SPEC 45307

CU 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free

Type MC Power Cable 600Volt Four Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polypropylene tape
  6. Armor:Aluminum Interlocked Armor (AIA)
  7. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE, 4-ORANGE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG_DUAL} SOUTHWIRE {UL} 4/C (XX AWG) XX.Xmm2 CU XX MILS XLP 600 VOLTS GW 1 X X AWG CU TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90°C USA -- {NOM}-ANCE Tipo MC XHHW-2 CT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundDiameter Over ArmorJacket ThicknessApprox. ODCopper WeightApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilNo. x AWGinchmilinchlb/1000ftlb/1000ft
    TBA8470.142451 x 100.774500.874206485BK
    5744606470.178451 x 80.875500.98379659BK
    TBA4470.225451 x 80.975501.075521888BK
    5807302470.283451 x 61.128501.2339101280BK
    TBA14190.322551 x 61.258501.35810421558BK
    8902291/04190.362551 x 61.382501.48713991909BK
    TBA2/04190.405551 x 61.459501.55916602271BK
    TBA3/04190.456551 x 41.683501.78320922941BK
    5626054/04190.512551 x 41.815601.94127703535BK
    5579592504370.558651 x 41.964602.0932494159BK
    5514523504370.661651 x 32.203602.32945305626BK
    6685193504370.661651 x 2/02.253752.4147815937BK
    6054105004370.789651 x 22.509752.66764447773BK
    5634076004610.866801 x 22.765752.92276919152BK
    6729896004610.866801 x 4/02.765752.92281469587BK
    TBA7504610.968801 x 13.043753.193935611304BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    TBA846.15280.6530.810.0524044
    574460646.98390.4110.510.0515260
    TBA447.513350.2580.320.0486876
    580730248.621230.1620.2010.04592104
    TBA149.526780.1280.1590.046104116
    8902291/0410.433790.1020.1270.044120136
    TBA2/0410.942590.0820.1020.043140156
    TBA3/0412.553690.0640.0790.042160180
    5626054/0413.667710.0510.0630.041184208
    557959250414.680000.0430.0530.041204232
    551452350416.3112000.0310.0390.04248280
    668519350416.9112000.0310.0390.04248280
    605410500418.7160000.0210.0270.039304344
    563407600420.5192000.0180.0240.039336380
    672989600420.5192000.0180.0240.039336380
    TBA750422.4240000.0140.0190.038380428
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.007