0.044 | 0.026 | 0.725+j0.540 | 0.365+j0.042 | 2033 | 135 | 157 |
| 1 | 15.4 | 1506 | 0.211 | 0.289 | 0.041 | 0.025 | 0.652+j0.522 | 0.289+j0.040 | 2129 | 154 | 178 |
| 1/0 | 15.9 | 1900 | 0.167 | 0.229 | 0.038 | 0.023 | 0.595+j0.503 | 0.229+j0.038 | 2243 | 176 | 202 |
| 2/0 | 16.5 | 2395 | 0.133 | 0.182 | 0.035 | 0.022 | 0.550+j0.483 | 0.182+j0.037 | 2367 | 204 | 229 |
| 3/0 | 17.1 | 3020 | 0.105 | 0.144 | 0.032 | 0.021 | 0.514+j0.461 | 0.144+j0.036 | 2513 | 234 | 260 |
| 4/0 | 18.2 | 3808 | 0.084 | 0.115 | 0.03 | 0.019 | 0.486+j0.439 | 0.115+j0.034 | 2674 | 268 | 294 |
| 250 | 18.6 | 4500 | 0.07 | 0.096 | 0.027 | 0.019 | 0.467+j0.417 | 0.096+j0.033 | 2838 | 296 | 323 |
| 350 | 20.5 | 6300 | 0.051 | 0.07 | 0.024 | 0.017 | 0.438+j0.381 | 0.070+j0.032 | 3136 | 363 | 386 |
| 500 | 23.2 | 9000 | 0.036 | 0.05 | 0.022 | 0.016 | 0.411+j0.334 | 0.050+j0.031 | 3582 | 447 | 465 |
| 750 | 25 | 13500 | 0.023 | 0.033 | 0.017 | 0.014 | 0.383+j0.291 | 0.033+j0.029 | 4071 | 566 | 563 |
| 1000 | 28.2 | 18000 | 0.017 | 0.025 | 0.015 | 0.013 | 0.358+j0.246 | 0.025+j0.029 | 4719 | 661 | 638 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch | |
| 673689 | 2 | 8 | 6.81 | 14.88 | 3.56 | 16.41 | 1x8 | 2.03 | 49.50 | 1.52 | 52.55 | 348 | 2585 | 2.5 |
| 652778 | 1 | 19 | 7.59 | 15.67 | 3.56 | 17.20 | 1x6 | 2.03 | 52.73 | 1.52 | 55.78 | 403 | 2970 | 3 |
| 672079 | 1/0 | 10 | 8.53 | 16.61 | 3.56 | 18.14 | 1x6 | 2.79 | 54.76 | 1.52 | 57.81 | 415 | 3249 | 3 |
| 674249 | 2/0 | 12 | 9.55 | 17.63 | 3.56 | 19.15 | 1x6 | 2.79 | 56.95 | 1.52 | 59.99 | 429 | 3528 | 3 |
| TBA | 3/0 | 19 | 10.74 | 18.82 | 3.56 | 20.35 | 1x6 | 2.79 | 58.06 | 1.91 | 61.87 | 423 | 3156 | 3 |
| 672070 | 4/0 | 19 | 12.07 | 20.14 | 3.56 | 21.67 | 1x6 | 2.79 | 62.38 | 1.91 | 66.19 | 461 | 4329 | 3.5 |
| TBA | 250 | 37 | 13.21 | 21.49 | 3.56 | 23.01 | 1x4 | 2.79 | 63.83 | 1.91 | 67.64 | 531 | 3906 | 3.5 |
| 652787 | 350 | 37 | 15.65 | 23.93 | 3.56 | 25.45 | 1x4 | 2.79 | 70.56 | 1.91 | 74.37 | 585 | 5603 | 4 |
| 674257 | 500 | 34 | 18.69 | 27.58 | 3.56 | 29.11 | 1x3 | 2.79 | 79.73 | 2.16 | 84.05 | 685 | 7099 | 4.5 |
| TBA | 750 | 61 | 23.06 | 31.60 | 3.56 | 33.12 | 1x2 | 3.18 | 86.44 | 2.16 | 90.75 | 790 | 7497 | 4.5 |
| TBA | 1000 | 61 | 28.37 | 36.91 | 3.56 | 38.43 | 1x2 | 3.18 | 97.89 | 2.16 | 102.21 | 868 | 9213 | 5.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 368.30 | 5313 | 0.8727 | 1.20 | 0.0134 | 0.0853 | 0.725+j0.540 | 0.365+j0.042 | 2033 | 135 | 157 |
| 1 | 391.16 | 6702 | 0.6923 | 0.95 | 0.0125 | 0.0820 | 0.652+j0.522 | 0.289+j0.040 | 2129 | 154 | 178 |
| 1/0 | 403.86 | 8455 | 0.5479 | 0.75 | 0.0116 | 0.0755 | 0.595+j0.503 | 0.229+j0.038 | 2243 | 176 | 202 |
| 2/0 | 419.10 | 10658 | 0.4364 | 0.60 | 0.0107 | 0.0722 | 0.550+j0.483 | 0.182+j0.037 | 2367 | 204 | 229 |
| 3/0 | 434.34 | 13439 | 0.3445 | 0.47 | 0.0098 | 0.0689 | 0.514+j0.461 | 0.144+j0.036 | 2513 | 234 | 260 |
| 4/0 | 462.28 | 16946 | 0.2756 | 0.38 | 0.0091 | 0.0623 | 0.486+j0.439 | 0.115+j0.034 | 2674 | 268 | 294 |
| 250 | 472.44 | 20025 | 0.2297 | 0.31 | 0.0082 | 0.0623 | 0.467+j0.417 | 0.096+j0.033 | 2838 | 296 | 323 |
| 350 | 520.70 | 28035 | 0.1673 | 0.23 | 0.0073 | 0.0558 | 0.438+j0.381 | 0.070+j0.032 | 3136 | 363 | 386 |
| 500 | 589.28 | 40050 | 0.1181 | 0.16 | 0.0067 | 0.0525 | 0.411+j0.334 | 0.050+j0.031 | 3582 | 447 | 465 |
| 750 | 635.00 | 60075 | 0.0755 | 0.11 | 0.0052 | 0.0459 | 0.383+j0.291 | 0.033+j0.029 | 4071 | 566 | 563 |
| 1000 | 716.28 | 80100 | 0.0558 | 0.08 | 0.0046 | 0.0427 | 0.358+j0.246 | 0.025+j0.029 | 4719 | 661 | 638 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC

