SPEC 13146

Category 6E 550 MHz CMP-LP

...

Construction:

  1. Conductor:Bare solid copper
  2. Insulation:Fluorinated Polyethylene FPE
  3. Separator:Spline separator cabled and jacketed
  4. Rip Cord:Rip cord for ease of jacket removal
  5. Jacket:Flame Retardant Polyvinyl Chloride PVC.

Applications and Features:

Southwire Cat 6E unshielded twisted pair cable is a high performance data communication cable. This ethernet cable is designed for indoor and riser network installations type CMP (Plenum rated communication cable), may be used in Ethernet Networking system, PoE applications, Video MPEG4 / M-JPEG/ Digital / Analog / Baseband / Broadband and other Multimedia Voice applications.

  • DC Resistance: <9.38 ohm/100m
  • DC Resistance Unbalance: <5.00%
  • Mutual Capacitance: <5.60 nF/100m
  • Capacitance Unbalance (Pair to Ground): <330 pF/100m
  • Insulation Resistance: >500 MOhm/100m
  • Impedance (mean): >100+/- 15% (1 < freq < 250MHz)
  • Propagation Delay Skew: <45 nano sec /100m
  • Specifications:

  • UL 444 Listed CMP
  • IEEE 802.3 and IEC 61156-5 Ed. 2.0
  • RoHS-3 Complies with European Directive 2015/863
  • NFPA 262
  • TIA/EIA 568.D.2 test to 550MHz, beyond 250MHz only for reference
  • NEC Article 800
  • Sample Print Legend:

    6EP CAT 6E SOUTHWIRE ® TAPPAN™ I99997 E118871 LBI 23AWG 4PR UTP TYPE CMP LP (0.6A) 105C C(UL)US LISTED ETL VERIFIED TO TIA/EIA 568.D.2 CATEGORY 6 RoHS 2 COMPLIANT YYMMDD 0000FT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeNumber of PairsJacket ThicknessApprox. ODApprox. Weight
    AWG/Kcmilpairmilinchlb/1000ft
    I99997234140.22831
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeNumber of PairsJacket ThicknessApprox. ODApprox. Weight
    AWG/Kcmilpairmmmmlb/km
    I999972340.365.7946

    Table 3 – Electrical Perforamce
    Freq.AttenuationNEXTACRPSNEXTPSACRACRFPS ACRFRL
    (MHz)(dB/100m)(dB/100m)(dB/100m)(dB/100m)(dB/100m)(dB/100m)(dB/100m)(ns/100m)
    Std.Avg.Std.Avg."Std"Avg.Min.Avg."Std"Avg.Std.Avg.Min.Avg.Min.Avg.
    121.674.397.772.396.172.390.170.388.567.891.964.8/td>82.820.033.2
    43.83.565.186.561.383.063.179.959.376.455.579.752.571.323.137.7
    85.35.060.981.755.676.758.975.153.670.149.973.146.965.224.537.6
    106.15.759.180.953.075.257.173.951.068.247.571.244.563.425.037.4
    167.57.256.377.548.870.354.370.646.863.443.766.740.759.425.037.6
    208.58.154.777.146.270.052.769.744.261.641.664.538.657.025.038.8
    259.69.153.274.743.665.651.267.941.658.839.762.836.754.924.337.2
    31.2510.710.351.873.541 .163.249.866.439.156.137.860.534.853.023.638.1
    62.515.414.647.375.931.961.345.362.129.947.531.855.228.846.321.536.6
    10019.818.944.366.324.547.442.358.922.540.027.849.324.841.420.133.3
    20029.027.339.861.810.834.537.854.78.827.421.842.318.834.318.028.9
    25032.830.738.360.35.529.636.353.33.522.619.839.516.830.717.328.8
    300- -33.8- -58.7- -24.9- -51.4- -17.6- -35.8- -26.5- -28.2
    400- -39.6- -56.3- -16.7- -49.9- -10.3- -29.0- -20.4- -25.5
    500- -44.7- -54.8- -10.1- -46.7- -2.0- -21.9- -13.3- -25.4
    550- -46.8- -54.4- -7.6- -46.3- -0.0- -19.5- -11.1- -24.2
    600- -48.8- -53.9- -5.1- -45.8- -(2.5)- -17.1- -8.8- -22.9

    Attenuation:
    Std. is a TIA 568C.2 Maximum (also called “Insertion Loss”)         Lower is better.
    NEXT:
    Std. is a TIA 568C.2 Minimum. (Near End Crosstalk)         Higher is better.
    ACR:
    NEXT minus Attenuation ; (“Attenuation to Crosstalk Ratio”)         Higher is better.
    SNEXT:
    Std. is a TIA 568C.2 Minimum. (Power Sum Near End Crosstalk)         Higher is better.
    PSACR:
    PSNEXT minus Attenuation ; (“Attenuation to PSNEXT Ratio”)         Higher is better.
    ACRF:
    Std. is a TIA 568C.2 Minimum. (Attenuation Crosstalk Ratio at Far End)         Higher is better.
    PSACRF:
    Std. is a TIA 568C.2 Minimum. (Power Sum Atten.’ to Crosstalk Ratio)         Higher is better.
    RL:
    Std. is a TIA 568C.2 Minimum. (Return Loss)         Higher is better.

    Revision: 1.000.145

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC