SPEC 22064

SIMpull® RWU90 Copper 1000 Volt

Single Copper Conductors, XLPE Insulation, 1000V / -40ºC MIN, 90ºC MAX, Sunlight Resistant. SIMpull® technology on sizes #8 and larger. Cable can be installed in conduit without the aid of lubrication. For Direct Burial

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Southwire’s RWU90 is designed for direct earth burial (with protection as required by the inspecting authority). For service entrance above or below ground. The minimum recommended installation temperature is minus 40°C (with suitable handling procedures). Maximum conductor temperature is 90°C. Note: Standard black is sunlight resistant and marked "SR". Standard coloured insulation is not sunlight resistant. SIMpull® technology on sizes #8 and larger. Cable can be installed in conduit without the aid of lubrication.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA AWM I A/B FT1
  • Sample Print Legend:

    SOUTHWIRE{R} XX AWG {NOLUBE}{R} {SIMPULL} RWU90{TM} LL90458 {CSA} (33.6{MM2}) CU RWU90 XLPE 1000 VOLTS -40{D}C SR - PAT www.patentSW.com - RWU90 XXX AWG
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    57836414760GN0.193240.800322.6313.1700.05825
    56325314760WE0.193240.800322.6313.1700.05825
    64674014760RD0.193240.800322.6313.1700.05825
    64760714760BE0.193240.800322.6313.1700.05825
    56657714760YW0.193240.800322.6313.1700.05825
    556978◊14760BK0.197240.800322.6313.1700.05825
    55660312760GY0.217340.800521.6622.0020.05430
    55698212760WE0.217340.800521.6622.0020.05430
    55698112760RD0.217340.800521.6622.0020.05430
    55660412760PE0.217340.800521.6622.0020.05430
    55660112760OE0.217340.800521.6622.0020.05430
    55698012760GN0.217340.800521.6622.0020.05430
    55660212760BN0.217340.800521.6622.0020.05430
    55660012760BE0.217340.800521.6622.0020.05430
    55697912760BK0.217340.800521.6622.0020.05430
    55793210Solid60WE0.227450.900831.0401.2530.05040
    55698310760BK0.239480.900831.0401.2530.05040
    57933810760YW0.239480.900831.0401.2530.05040
    55698410760WE0.239480.900831.0401.2530.05040
    55698610760RD0.239480.900831.0401.2530.05040
    55659810760GN0.239480.900831.0401.2530.05040
    55698710760BE0.239480.900831.0401.2530.05040
    556992◊8780BE0.302771.2001320.6530.7860.05255
    556990◊8780RD0.312791.2001320.6530.7860.05255
    556988◊8780BK0.312791.2001320.6530.7860.05255
    556991◊8780GN0.312791.2001320.6530.7860.05255
    556989◊8780WE0.312791.2001320.6530.7860.05255
    556997◊6780GN0.3481141.4002090.4110.4950.05175
    556994◊6780BK0.3481131.4002090.4110.4950.05175
    643550◊6780YW0.3481141.4002090.4110.4950.05175
    556998◊6780BE0.3481141.4002090.4110.4950.05175
    556996◊6780RD0.3481131.4002090.4110.4950.05175
    556995◊6780WE0.3481131.4002090.4110.4950.05175
    557003◊4780BE0.3951681.6003330.2580.3100.04895
    557000◊4780WE0.3951681.6003330.2580.3100.04895
    557001◊4780RD0.3951681.6003330.2580.3100.04895
    557002◊4780GN0.3951681.6003330.2580.3100.04895
    556999◊4780BK0.3951681.6003330.2580.3100.04895
    557004◊3780BK0.4222051.7004200.2050.2460.047115
    137969◊3780GN0.4222051.7004200.2050.2460.047115
    641557◊3780WE0.4222051.7004200.2050.2460.047115
    557006◊2780WE0.4532521.8005300.1620.1950.045130
    5565962780BE0.4532521.8005300.1620.1950.045130
    571898◊2780GN0.4532521.8005300.1620.1950.045130
    557005◊2780BK0.4532521.8005300.1620.1950.045130
    557007◊2780RD0.4532521.8005300.1620.1950.045130
    137926◊11995BK0.5223202.1006690.1280.1540.046145
    664805◊1/01995GN0.5623942.2008440.1020.1220.044170
    669505◊1/01995WE0.5623942.2008440.1020.1220.044170
    666075◊1/01995RD0.5623932.2008440.1020.1220.044170
    666074◊1/01995BE0.5623932.2008440.1020.1220.044170
    590651◊1/01995BK0.5623942.2008440.1020.1220.044170
    668802◊2/01995BE0.6044852.40010640.0810.0970.043195
    668801◊2/01995RD0.6044852.40010640.0810.0970.043195
    668800◊2/01995WE0.6044852.40010640.0810.0970.043195
    138905◊2/01995GN0.6044852.40010640.0810.0970.043195
    590652◊2/01995BK0.6064852.40010640.0810.0970.043195
    665409◊3/01995GN0.6546002.60013420.0640.0780.042225
    593060◊3/01995BE0.6546002.60013420.0640.0780.042225
    593058◊3/01995WE0.6546002.60013420.0640.0780.042225
    590653◊3/01995BK0.6546002.60013420.0640.0780.042225
    593059◊3/01995RD0.6546002.60013420.0640.0780.042225
    668805◊4/01995RD0.6987382.80016920.0510.0620.041260
    668806◊4/01995BE0.6987392.80016920.0510.0620.041260
    590654◊4/01995BK0.7107462.80016920.0510.0620.041260
    5834404/01995GN0.7107442.80016920.0510.0620.041260
    678382◊4/01995WE0.7107462.80016920.0510.0620.041260
    590655◊25037110BK0.7748753.10020000.0430.0530.041290
    590658◊35037110RD0.87311983.50028000.0310.0390.040350
    590656◊35037110BK0.87311983.50028000.0310.0390.040350
    590657◊35037110BE0.87312083.50028000.0310.0390.040350
    590659◊35037110WE0.89312113.60028000.0310.0390.040350
    590662◊50037110RD0.99816804.00040000.0220.0290.039430
    590661◊50037110BE0.99816814.00040000.0220.0290.039430
    590663◊50037110WE0.99816804.00040000.0220.0290.039430
    590660◊50037110BK0.99816804.00040000.0220.0290.039430
    592347◊60061125BK1.10420175.50048000.0180.0250.039475
    59235060061125BE1.10420195.50048000.0180.0250.039475
    59234860061125RD1.10420175.50048000.0180.0250.039475
    59234960061125WE1.10420185.50048000.0180.0250.039475
    590664◊75061125BK1.20324956.00060000.0140.0220.038535
    671492◊100061125BK1.38133196.90080000.0110.0180.037615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities derived from the 2021 Canadian Electrical Code Table 1 for not more than three insulated copper conductors, rated not more than 5000 V and unshielded, in raceway or cable (based on an ambient temperature of 30 °C)
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    5783641471.52GN4.903620.321428.6310.400.190325
    5632531471.52WE4.903620.321428.6310.400.190325
    6467401471.52RD4.903620.321428.6310.400.190325
    6476071471.52BE4.903620.321428.6310.400.190325
    5665771471.52YW4.903620.321428.6310.400.190325
    556978◊1471.52BK5.003620.321428.6310.400.190325
    5566031271.52GY5.515120.322315.456.570.177230
    5569821271.52WE5.515120.322315.456.570.177230
    5569811271.52RD5.515120.322315.456.570.177230
    5566041271.52PE5.515120.322315.456.570.177230
    5566011271.52OE5.515120.322315.456.570.177230
    5569801271.52GN5.515120.322315.456.570.177230
    5566021271.52BN5.515120.322315.456.570.177230
    5566001271.52BE5.515120.322315.456.570.177230
    5569791271.52BK5.515120.322315.456.570.177230
    55793210Solid1.52WE5.776722.863693.414.110.164040
    5569831071.52BK6.077122.863693.414.110.164040
    5793381071.52YW6.077122.863693.414.110.164040
    5569841071.52WE6.077122.863693.414.110.164040
    5569861071.52RD6.077122.863693.414.110.164040
    5565981071.52GN6.077122.863693.414.110.164040
    5569871071.52BE6.077122.863693.414.110.164040
    556992◊872.03BE7.6711530.485872.142.580.170655
    556990◊872.03RD7.9211830.485872.142.580.170655
    556988◊872.03BK7.9211830.485872.142.580.170655
    556991◊872.03GN7.9211830.485872.142.580.170655
    556989◊872.03WE7.9211830.485872.142.580.170655
    556997◊672.03GN8.8417035.569301.351.620.167375
    556994◊672.03BK8.8416835.569301.351.620.167375
    643550◊672.03YW8.8417035.569301.351.620.167375
    556998◊672.03BE8.8417035.569301.351.620.167375
    556996◊672.03RD8.8416835.569301.351.620.167375
    556995◊672.03WE8.8416835.569301.351.620.167375
    557003◊472.03BE10.0325040.6414820.851.020.157595
    557000◊472.03WE10.0325040.6414820.851.020.157595
    557001◊472.03RD10.0325040.6414820.851.020.157595
    557002◊472.03GN10.0325040.6414820.851.020.157595
    556999◊472.03BK10.0325040.6414820.851.020.157595
    557004◊372.03BK10.7230543.1818690.670.810.1542115
    137969◊372.03GN10.7230543.1818690.670.810.1542115
    641557◊372.03WE10.7230543.1818690.670.810.1542115
    557006◊272.03WE11.5137545.7223590.530.640.1476130
    556596272.03BE11.5137545.7223590.530.640.1476130
    571898◊272.03GN11.5137545.7223590.530.640.1476130
    557005◊272.03BK11.5137545.7223590.530.640.1476130
    557007◊272.03RD11.5137545.7223590.530.640.1476130
    137926◊1192.41BK13.2647653.3429770.420.510.1509145
    664805◊1/0192.41GN14.2758655.8837560.330.400.1444170
    669505◊1/0192.41WE14.2758655.8837560.330.400.1444170
    666075◊1/0192.41RD14.2758555.8837560.330.400.1444170
    666074◊1/0192.41BE14.2758555.8837560.330.400.1444170
    590651◊1/0192.41BK14.2758655.8837560.330.400.1444170
    668802◊2/0192.41BE15.3472260.9647350.270.320.1411195
    668801◊2/0192.41RD15.3472260.9647350.270.320.1411195
    668800◊2/0192.41WE15.3472260.9647350.270.320.1411195
    138905◊2/0192.41GN15.3472260.9647350.270.320.1411195
    590652◊2/0192.41BK15.3972260.9647350.270.320.1411195
    665409◊3/0192.41GN16.6189366.0459720.210.260.1378225
    593060◊3/0192.41BE16.6189366.0459720.210.260.1378225
    593058◊3/0192.41WE16.6189366.0459720.210.260.1378225
    590653◊3/0192.41BK16.6189366.0459720.210.260.1378225
    593059◊3/0192.41RD16.6189366.0459720.210.260.1378225
    668805◊4/0192.41RD17.73109871.1275290.170.200.1345260
    668806◊4/0192.41BE17.73110071.1275290.170.200.1345260
    590654◊4/0192.41BK18.03111071.1275290.170.200.1345260
    5834404/0192.41GN18.03110771.1275290.170.200.1345260
    678382◊4/0192.41WE18.03111071.1275290.170.200.1345260
    590655◊250372.79BK19.66130278.7489000.140.170.1345290
    590658◊350372.79RD22.17178388.90124600.100.130.1312350
    590656◊350372.79BK22.17178388.90124600.100.130.1312350
    590657◊350372.79BE22.17179888.90124600.100.130.1312350
    590659◊350372.79WE22.68180291.44124600.100.130.1312350
    590662◊500372.79RD25.352500101.60178000.070.100.1280430
    590661◊500372.79BE25.352502101.60178000.070.100.1280430
    590663◊500372.79WE25.352500101.60178000.070.100.1280430
    590660◊500372.79BK25.352500101.60178000.070.100.1280430
    592347◊600613.18BK28.043002139.70213600.060.080.1280475
    592350600613.18BE28.043005139.70213600.060.080.1280475
    592348600613.18RD28.043002139.70213600.060.080.1280475
    592349600613.18WE28.043003139.70213600.060.080.1280475
    590664◊750613.18BK30.563713152.40267000.050.070.1247535
    671492◊1000613.18BK35.084939175.26356000.040.060.1214615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities derived from the 2021 Canadian Electrical Code Table 1 for not more than three insulated copper conductors, rated not more than 5000 V and unshielded, in raceway or cable (based on an ambient temperature of 30 °C)
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Table 3 – Colors
    Cond. SizeStrandingColor
    AWG or kcmilnumBlackGreenWhiteRedBlueYellowOrangePurpleBrownGray
    147556978578364563253646740647607566577
    127556979556980556982556981556600556601556604556602556603
    101 (solid)557932
    107556983556598556984556986556987579338
    87556991556991556989556990556992
    67556994556997556995556996556998643550
    47556999557002557000557001557003
    37557004137969641557
    27557005571898557006557007556596
    119137926
    1/019590651664805669505666075666074
    2/019590652138905668800668801668802
    3/019590653593058593059593060
    4/019590654583440678382668805668806
    25037590655
    35037590656590659590658590657
    50037590660590663590662590661
    60061592347592349592348592350
    75061590664
    100061671492