SPEC 10091

CU 300V HVAC Wire Unshielded Thermostat Plenum Rated

CU 300V HDPE Insulation CMP/CL2P PVC Jacket Power Limited Unshielded Thermostat Wire Plenum Rated 75ºC

...

Construction:

  1. Conductor:Solid bare copper per ASTM B3
  2. Insulation:Polyvinyl Chloride PVC
  3. Rip Cord:Rip cord for ease of jacket strip ability
  4. Overall Jacket:Polyvinyl Chloride (PVC) Jacket in White

Applications and Features:

Thermostat Wire is a class 2 power-limited circuit cable for use in thermostat control applications from floor to floor and up access shafts without conduit
  • 300 Voltage
  • ETL Listed Meets UL 444 Type CMP
  • ETL Listed Meets UL 1424
  • ETL Listed Meets UL 13 Type CL2P/li>
  • CSA FT6
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • UL 13 Power-Limited Circuit Cables
  • UL 444 CMP/CL2P
  • RoHS-3 Complies with Latest Directive
  • Sample Print Legend:

    BARON WIRE 55504 18 AWG X/C C{ETL}US MASTER-DESIGN TYPE CMP/CL2P 75{D}C BAROPLEN -- TYPE CMP FT6 -- {MM/DD/YY} {HH:MM}
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insulation ColorInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending Radius
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinch
    18 AWG
    55502◊182SOLID0.04BK,RD5150.14410166.6598.2650.0360.6
    55503◊183SOLID0.04BK,RD,WE5150.15315226.6598.2650.0360.6
    55504◊184SOLID0.04BK,RD,WE,GN5150.16820286.6598.2650.0360.7
    55505◊185SOLID0.04BK,RD,WE,GN,BN5150.18880356.6598.2650.0360.8
    55506◊186SOLID0.04BK,RD,WE,GN,BN,BE5150.20630426.6598.2650.0360.8
    55508◊188SOLID0.04BK,RD,WE,GN,BN,BE,OE,YW5150.22440546.6598.2650.0360.9
    55510◊1810SOLID0.04BK,RD,WE,GN,BN,BE,OE,YW,PE,GY5150.26449686.6598.2650.0361.1
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.021

    Updated On: Dec. 31, 2024, 11:06 p.m. UTC