SPEC 80213
MV-105 35kV AL 100% TRXLPE One-Third (Based on Short Circuit) HI-DRI-PLUS® Renewable (Solar or Wind)
Moisture Blocked Aluminum Conductors. TRXLP Insulation. One-Third Concentric Neutrals. XLPE Jacket

Construction:
- Conductor:Moisture Blocked 1350 H16/H26 Aluminum, Class B Compressed or Compressed Unilay Stranded
- Strand Shield:Semi-conducting Crosslinked Polyethylene
- Insulation:Tree Retardant Crosslinked Polyethylene (TRXLP)
- Insulation Shield:Strippable Semi-conducting Crosslinked Polyethylene
- Concentric Neutral:Annealed Copper Wires Helically Applied One-Third Concentric Neutral
- Overall Jacket & Water Block:HI-DRI-PLUS® Water Swellable Powder Black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes
Applications and Features:
- Predominately used for renewable projects with wind or solar applications.
- Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
- To be used at conductor temperature not to exceed 105ºC normal operation.
- UL listed MV-105
- The concentric neutral counts and sizes listed in Table 1 are based on the ICEA P-45-482 short circuit calculation of an MV-90 design. The short circuit value in Table 1 is calculated using a higher thermal limit of a crosslinked XLPE jacket MV-105 design.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE(R) HI-DRI-PLUS(R) (UL) XXX KCMIL AL 345 MILS TRXLPE TYPE MV-105 35KV 100% INSUL LEVEL -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | inch | mil | inch | No. x AWG | Ω/1000ft | mil | inch | lb/1000ft | inch | lb | |
| 629775 | 1/0 (19) | 0.352 | 1.072 | 345 | 1.182 | 7x16 | 0.736 | 50 | 1.384 | 742 | 6.9 | 633 |
| 662111 | 4/0 (19) | 0.498 | 1.218 | 345 | 1.328 | 13x16 | 0.396 | 50 | 1.53 | 991 | 7.6 | 1269 |
| 626308 | 4/0 (19) | 0.498 | 1.218 | 345 | 1.328 | 9x14 | 0.36 | 50 | 1.556 | 1026 | 7.8 | 1269 |
| 662685 | 350 (37) | 0.661 | 1.391 | 345 | 1.501 | 14x14 | 0.231 | 75 | 1.783 | 1409 | 8.9 | 2100 |
| 662101 | 500 (37) | 0.789 | 1.519 | 345 | 1.629 | 29x16 | 0.178 | 75 | 1.885 | 1677 | 9.4 | 3000 |
| 629794 | 500 (37) | 0.789 | 1.519 | 345 | 1.629 | 18x14 | 0.18 | 75 | 1.911 | 1704 | 9.6 | 3000 |
| 607595 | 500 (37) | 0.789 | 1.519 | 345 | 1.629 | 18x14 | 0.18 | 75 | 1.911 | 1704 | 9.6 | 3000 |
| 626328 | 500 (37) | 0.789 | 1.519 | 345 | 1.629 | 12x12 | 0.171 | 75 | 1.945 | 1763 | 9.7 | 3000 |
| 459248 | 500 (37) | 0.789 | 1.525 | 345 | 1.675 | 19x14 | 0.171 | 75 | 1.953 | 1930 | 9.8 | 3000 |
| 626338 | 750 (61) | 0.968 | 1.708 | 345 | 1.848 | 18x12 | 0.114 | 75 | 2.164 | 2325 | 13 | 4500 |
| 607594 | 1000 (61) | 1.084 | 1.857 | 345 | 1.997 | 23x12 | 0.089 | 75 | 2.313 | 2789 | 13.9 | 6000 |
| 456692 | 1000 (61) | 1.084 | 1.857 | 345 | 1.997 | 15x10 | 0.085 | 75 | 2.355 | 2867 | 14.1 | 6000 |
| 456402 | 1250 (61) | 1.25 | 2 | 345 | 2.14 | 19x10 | 0.067 | 75 | 2.498 | 3367 | 15 | 7500 |
| 607763 | 1250 (91) | 1.25 | 2.001 | 345 | 2.141 | 18x10 | 0.071 | 75 | 2.499 | 3343 | 15 | 7500 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Pulling tension based on pulling eye directly connected to conductor
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 (19) | 0.167 | 0.208 | 0.069 | 0.053 | 0.560+j0.375 | 0.209+j0.058 | 2273 | 160 | 195 |
| 4/0 (19) | 0.084 | 0.115 | 0.056 | 0.048 | 0.408+j0.189 | 0.116+j0.052 | 4222 | 235 | 285 |
| 4/0 (19) | 0.084 | 0.115 | 0.056 | 0.048 | 0.392+j0.168 | 0.117+j0.053 | 4660 | 235 | 285 |
| 350 (37) | 0.051 | 0.07 | 0.046 | 0.045 | 0.273+j0.093 | 0.072+j0.050 | 7249 | 315 | 370 |
| 500 (37) | 0.036 | 0.05 | 0.041 | 0.042 | 0.214+j0.065 | 0.053+j0.047 | 9417 | 380 | 445 |
| 500 (37) | 0.036 | 0.05 | 0.041 | 0.042 | 0.215+j0.067 | 0.053+j0.047 | 9321 | 380 | 445 |
| 500 (37) | 0.036 | 0.05 | 0.041 | 0.042 | 0.215+j0.067 | 0.053+j0.047 | 9321 | 380 | 445 |
| 500 (37) | 0.036 | 0.05 | 0.041 | 0.042 | 0.207+j0.063 | 0.053+j0.047 | 9863 | 380 | 445 |
| 500 (37) | 0.036 | 0.05 | 0.041 | 0.043 | 0.208+j0.063 | 0.053+j0.048 | 9838 | 380 | 445 |
| 750 (61) | 0.023 | 0.033 | 0.035 | 0.04 | 0.142+j0.040 | 0.038+j0.044 | 14794 | 470 | 530 |
| 1000 (61) | 0.017 | 0.025 | 0.033 | 0.039 | 0.112+j0.032 | 0.031+j0.042 | 18904 | 530 | 585 |
| 1000 (61) | 0.017 | 0.025 | 0.033 | 0.04 | 0.108+j0.032 | 0.031+j0.042 | 19597 | 530 | 585 |
| 1250 (61) | 0.014 | 0.022 | 0.029 | 0.038 | 0.088+j0.026 | 0.029+j0.040 | 24823 | ||
| 1250 (91) | 0.014 | 0.022 | 0.029 | 0.038 | 0.092+j0.027 | 0.029+j0.040 | 23517 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | mm | mm | mm | No. x AWG | Ω/km | mm | mm | kg/km | mm | newton | |
| 629775 | 1/0 (19) | 8.94 | 27.23 | 8.76 | 30.02 | 7x16 | 2.41 | 1.27 | 35.15 | 1104 | 175.26 | 2817 |
| 662111 | 4/0 (19) | 12.65 | 30.94 | 8.76 | 33.73 | 13x16 | 1.30 | 1.27 | 38.86 | 1475 | 193.04 | 5647 |
| 626308 | 4/0 (19) | 12.65 | 30.94 | 8.76 | 33.73 | 9x14 | 1.18 | 1.27 | 39.52 | 1527 | 198.12 | 5647 |
| 662685 | 350 (37) | 16.79 | 35.33 | 8.76 | 38.13 | 14x14 | 0.76 | 1.91 | 45.29 | 2097 | 226.06 | 9345 |
| 662101 | 500 (37) | 20.04 | 38.58 | 8.76 | 41.38 | 29x16 | 0.58 | 1.91 | 47.88 | 2496 | 238.76 | 13350 |
| 629794 | 500 (37) | 20.04 | 38.58 | 8.76 | 41.38 | 18x14 | 0.59 | 1.91 | 48.54 | 2536 | 243.84 | 13350 |
| 607595 | 500 (37) | 20.04 | 38.58 | 8.76 | 41.38 | 18x14 | 0.59 | 1.91 | 48.54 | 2536 | 243.84 | 13350 |
| 626328 | 500 (37) | 20.04 | 38.58 | 8.76 | 41.38 | 12x12 | 0.56 | 1.91 | 49.40 | 2624 | 246.38 | 13350 |
| 459248 | 500 (37) | 20.04 | 38.73 | 8.76 | 42.55 | 19x14 | 0.56 | 1.91 | 49.61 | 2872 | 248.92 | 13350 |
| 626338 | 750 (61) | 24.59 | 43.38 | 8.76 | 46.94 | 18x12 | 0.37 | 1.91 | 54.97 | 3460 | 330.20 | 20025 |
| 607594 | 1000 (61) | 27.53 | 47.17 | 8.76 | 50.72 | 23x12 | 0.29 | 1.91 | 58.75 | 4150 | 353.06 | 26700 |
| 456692 | 1000 (61) | 27.53 | 47.17 | 8.76 | 50.72 | 15x10 | 0.28 | 1.91 | 59.82 | 4267 | 358.14 | 26700 |
| 456402 | 1250 (61) | 31.75 | 50.80 | 8.76 | 54.36 | 19x10 | 0.22 | 1.91 | 63.45 | 5011 | 381.00 | 33375 |
| 607763 | 1250 (91) | 31.75 | 50.83 | 8.76 | 54.38 | 18x10 | 0.23 | 1.91 | 63.47 | 4975 | 381.00 | 33375 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Pulling tension based on pulling eye directly connected to conductor
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 (19) | 0.5479 | 0.68 | 0.0210 | 0.1739 | 0.560+j0.375 | 0.209+j0.058 | 2273 | 160 | 195 |
| 4/0 (19) | 0.2756 | 0.38 | 0.0171 | 0.1575 | 0.408+j0.189 | 0.116+j0.052 | 4222 | 235 | 285 |
| 4/0 (19) | 0.2756 | 0.38 | 0.0171 | 0.1575 | 0.392+j0.168 | 0.117+j0.053 | 4660 | 235 | 285 |
| 350 (37) | 0.1673 | 0.23 | 0.0140 | 0.1476 | 0.273+j0.093 | 0.072+j0.050 | 7249 | 315 | 370 |
| 500 (37) | 0.1181 | 0.16 | 0.0125 | 0.1378 | 0.214+j0.065 | 0.053+j0.047 | 9417 | 380 | 445 |
| 500 (37) | 0.1181 | 0.16 | 0.0125 | 0.1378 | 0.215+j0.067 | 0.053+j0.047 | 9321 | 380 | 445 |
| 500 (37) | 0.1181 | 0.16 | 0.0125 | 0.1378 | 0.215+j0.067 | 0.053+j0.047 | 9321 | 380 | 445 |
| 500 (37) | 0.1181 | 0.16 | 0.0125 | 0.1378 | 0.207+j0.063 | 0.053+j0.047 | 9863 | 380 | 445 |
| 500 (37) | 0.1181 | 0.16 | 0.0125 | 0.1411 | 0.208+j0.063 | 0.053+j0.048 | 9838 | 380 | 445 |
| 750 (61) | 0.0755 | 0.11 | 0.0107 | 0.1312 | 0.142+j0.040 | 0.038+j0.044 | 14794 | 470 | 530 |
| 1000 (61) | 0.0558 | 0.08 | 0.0101 | 0.1280 | 0.112+j0.032 | 0.031+j0.042 | 18904 | 530 | 585 |
| 1000 (61) | 0.0558 | 0.08 | 0.0101 | 0.1312 | 0.108+j0.032 | 0.031+j0.042 | 19597 | 530 | 585 |
| 1250 (61) | 0.0459 | 0.07 | 0.0088 | 0.1247 | 0.088+j0.026 | 0.029+j0.040 | 24823 | ||
| 1250 (91) | 0.0459 | 0.07 | 0.0088 | 0.1247 | 0.092+j0.027 | 0.029+j0.040 | 23517 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Revision: 1.000.023