SPEC 10004
TFN/TFFN Copper
600 Volt. Copper Conductor. PVC Insulation/Nylon Sheath. Heat, Moisture, Oil, and Gasoline Resistant II. Also Rated MTW and AWM.
Construction:
- Conductor: Solid soft drawn bare copper per ASTM B3 for TFN. Class K bunch-stranded soft drawn bare copper per ASTM B174 for TFFN.
- Insulation: Heat and moisture resistant PVC
- Sheath:Nylon
Applications and Features:
APPLICATION
Southwire Type TFN/TFFN or MTW or AWM may be used as fixture wire, machine tool wiring, or appliance wiring material as specified in the National Electrical Code® and other applicable codes and standards. Voltage for all applications is 600 volts. Allowable temperatures are as follows:
- TFN/TFFN- Dry locations not to exceed 90°C
- AWM- When rated as appliance wiring material in dry locations, conductor temperatures not to exceed 105°C
- MTW- Wet locations or when exposed to oil at temperatures not to exceed 60°C or dry locations not to exceed 90°C (with ampacity limited to that for 75°C conductor temperature per NFPA 79)
FEATURES
- Gasoline and Oil Resistant II
- MTW- Stranded Constructions Only
- RoHS Compliant
Southwire Type TFN/TFFN or MTW or AWM may be used as fixture wire, machine tool wiring, or appliance wiring material as specified in the National Electrical Code® and other applicable codes and standards. Voltage for all applications is 600 volts. Allowable temperatures are as follows:
- TFN/TFFN- Dry locations not to exceed 90°C
- AWM- When rated as appliance wiring material in dry locations, conductor temperatures not to exceed 105°C
- MTW- Wet locations or when exposed to oil at temperatures not to exceed 60°C or dry locations not to exceed 90°C (with ampacity limited to that for 75°C conductor temperature per NFPA 79)
FEATURES
- Gasoline and Oil Resistant II
- MTW- Stranded Constructions Only
- RoHS Compliant
Specifications:
Sample Print Legend:
E30071 (UL) XX AWG CU TYPE TFFN OR MTW OR GASOLINE AND OIL RESISTANT II OR AWM 600 VOLTS --- RoHS
Table 1 – Weights and Measurements
Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | |
18 | 1 | Solid | 0.040 | 15 | 5 | 0.080 | 4 | 6 |
16 | 1 | Solid | 0.050 | 15 | 5 | 0.090 | 7 | 10 |
18 | 1 | 16 | 0.045 | 15 | 5 | 0.085 | 4 | 7 |
16 | 1 | 26 | 0.059 | 15 | 5 | 0.101 | 7 | 10 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Cond. Size | Cond. Number | Min Bending Radius | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | |
18 | 1 | 0.3 | 6.669 | 8.035 | 0.036 | - | 6 |
16 | 1 | 0.4 | 4.181 | 5.037 | 0.033 | - | 8 |
18 | 1 | 0.3 | 7.148 | 8.613 | 0.036 | - | 6 |
16 | 1 | 0.4 | 4.487 | 5.406 | 0.033 | - | 8 |
* Ampacities based on 2023 NEC Table 402.5.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
Table 3 - Stock Code Colors ( / means stripe. Blue/White: Blue with White Stripe)
Size (Strand) | Black | Red | Blue | White | Brown | Orange | Yellow | Gray | Pink | Purple | Tan | Violet |
18 (Solid) | 269779 | 269795 | 269803 | 269787 | 269845 | 269837 | 269829 | 269878 | 269860 | |||
16 (Solid) | 269886 | 269902 | 269910 | 269894 | 269951 | 269944 | 269936 | 269985 | 269977 | |||
18 (16) | 270215 | 270231 | 270249 | 270223 | 270280 | 270272 | 270264 | 270314 | 270298 | 270306 | 297549 | 561595 |
16 (26) | 270322 | 270348 | 270355 | 270330 | 270397 | 270389 | 270371 | 270421 | 270405 | 270413 | 297531 |
Table 3 Cont. - Stock Code Colors ( / means stripe. Blue/White: Blue with White Stripe)
Size (Strand) | Black/Orange | Black/Yellow | Black/Gray | Black/Violet | White/Black | White/Red | White/Blue | Blue/White | Green | Black/Red | Black/Blue | Black/White | Black/Brown |
18 (Solid) | 589281 | 558028 | 269811 | ||||||||||
16 (Solid) | 567169 | 269928 | |||||||||||
18 (16) | 587084 | 587087 | 587082 | 587081 | 587091 | 270256 | 587083 | 587085 | 587090 | 587086 | |||
16 (26) | 270363 |
Revision: 1.000.024