SPEC 80213

MV-105 35kV AL 100% TRXLPE One-Third (Based on Short Circuit) HI-DRI-PLUS® Renewable (Solar or Wind)

Moisture Blocked Aluminum Conductors. TRXLP Insulation. One-Third Concentric Neutrals. XLPE Jacket

...

Construction:

  1. Conductor:Moisture Blocked 1350 H16/H26 Aluminum, Class B Compressed or Compressed Unilay Stranded
  2. Strand Shield:Semi-conducting Crosslinked Polyethylene
  3. Insulation:Tree Retardant Crosslinked Polyethylene (TRXLP)
  4. Insulation Shield:Strippable Semi-conducting Crosslinked Polyethylene
  5. Concentric Neutral:Annealed Copper Wires Helically Applied One-Third Concentric Neutral
  6. Overall Jacket & Water Block:HI-DRI-PLUS® Water Swellable Powder Black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes

Applications and Features:

  • Predominately used for renewable projects with wind or solar applications.
  • Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
  • To be used at conductor temperature not to exceed 105ºC normal operation.
  • UL listed MV-105
  • The concentric neutral counts and sizes listed in Table 1 are based on the ICEA P-45-482 short circuit calculation of an MV-90 design. The short circuit value in Table 1 is calculated using a higher thermal limit of a crosslinked XLPE jacket MV-105 design.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • UL 1072 Medium-Voltage Power Cables
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE(R) HI-DRI-PLUS(R) (UL) XXX KCMIL AL 345 MILS TRXLPE TYPE MV-105 35KV 100% INSUL LEVEL -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    6297751/0 (19)0.3521.0723451.1827x160.736501.3847426.9633
    6621114/0 (19)0.4981.2183451.32813x160.396501.539917.61269
    6263084/0 (19)0.4981.2183451.3289x140.36501.55610267.81269
    662685350 (37)0.6611.3913451.50114x140.231751.78314098.92100
    662101500 (37)0.7891.5193451.62929x160.178751.88516779.43000
    629794500 (37)0.7891.5193451.62918x140.18751.91117049.63000
    607595500 (37)0.7891.5193451.62918x140.18751.91117049.63000
    626328500 (37)0.7891.5193451.62912x120.171751.94517639.73000
    459248500 (37)0.7891.5253451.67519x140.171751.95319309.83000
    626338750 (61)0.9681.7083451.84818x120.114752.1642325134500
    6075941000 (61)1.0841.8573451.99723x120.089752.313278913.96000
    4566921000 (61)1.0841.8573451.99715x100.085752.355286714.16000
    4564021250 (61)1.2523452.1419x100.067752.4983367157500
    6077631250 (91)1.252.0013452.14118x100.071752.4993343157500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedanceShort Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (19)0.1670.2080.0690.0530.560+j0.3750.209+j0.0582273160195
    4/0 (19)0.0840.1150.0560.0480.408+j0.1890.116+j0.0524222235285
    4/0 (19)0.0840.1150.0560.0480.392+j0.1680.117+j0.0534660235285
    350 (37)0.0510.070.0460.0450.273+j0.0930.072+j0.0507249315370
    500 (37)0.0360.050.0410.0420.214+j0.0650.053+j0.0479417380445
    500 (37)0.0360.050.0410.0420.215+j0.0670.053+j0.0479321380445
    500 (37)0.0360.050.0410.0420.215+j0.0670.053+j0.0479321380445
    500 (37)0.0360.050.0410.0420.207+j0.0630.053+j0.0479863380445
    500 (37)0.0360.050.0410.0430.208+j0.0630.053+j0.0489838380445
    750 (61)0.0230.0330.0350.040.142+j0.0400.038+j0.04414794470530
    1000 (61)0.0170.0250.0330.0390.112+j0.0320.031+j0.04218904530585
    1000 (61)0.0170.0250.0330.040.108+j0.0320.031+j0.04219597530585
    1250 (61)0.0140.0220.0290.0380.088+j0.0260.029+j0.04024823
    1250 (91)0.0140.0220.0290.0380.092+j0.0270.029+j0.04023517
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    6297751/0 (19)8.9427.238.7630.027x162.411.2735.151104175.262817
    6621114/0 (19)12.6530.948.7633.7313x161.301.2738.861475193.045647
    6263084/0 (19)12.6530.948.7633.739x141.181.2739.521527198.125647
    662685350 (37)16.7935.338.7638.1314x140.761.9145.292097226.069345
    662101500 (37)20.0438.588.7641.3829x160.581.9147.882496238.7613350
    629794500 (37)20.0438.588.7641.3818x140.591.9148.542536243.8413350
    607595500 (37)20.0438.588.7641.3818x140.591.9148.542536243.8413350
    626328500 (37)20.0438.588.7641.3812x120.561.9149.402624246.3813350
    459248500 (37)20.0438.738.7642.5519x140.561.9149.612872248.9213350
    626338750 (61)24.5943.388.7646.9418x120.371.9154.973460330.2020025
    6075941000 (61)27.5347.178.7650.7223x120.291.9158.754150353.0626700
    4566921000 (61)27.5347.178.7650.7215x100.281.9159.824267358.1426700
    4564021250 (61)31.7550.808.7654.3619x100.221.9163.455011381.0033375
    6077631250 (91)31.7550.838.7654.3818x100.231.9163.474975381.0033375
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (19)0.54790.680.02100.17390.560+j0.3750.209+j0.0582273160195
    4/0 (19)0.27560.380.01710.15750.408+j0.1890.116+j0.0524222235285
    4/0 (19)0.27560.380.01710.15750.392+j0.1680.117+j0.0534660235285
    350 (37)0.16730.230.01400.14760.273+j0.0930.072+j0.0507249315370
    500 (37)0.11810.160.01250.13780.214+j0.0650.053+j0.0479417380445
    500 (37)0.11810.160.01250.13780.215+j0.0670.053+j0.0479321380445
    500 (37)0.11810.160.01250.13780.215+j0.0670.053+j0.0479321380445
    500 (37)0.11810.160.01250.13780.207+j0.0630.053+j0.0479863380445
    500 (37)0.11810.160.01250.14110.208+j0.0630.053+j0.0489838380445
    750 (61)0.07550.110.01070.13120.142+j0.0400.038+j0.04414794470530
    1000 (61)0.05580.080.01010.12800.112+j0.0320.031+j0.04218904530585
    1000 (61)0.05580.080.01010.13120.108+j0.0320.031+j0.04219597530585
    1250 (61)0.04590.070.00880.12470.088+j0.0260.029+j0.04024823
    1250 (91)0.04590.070.00880.12470.092+j0.0270.029+j0.04023517
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.

    Revision: 1.000.023