SPEC 60504

Data-Flex Flexible Metal Conduit

Flexible Metal Conduit. Crush/Corrosion Resistant. Smooth Interior for Easy Pulling.

...

Construction:

  1. Armor:Data-Flex is manufactured with a spiral wound strip of corrosion-resistant, hot-dipped galvanized steel with a heavy zinc coating. The metal strip is helically formed into a continuously interlocked flexible metal conduit that can withstand impact and crushing forces.

Applications and Features:

Data-Flex Flexible Metal Conduit is suitable for the following installations:
  • Suitable for concealed, exposed, or approved raceways
  • Can be used where listed products are not required.

  • Features
  • Provides mechanical protection for conductors and cable
  • Smooth interior for easy wire pulling
  • High strength steel construction
  • Superior crush proof qualities
  • Hot-dipped, heavy zinc coating for rust/corrosion resistance
  • Built in flexibility for simplified positioning
  • Specifications:

  • UL 1 Standard for Safety Flexible Metal Conduit
  • CSA 22.2 No. 56 Flexible metal conduit and liquid-tight flexible metal conduit
  • NFPA 70 (National Electrical Code), Article 350 - Liquidtight Flexible Metal Conduit
  • Data-Flex® Flexible Metal Conduit

    Trade SizeInner Diam (Min/Max)Outer Diam (Min/Max)WeightMinimum Bend Radius
    InchInchInchLb/100ftInch
    5/160.312/0.3370.470/0.51092.5*
    3/80.375/0.3930.560/0.610123*
    1/20.625/0.6450.860/0.920194
    3/40.812/0.8351.045/1.105245
    11.000/1.0401.300/1.380328
    1-1/41.250/1.3001.550/1.6304610
    1-1/21.500/1.5751.850/1.9505412
    22.000/2.0802.350/2.4507516
    2-1/22.52.860/3.0609220
    33.03.360/3.56010924
    3-1/23.53.860/4.06012628
    44.04.360/4.56014332

    * Suggestion only. Non-NEC requirement

    Put Ups

    Trade Size (Inch)25 ft50 ft100 ft150 ft250 ft300 ft400 ft500 ft600 ft1000 ft
    3/8552820015528200255282003
    1/25528210155282103
    3/45528220155282203
    15528230455282305
    1-1/45528240455282406
    1-1/25528250855282515
    25528260855282609
    2-1/255282708
    355282908
    3-1/255283008
    455283108

    Revision: 1.000.003

    Updated On: May 28, 2025, 7:56 p.m. UTC