SPEC 45301
CU 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free
Type MC Power Cable 600Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polypropylene tape
- Armor:Aluminum Interlocked Armor (AIA)
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE {UL} 3/C (1 AWG) XX.Xmm2 CU XX MILS XLP 600 VOLTS GW 1 X X AWG CU TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90°C USA -- {NOM}-ANCE Tipo MC XHHW-2 CT FT4
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | inch | mil | inch | lb/1000ft | lb/1000ft | |||
| 606939 | 8 | 3 | 7 | 0.142 | 45 | 1 x 10 | 0.728 | 50 | 0.833 | 187 | 409 | BK |
| 606947 | 6 | 3 | 7 | 0.178 | 45 | 1 x 8 | 0.806 | 50 | 0.91 | 297 | 552 | BK |
| 606954◊ | 4 | 3 | 7 | 0.225 | 45 | 1 x 8 | 0.907 | 50 | 1.012 | 442 | 718 | BK |
| 671892 | 3 | 3 | 7 | 0.252 | 45 | 1 x 6 | 0.965 | 50 | 1.07 | 574 | 890 | BK |
| 560466◊ | 2 | 3 | 7 | 0.283 | 45 | 1 x 6 | 1.032 | 50 | 1.137 | 703 | 1041 | BK |
| 550801 | 1 | 3 | 19 | 0.322 | 55 | 1 x 6 | 1.177 | 50 | 1.282 | 865 | 1271 | BK |
| 560474◊ | 1/0 | 3 | 19 | 0.362 | 55 | 1 x 6 | 1.259 | 50 | 1.364 | 1070 | 1499 | BK |
| 560482◊ | 2/0 | 3 | 19 | 0.405 | 55 | 1 x 6 | 1.354 | 50 | 1.459 | 1327 | 1812 | BK |
| 890339◊ | 3/0 | 3 | 19 | 0.456 | 55 | 1 x 4 | 1.462 | 50 | 1.567 | 1700 | 2238 | BK |
| 383679◊ | 4/0 | 3 | 19 | 0.512 | 55 | 1 x 4 | 1.657 | 60 | 1.783 | 2110 | 2779 | BK |
| 601377 | 250 | 3 | 37 | 0.558 | 65 | 1 x 4 | 1.791 | 60 | 1.917 | 2469 | 3307 | BK |
| 383646◊ | 350 | 3 | 37 | 0.661 | 65 | 1 x 3 | 2.005 | 60 | 2.131 | 3439 | 4437 | BK |
| 380618◊ | 500 | 3 | 37 | 0.789 | 65 | 1 x 2 | 2.275 | 75 | 2.432 | 4885 | 6075 | BK |
| 582274 | 500 | 3 | 37 | 0.789 | 65 | 1 x 4/0 | 2.341 | 75 | 2.491 | 5338 | 6692 | BK |
| 890391 | 600 | 3 | 61 | 0.866 | 80 | 1 x 4/0 | 2.508 | 75 | 2.665 | 6273 | 7555 | BK |
| 890405 | 750 | 3 | 61 | 0.968 | 80 | 1 x 1 | 2.784 | 75 | 2.942 | 7277 | 8988 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| 606939 | 8 | 3 | 5.8 | 396 | 0.653 | 0.81 | 0.052 | 50 | 55 |
| 606947 | 6 | 3 | 6.4 | 629 | 0.411 | 0.51 | 0.051 | 65 | 75 |
| 606954◊ | 4 | 3 | 7.1 | 1001 | 0.258 | 0.32 | 0.048 | 85 | 95 |
| 671892 | 3 | 3 | 7.5 | 1262 | 0.205 | 0.254 | 0.047 | 100 | 115 |
| 560466◊ | 2 | 3 | 8 | 1592 | 0.162 | 0.201 | 0.045 | 115 | 130 |
| 550801 | 1 | 3 | 9 | 2008 | 0.128 | 0.159 | 0.046 | 130 | 145 |
| 560474◊ | 1/0 | 3 | 9.5 | 2534 | 0.102 | 0.127 | 0.044 | 150 | 170 |
| 560482◊ | 2/0 | 3 | 10.2 | 3194 | 0.082 | 0.102 | 0.043 | 175 | 195 |
| 890339◊ | 3/0 | 3 | 11 | 4027 | 0.064 | 0.079 | 0.042 | 200 | 225 |
| 383679◊ | 4/0 | 3 | 12.5 | 5078 | 0.051 | 0.063 | 0.041 | 230 | 260 |
| 601377 | 250 | 3 | 13.4 | 6000 | 0.043 | 0.053 | 0.041 | 255 | 290 |
| 383646◊ | 350 | 3 | 14.9 | 8400 | 0.031 | 0.039 | 0.04 | 310 | 350 |
| 380618◊ | 500 | 3 | 17 | 12000 | 0.021 | 0.027 | 0.039 | 380 | 430 |
| 582274 | 500 | 3 | 17.4 | 12000 | 0.021 | 0.027 | 0.039 | 380 | 430 |
| 890391 | 600 | 3 | 18.7 | 14400 | 0.018 | 0.024 | 0.039 | 420 | 475 |
| 890405 | 750 | 3 | 20.6 | 18000 | 0.014 | 0.019 | 0.038 | 475 | 535 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.008