SPEC 10004

TFN/TFFN Copper

600 Volt. Copper Conductor. PVC Insulation/Nylon Sheath. Heat, Moisture, Oil, and Gasoline Resistant II. Also Rated MTW and AWM.

...

Construction:

  1. Conductor: Solid soft drawn bare copper per ASTM B3 for TFN. Class K bunch-stranded soft drawn bare copper per ASTM B174 for TFFN.
  2. Insulation: Heat and moisture resistant PVC
  3. Sheath:Nylon

Applications and Features:

APPLICATION
Southwire Type TFN/TFFN or MTW or AWM may be used as fixture wire, machine tool wiring, or appliance wiring material as specified in the National Electrical Code® and other applicable codes and standards. Voltage for all applications is 600 volts. Allowable temperatures are as follows:

- TFN/TFFN- Dry locations not to exceed 90°C
- AWM- When rated as appliance wiring material in dry locations, conductor temperatures not to exceed 105°C
- MTW- Wet locations or when exposed to oil at temperatures not to exceed 60°C or dry locations not to exceed 90°C (with ampacity limited to that for 75°C conductor temperature per NFPA 79)

FEATURES
- Gasoline and Oil Resistant II
- MTW- Stranded Constructions Only
- RoHS Compliant

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 66 Fixture Wire
  • UL 758 Standard for Appliance Wiring Material
  • UL 1063 Machine Tool Wiring (MTW)
  • Sample Print Legend:

    E30071 (UL) XX AWG CU TYPE TFFN OR MTW OR GASOLINE AND OIL RESISTANT II OR AWM 600 VOLTS --- RoHS
    Table 1 – Weights and Measurements
    Cond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ftlb/1000ft
    181Solid0.0401550.08046
    161Solid0.0501550.090710
    181160.0451550.08547
    161260.0591550.101710
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeCond. NumberMin Bending RadiusDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    1810.36.6698.0350.036-6
    1610.44.1815.0370.033-8
    1810.37.1488.6130.036-6
    1610.44.4875.4060.033-8
    * Ampacities based on 2023 NEC Table 402.5.
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Table 3 - Stock Code Colors ( / means stripe. Blue/White: Blue with White Stripe)

    Size (Strand)BlackRedBlueWhiteBrownOrangeYellowGrayPinkPurpleTanViolet
    18 (Solid)269779269795269803269787269845269837269829269878269860
    16 (Solid)269886269902269910269894269951269944269936269985269977
    18 (16)270215270231270249270223270280270272270264270314270298270306297549561595
    16 (26)270322270348270355270330270397270389270371270421270405270413297531

    Table 3 Cont. - Stock Code Colors ( / means stripe. Blue/White: Blue with White Stripe)

    Size (Strand)Black/OrangeBlack/YellowBlack/GrayBlack/VioletWhite/BlackWhite/RedWhite/BlueBlue/WhiteGreenBlack/RedBlack/BlueBlack/WhiteBlack/Brown
    18 (Solid)589281558028269811
    16 (Solid)567169269928
    18 (16)587084587087587082587081587091270256587083587085587090587086
    16 (26)270363

    Revision: 1.000.024

    Updated On: Nov. 13, 2024, 1:26 p.m. UTC