SPEC 22061

RW90 Copper Circuit Sizes (14, 12 & 10 AWG)

Copper Conductor, 600V, 90°C MAX, -40°C MIN. All Sizes and Colors are Sunlight Resistant.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Single copper conductor with low temperature, moisture resisting XLPE (cross linked polyethylene) insulation. All sizes are Sunlight Resistant in all colors and packaging. This product meets the current RoHS requirements. No lead is added or used in manufacturing.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA SUN RES - for Sunlight Resistant rating
  • Sample Print Legend:

    SOUTHWIRE& LL90458 (CSA) 12 AWG CU RW90 XLPE 600 VOLTS (-40{D}C) SR
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    95611014Solid300.128160.500322.6313.1700.05825
    95617714Solid300.128160.500322.6313.1700.05825
    95614414Solid300.128160.500322.6313.1700.05825
    95625014Solid300.128160.500322.6313.1700.05825
    95627614Solid300.128160.500322.6313.1700.05825
    95620114Solid300.128160.500322.6313.1700.05825
    95623514Solid300.128160.500322.6313.1700.05825
    55791714Solid300.128160.500322.6313.1700.05825
    955617147300.135170.500322.6313.1700.05825
    955245147300.135170.500322.6313.1700.05825
    955666147300.135170.500322.6313.1700.05825
    955708147300.135170.500322.6313.1700.05825
    951731147300.135170.500322.6313.1700.05825
    557924147300.135170.500322.6313.1700.05825
    955682147300.135170.500322.6313.1700.05825
    55786112Solid300.144240.600521.6622.0020.05430
    95610212Solid300.144240.600521.6622.0020.05430
    95616912Solid300.144240.600521.6622.0020.05430
    95622712Solid300.144240.600521.6622.0020.05430
    95624312Solid300.144240.600521.6622.0020.05430
    95626812Solid300.144240.600521.6622.0020.05430
    95613612Solid300.144240.600521.6622.0020.05430
    95619312Solid300.144240.600521.6622.0020.05430
    955609127300.153250.600521.6622.0020.05430
    955658127300.153250.600521.6622.0020.05430
    955674127300.153250.600521.6622.0020.05430
    955237127300.153250.600521.6622.0020.05430
    557923127300.153250.600521.6622.0020.05430
    955690127300.153250.600521.6622.0020.05430
    951749127300.153250.600321.6622.0020.05430
    95615110Solid300.165370.700831.0401.2530.05040
    55793010Solid300.165370.700831.0401.2530.05040
    95609410Solid300.165370.700831.0401.2530.05040
    55792910Solid300.165370.700831.0401.2530.05040
    95612810Solid300.165370.700831.0401.2530.05040
    95618510Solid300.165370.700831.0401.2530.05040
    95621910Solid300.165370.700831.0401.2530.05040
    951756107300.175380.700521.0401.2530.05040
    955641107300.177390.700831.0401.2530.05040
    557921107300.177390.700831.0401.2530.05040
    955591107300.177390.700831.0401.2530.05040
    557920107300.177390.700831.0401.2530.05040
    557922107300.177390.700831.0401.2530.05040
    955229107300.177390.700831.0401.2530.05040
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    95611014Solid0.763.252412.701428.6310.400.190325
    95617714Solid0.763.252412.701428.6310.400.190325
    95614414Solid0.763.252412.701428.6310.400.190325
    95625014Solid0.763.252412.701428.6310.400.190325
    95627614Solid0.763.252412.701428.6310.400.190325
    95620114Solid0.763.252412.701428.6310.400.190325
    95623514Solid0.763.252412.701428.6310.400.190325
    55791714Solid0.763.252412.701428.6310.400.190325
    9556171470.763.432512.701428.6310.400.190325
    9552451470.763.432512.701428.6310.400.190325
    9556661470.763.432512.701428.6310.400.190325
    9557081470.763.432512.701428.6310.400.190325
    9517311470.763.432512.701428.6310.400.190325
    5579241470.763.432512.701428.6310.400.190325
    9556821470.763.432512.701428.6310.400.190325
    55786112Solid0.763.663615.242315.456.570.177230
    95610212Solid0.763.663615.242315.456.570.177230
    95616912Solid0.763.663615.242315.456.570.177230
    95622712Solid0.763.663615.242315.456.570.177230
    95624312Solid0.763.663615.242315.456.570.177230
    95626812Solid0.763.663615.242315.456.570.177230
    95613612Solid0.763.663615.242315.456.570.177230
    95619312Solid0.763.663615.242315.456.570.177230
    9556091270.763.893715.242315.456.570.177230
    9556581270.763.893715.242315.456.570.177230
    9556741270.763.893715.242315.456.570.177230
    9552371270.763.893715.242315.456.570.177230
    5579231270.763.893715.242315.456.570.177230
    9556901270.763.893715.242315.456.570.177230
    9517491270.763.893715.241425.456.570.177230
    95615110Solid0.764.195517.783693.414.110.164040
    55793010Solid0.764.195517.783693.414.110.164040
    95609410Solid0.764.195517.783693.414.110.164040
    55792910Solid0.764.195517.783693.414.110.164040
    95612810Solid0.764.195517.783693.414.110.164040
    95618510Solid0.764.195517.783693.414.110.164040
    95621910Solid0.764.195517.783693.414.110.164040
    9517561070.764.445717.782313.414.110.164040
    9556411070.764.505817.783693.414.110.164040
    5579211070.764.505817.783693.414.110.164040
    9555911070.764.505817.783693.414.110.164040
    5579201070.764.505817.783693.414.110.164040
    5579221070.764.505817.783693.414.110.164040
    9552291070.764.505817.783693.414.110.164040
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.

    Table 3 - Stock Code Colors

    Size (Strand)ColorStock Number
    14 (Solid)BK956110
    14 (Solid)RD956177
    14 (Solid)WE956144
    14 (Solid)BN956250
    14 (Solid)YW956276
    14 (Solid)GN956201
    14 (Solid)BE956235
    14 (Solid)OE557917
    14 (7)GN955617
    14 (7)RD955245
    14 (7)BE955666
    14 (7)YW955708
    14 (7)BK951731
    14 (7)OE557924
    14 (7)BN955682
    12 (Solid)OE557861
    12 (Solid)BK956102
    12 (Solid)RD956169
    12 (Solid)BE956227
    12 (Solid)BN956243
    12 (Solid)YW956268
    12 (Solid)WE956136
    12 (Solid)GN956193
    12 (7)BK951749
    12 (7)GN955609
    12 (7)BE955658
    12 (7)BN955674
    12 (7)RD955237
    12 (7)OE557923
    12 (7)YW955690
    10 (Solid)RD956151
    10 (Solid)OE557930
    10 (Solid)BK956094
    10 (Solid)BN557929
    10 (Solid)WE956128
    10 (Solid)GN956185
    10 (Solid)BE956219
    10 (7)BK951756
    10 (7)BE955641
    10 (7)OE557921
    10 (7)GN955591
    10 (7)BN557920
    10 (7)YW557922
    10 (7)RD955229

    Revision: 1.000.011

    Updated On: Nov. 8, 2024, 7:10 p.m. UTC