SPEC 45264
AL 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Sunlight resistant Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.
Specifications:
Sample Print Legend:
SOUTHWIRE® {UL} XXX AWG AL 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG AL 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {YYYY} PC09-FLRBLGN {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Aluminum Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |||
| 582238 | 8 | 3 | 7 | 0.134 | 45 | 1 x 8 | 60 | 0.666 | 63 | 189 | BK |
| TBA | 6 | 3 | 7 | 0.169 | 45 | 1 x 8 | 60 | 0.685 | 93 | 211 | BK |
| 671633 | 4 | 3 | 7 | 0.213 | 45 | 1 x 6 | 80 | 0.886 | 144 | 379 | BK |
| 670971 | 2 | 3 | 6 | 0.268 | 45 | 1 x 6 | 80 | 0.983 | 214 | 494 | BK |
| 675018 | 1 | 3 | 8 | 0.299 | 55 | 1 x 4 | 80 | 1.123 | 279 | 572 | BK |
| 670963 | 1/0 | 3 | 10 | 0.336 | 55 | 1 x 4 | 80 | 1.173 | 341 | 732 | BK |
| 646672 | 2/0 | 3 | 12 | 0.376 | 55 | 1 x 4 | 80 | 1.236 | 420 | 753 | BK |
| 599619 | 3/0 | 3 | 15 | 0.423 | 55 | 1 x 4 | 80 | 1.337 | 519 | 881 | BK |
| 672057 | 4/0 | 3 | 19 | 0.475 | 55 | 1 x 2 | 80 | 1.45 | 667 | 1069 | BK |
| 646667 | 250 | 3 | 22 | 0.52 | 65 | 1 x 1 | 80 | 1.586 | 793 | 1266 | BK |
| 672257 | 300 | 3 | 21 | 0.57 | 65 | 1 x 2 | 110 | 1.754 | 919 | 1528 | BK |
| 137880 | 350 | 3 | 35 | 0.616 | 65 | 1 x 1 | 110 | 1.853 | 1079 | 1721 | BK |
| 582220 | 400 | 3 | 35 | 0.659 | 65 | 1 x 3/0 | 110 | 1.96 | 1301 | 1995 | BK |
| 563211 | 500 | 3 | 34 | 0.736 | 65 | 1 x 1 | 110 | 2.112 | 1507 | 2246 | BK |
| 582223 | 500 | 3 | 34 | 0.736 | 65 | 1 x 2/0 | 110 | 2.112 | 1554 | 2327 | BK |
| 671494 | 500 | 3 | 34 | 0.736 | 65 | 1 x 250 | 110 | 2.214 | 1665 | 2486 | BK |
| 672259 | 500 | 3 | 34 | 0.736 | 65 | 1 x 4/0 | 110 | 2.223 | 1629 | 2459 | BK |
| 582129 | 600 | 3 | 37 | 0.813 | 80 | 1 x 1/0 | 110 | 2.348 | 1813 | 2790 | BK |
| 679401 | 600 | 3 | 37 | 0.813 | 80 | 1 x 350 | 110 | 2.598 | 2046 | 3076 | BK |
| 587573 | 750 | 3 | 58 | 0.908 | 80 | 1 x 1/0 | 110 | 2.553 | 2241 | 3278 | BK |
| 579924 | 750 | 3 | 58 | 0.908 | 80 | 3 x 2/0 | 110 | 2.553 | 2521 | 3666 | BK |
| 580013 | 750 | 3 | 58 | 0.908 | 80 | 1 x 3/0 | 110 | 2.553 | 2301 | 3324 | BK |
| 671392 | 750 | 3 | 58 | 0.908 | 80 | 1 x 400 | 110 | 2.585 | 2521 | 3620 | BK |
| TBA | 1000 | 3 | 61 | 1.117 | 80 | 1 x 1/0 | 140 | 3.044 | 2923 | 4159 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| 582238 | 8 | 3 | 2.7 | 297 | 1.071 | 1.334 | 0.052 | 40 | 45 |
| TBA | 6 | 3 | 2.7 | 472 | 0.674 | 0.84 | 0.051 | 50 | 55 |
| 671633 | 4 | 3 | 3.5 | 751 | 0.424 | 0.528 | 0.048 | 65 | 75 |
| 670971 | 2 | 3 | 3.9 | 1194 | 0.266 | 0.331 | 0.045 | 90 | 100 |
| 675018 | 1 | 3 | 5.6 | 1506 | 0.211 | 0.263 | 0.046 | 100 | 115 |
| 670963 | 1/0 | 3 | 5.9 | 1900 | 0.167 | 0.208 | 0.044 | 120 | 135 |
| 646672 | 2/0 | 3 | 6.2 | 2395 | 0.133 | 0.166 | 0.043 | 135 | 150 |
| 599619 | 3/0 | 3 | 6.7 | 3020 | 0.105 | 0.131 | 0.042 | 155 | 175 |
| 672057 | 4/0 | 3 | 7.2 | 3808 | 0.084 | 0.105 | 0.041 | 180 | 205 |
| 646667 | 250 | 3 | 7.9 | 4500 | 0.07 | 0.087 | 0.041 | 205 | 230 |
| 672257 | 300 | 3 | 8.8 | 5400 | 0.059 | 0.071 | 0.041 | 230 | 260 |
| 137880 | 350 | 3 | 9.3 | 6300 | 0.051 | 0.064 | 0.04 | 250 | 280 |
| 582220 | 400 | 3 | 9.8 | 7200 | 0.044 | 0.055 | 0.04 | 270 | 305 |
| 563211 | 500 | 3 | 12.7 | 9000 | 0.036 | 0.045 | 0.039 | 310 | 350 |
| 582223 | 500 | 3 | 12.7 | 9000 | 0.036 | 0.045 | 0.039 | 310 | 350 |
| 671494 | 500 | 3 | 13.3 | 9000 | 0.036 | 0.045 | 0.039 | 310 | 350 |
| 672259 | 500 | 3 | 13.3 | 9000 | 0.036 | 0.045 | 0.039 | 310 | 350 |
| 582129 | 600 | 3 | 14.1 | 10800 | 0.03 | 0.038 | 0.039 | 340 | 385 |
| 679401 | 600 | 3 | 15.6 | 10800 | 0.03 | 0.038 | 0.039 | 340 | 385 |
| 587573 | 750 | 3 | 15.3 | 13500 | 0.023 | 0.03 | 0.038 | 385 | 435 |
| 579924 | 750 | 3 | 15.3 | 13500 | 0.023 | 0.03 | 0.038 | 385 | 435 |
| 580013 | 750 | 3 | 15.3 | 13500 | 0.023 | 0.03 | 0.038 | 385 | 435 |
| 671392 | 750 | 3 | 15.5 | 13500 | 0.023 | 0.03 | 0.038 | 385 | 435 |
| TBA | 1000 | 3 | 18.3 | 18000 | 0.017 | 0.023 | 0.037 | 445 | 500 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.