SPEC 45301

CU 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free

Type MC Power Cable 600Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polypropylene tape
  6. Armor:Aluminum Interlocked Armor (AIA)
  7. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • Sample Print Legend:

    {SQFTG_DUAL} SOUTHWIRE {UL} 3/C (1 AWG) XX.Xmm2 CU XX MILS XLP 600 VOLTS GW 1 X X AWG CU TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90°C USA -- {NOM}-ANCE Tipo MC XHHW-2 CT FT4
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundDiameter Over ArmorJacket ThicknessApprox. ODCopper WeightApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilNo. x AWGinchmilinchlb/1000ftlb/1000ft
    6069398370.142451 x 100.728500.833187409BK
    6069476370.178451 x 80.806500.91297552BK
    606954◊4370.225451 x 80.907501.012442718BK
    6718923370.252451 x 60.965501.07574890BK
    560466◊2370.283451 x 61.032501.1377031041BK
    55080113190.322551 x 61.177501.2828651271BK
    560474◊1/03190.362551 x 61.259501.36410701499BK
    560482◊2/03190.405551 x 61.354501.45913271812BK
    890339◊3/03190.456551 x 41.462501.56717002238BK
    383679◊4/03190.512551 x 41.657601.78321102779BK
    6013772503370.558651 x 41.791601.91724693307BK
    383646◊3503370.661651 x 32.005602.13134394437BK
    380618◊5003370.789651 x 22.275752.43248856075BK
    5822745003370.789651 x 4/02.341752.49153386692BK
    8903916003610.866801 x 4/02.508752.66562737555BK
    8904057503610.968801 x 12.784752.94272778988BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    606939835.83960.6530.810.0525055
    606947636.46290.4110.510.0516575
    606954◊437.110010.2580.320.0488595
    671892337.512620.2050.2540.047100115
    560466◊23815920.1620.2010.045115130
    55080113920080.1280.1590.046130145
    560474◊1/039.525340.1020.1270.044150170
    560482◊2/0310.231940.0820.1020.043175195
    890339◊3/031140270.0640.0790.042200225
    383679◊4/0312.550780.0510.0630.041230260
    601377250313.460000.0430.0530.041255290
    383646◊350314.984000.0310.0390.04310350
    380618◊500317120000.0210.0270.039380430
    582274500317.4120000.0210.0270.039380430
    890391600318.7144000.0180.0240.039420475
    890405750320.6180000.0140.0190.038475535
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.