SPEC 13055

Access Control CMP Shielded

Access Control Doors. 300 Volts 75ºC. Shielded CMP/CL3P

...

Construction:

  1. Door Contact:Stranded bare copper, Two Conductor #22 AWG Black and Red with overall aluminum foil shield. Overall white jacket with green stripe
  2. Lock Power:Stranded bare copper, Four Conductor #18 AWG Black, Red, White and Green with overall aluminum foil shield. Overall white jacket with purple stripe
  3. Card Reader:Stranded bare copper. Three pair with aluminum foil shield, Black and Red, Green and White, Orange and Brown. Overall white jacket with yellow stripe
  4. Request Exit/Spare:Four Conductor #22 AWG Black, Red, White and Green with overall aluminum foil shield. Overall white jacket with Orange stripe
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Jacket: Yellow PVC jacket

Applications and Features:

Access control doors with four functions, typically device dependent. General purpose low voltage and power-limited systems' circuits to NEC Articles 725 and 800

  • Flame Test: UL 1666 or NFPA 262
  • Voltage: 300 Volts
  • Temperature: 75ºC
  • Specifications:

  • UL 1424 Cables for Power-Limited Fire-Alarm Circuits
  • UL 13 Power-Limited Circuit Cables
  • UL 444 Communications Cables (22 AWG - 16 AWG)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    ACCESS CONTROL CABLE 18/4C + 22/3PR SHLD + 22/2C + 22/4C E57497 c{UL}US CMP/CL3P/FPLP -- CMP FT6 MADE IN USA ROHS-2 COMPLIANT -- {MM/DD/YY} {HH:MM} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    CMP/CL3P - Shielded
    Stock #DescriptionSizeNumber of ConductorsNominal Overall DiameterOverall WeightUL/NEC
    AWGIncheslbs/1000 ft
    H91601-122/3PR STR BC OAS - CARD READER223/PR0.412102CMP/CL3P
    18/4C STR BC OAS - LOCK POWER184/C
    22/4C STR BC OAS - REQUEST EXIT224/C
    22/2C STR BC OAS - DOOR CONTACT222/C

    Revision: 1.000.006