SPEC 26262

HVTECK AL 3/C 140NLEPR TS PVC AIA PVC 8kV 133% CSA

3 Conductor, 140 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:140 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    {SQMTR} {CSA} SOUTHWIRE POWER CABLE {NESC} 3/C XXX AWG COMPACT AL.--- {ALUMAFLEX}® AA8176 X.XX mm (140 mils) TR-XLPE AIA 8KV 133% INS LEVEL 25%TS SUN. RES. 90°C FT4 HL (-40°C) LTGG RoHS
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    270.2680.5861400.6461x8801.891602.01121514172.5
    1190.2990.6171400.6771x6801.958602.07825315562.5
    1/0190.3360.6541400.7141x61102.098602.21826217063
    2/0190.3760.6941400.7541x61102.185602.30527218643
    3/0190.4230.7411400.8011x61102.286752.43628421213
    4/0190.4750.7931400.8531x61102.398752.54829623493
    250370.520.8461400.9061x41102.513752.66335726253.5
    350370.6160.9421401.0021x41102.72752.8738031053.5
    500370.7361.0621401.1221x31102.98753.1344838184
    750610.9081.2441401.3041x21253.403853.57353150384.5
    1000611.1171.4531401.5131x21253.854854.02458361915.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    214.111940.2660.3650.0340.0260.725+j0.5400.365+j0.0422033135157
    114.515060.2110.2890.0320.0250.652+j0.5220.289+j0.0402129154178
    1/015.519000.1670.2290.0290.0230.595+j0.5030.229+j0.0382243176202
    2/016.123950.1330.1820.0270.0220.550+j0.4830.182+j0.0372367204229
    3/017.130200.1050.1440.0250.0210.514+j0.4610.144+j0.0362513234260
    4/017.838080.0840.1150.0230.0190.486+j0.4390.115+j0.0342674268294
    25018.645000.070.0960.0210.0190.467+j0.4170.096+j0.0332838296323
    35020.163000.0510.070.0180.0170.438+j0.3810.070+j0.0323136363386
    50021.990000.0360.050.0160.0160.413+j0.3410.050+j0.0303507447465
    75025135000.0230.0330.0130.0140.383+j0.2910.033+j0.0294071566563
    100028.2180000.0170.0250.0110.0130.358+j0.2460.025+j0.0294719661638
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    276.8114.883.5616.411x82.0348.031.5251.0832021092.5
    1197.5915.673.5617.201x62.0349.731.5252.7837723162.5
    1/0198.5316.613.5618.141x62.7953.291.5256.3439025393
    2/0199.5517.633.5619.151x62.7955.501.5258.5540527743
    3/01910.7418.823.5620.351x62.7958.061.9161.8742331563
    4/01912.0720.143.5621.671x62.7960.911.9164.7244034963
    2503713.2121.493.5623.011x42.7963.831.9167.6453139063.5
    3503715.6523.933.5625.451x42.7969.091.9172.9056646213.5
    5003718.6926.973.5628.501x32.7975.691.9179.5066756824
    7506123.0631.603.5633.121x23.1886.442.1690.7579074974.5
    10006128.3736.913.5638.431x23.1897.892.16102.2186892135.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2358.1453130.87271.200.01040.08530.725+j0.5400.365+j0.0422033135157
    1368.3067020.69230.950.00980.08200.652+j0.5220.289+j0.0402129154178
    1/0393.7084550.54790.750.00880.07550.595+j0.5030.229+j0.0382243176202
    2/0408.94106580.43640.600.00820.07220.550+j0.4830.182+j0.0372367204229
    3/0434.34134390.34450.470.00760.06890.514+j0.4610.144+j0.0362513234260
    4/0452.12169460.27560.380.00700.06230.486+j0.4390.115+j0.0342674268294
    250472.44200250.22970.310.00640.06230.467+j0.4170.096+j0.0332838296323
    350510.54280350.16730.230.00550.05580.438+j0.3810.070+j0.0323136363386
    500556.26400500.11810.160.00490.05250.413+j0.3410.050+j0.0303507447465
    750635.00600750.07550.110.00400.04590.383+j0.2910.033+j0.0294071566563
    1000716.28801000.05580.080.00340.04270.358+j0.2460.025+j0.0294719661638
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E