SPEC 26262

HVTECK AL 3/C 140NLEPR TS PVC AIA PVC 8kV 133% CSA

3 Conductor, 140 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:140 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    {SQMTR} {CSA} SOUTHWIRE POWER CABLE {NESC} 3/C XXX AWG COMPACT AL.--- {ALUMAFLEX}® AA8176 X.XX mm (140 mils) TR-XLPE AIA 8KV 133% INS LEVEL 25%TS SUN. RES. 90°C FT4 HL (-40°C) LTGG RoHS
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchAWGmilinchmilinchlb/1000ft
    270.2680.5861400.6468801.955602.0751651
    1190.2980.6161400.67661102.079602.1991901
    1/0190.3360.6541400.71461102.161602.2812061
    2/0190.3760.6941400.75461102.248602.3682245
    3/0190.4220.7401400.80061102.347752.4972537
    4/0190.4740.7921400.85261102.460752.6102804
    250370.5200.8461400.90641102.576752.7263084
    350370.6150.9411401.00141102.781752.9313633
    500370.7351.0611401.12131103.041853.2114479
    750610.9081.2441401.30421253.466853.6365870
    1000611.0601.3961401.45621253.794853.9647056
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    214.511940.2670.3360.0370.0430.708 + j0.4980.336 + j0.0422032135157
    115.415060.2110.2660.0300.0410.640 + j0.480.266 + j0.0402125154178
    1/016.019000.1680.2110.0300.0400.586 + j0.460.211 + j0.0382243176202
    2/016.623950.1330.1670.0300.0380.543 + j0.4390.167 + j0.0372367204229
    3/017.530200.1050.1330.0300.0370.508 + j0.4170.133 + j0.0352509234260
    4/018.338080.0840.1050.0200.0360.479 + j0.3940.105 + j0.0342670268294
    25019.145000.0710.0900.0200.0300.461 + j0.3720.090 + j0.0332838296323
    35020.563000.0500.0650.0200.0300.430 + j0.3370.065 + j0.0323132363386
    50022.590000.0350.0460.0200.0300.401 + j0.2980.046 + j0.0303504447465
    75025.5135000.0200.0300.0140.0300.371 + j0.2500.033 + j0.0294071566563
    100027.7180000.0200.0300.0130.0300.349 + j0.2180.027 + j0.0284542661638
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmAWGmmmmmmmmkg/km
    276.8114.883.5616.4182.0349.661.5252.712457
    1197.5715.653.5617.1762.7952.811.5255.852829
    1/0198.5316.613.5618.1462.7954.891.5257.943067
    2/0199.5517.633.5619.1562.7957.101.5260.153341
    3/01910.7218.803.5620.3262.7959.611.9163.423775
    4/01912.0420.123.5621.6462.7962.481.9166.294173
    2503713.2121.493.5623.0142.7965.431.9169.244589
    3503715.6223.903.5625.4342.7970.641.9174.455406
    5003718.6726.953.5628.4732.7977.242.1681.566665
    7506123.0631.603.5633.1223.1888.042.1692.358736
    10006126.9235.463.5636.9823.1896.372.16100.6910500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2368.3053130.87601.100.01130.14110.708 + j0.4980.336 + j0.0422032135157
    1391.1667020.69230.870.00910.13450.640 + j0.480.266 + j0.0402125154178
    1/0406.4084550.55120.690.00910.13120.586 + j0.460.211 + j0.0382243176202
    2/0421.64106580.43640.550.00910.12470.543 + j0.4390.167 + j0.0372367204229
    3/0444.50134390.34450.440.00910.12140.508 + j0.4170.133 + j0.0352509234260
    4/0464.82169460.27560.340.00610.11810.479 + j0.3940.105 + j0.0342670268294
    250485.14200250.23290.300.00610.09840.461 + j0.3720.090 + j0.0332838296323
    350520.70280350.16400.210.00610.09840.430 + j0.3370.065 + j0.0323132363386
    500571.50400500.11480.150.00610.09840.401 + j0.2980.046 + j0.0303504447465
    750647.70600750.06560.100.00430.09840.371 + j0.2500.033 + j0.0294071566563
    1000703.58801000.06560.100.00400.09840.349 + j0.2180.027 + j0.0284542661638
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E