SPEC 45264

AL 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Sunlight resistant Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-58-679 Control Cable Conductor Identification Method 4
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    SOUTHWIRE® {UL} XXX AWG AL 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG AL 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {YYYY} PC09-FLRBLGN {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODAluminum WeightApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    5822388370.134451 x 8600.66663189BK
    TBA6370.169451 x 8600.68593211BK
    6716334370.213451 x 6800.886144379BK
    6709712360.268451 x 6800.983214494BK
    6750181380.299551 x 4801.123279572BK
    6709631/03100.336551 x 4801.173341732BK
    6466722/03120.376551 x 4801.236420753BK
    5996193/03150.423551 x 4801.337519881BK
    6720574/03190.475551 x 2801.456671069BK
    6466672503220.52651 x 1801.5867931266BK
    6722573003210.57651 x 21101.7549191528BK
    1378803503350.616651 x 11101.85310791721BK
    5822204003350.659651 x 3/01101.9613011995BK
    5632115003340.736651 x 11102.11215072246BK
    5822235003340.736651 x 2/01102.11215542327BK
    6714945003340.736651 x 2501102.21416652486BK
    6722595003340.736651 x 4/01102.22316292459BK
    5821296003370.813801 x 1/01102.34818132790BK
    6794016003370.813801 x 3501102.59820463076BK
    5875737503580.908801 x 1/01102.55322413278BK
    5799247503580.908803 x 2/01102.55325213666BK
    5800137503580.908801 x 3/01102.55323013324BK
    6713927503580.908801 x 4001102.58525213620BK
    TBA10003611.117801 x 1/01403.04429234159BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    582238832.72971.0711.3340.0524045
    TBA632.74720.6740.840.0515055
    671633433.57510.4240.5280.0486575
    670971233.911940.2660.3310.04590100
    675018135.615060.2110.2630.046100115
    6709631/035.919000.1670.2080.044120135
    6466722/036.223950.1330.1660.043135150
    5996193/036.730200.1050.1310.042155175
    6720574/037.238080.0840.1050.041180205
    64666725037.945000.070.0870.041205230
    67225730038.854000.0590.0710.041230260
    13788035039.363000.0510.0640.04250280
    58222040039.872000.0440.0550.04270305
    563211500312.790000.0360.0450.039310350
    582223500312.790000.0360.0450.039310350
    671494500313.390000.0360.0450.039310350
    672259500313.390000.0360.0450.039310350
    582129600314.1108000.030.0380.039340385
    679401600315.6108000.030.0380.039340385
    587573750315.3135000.0230.030.038385435
    579924750315.3135000.0230.030.038385435
    580013750315.3135000.0230.030.038385435
    671392750315.5135000.0230.030.038385435
    TBA1000318.3180000.0170.0230.037445500
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 1.000.006

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC