SPEC 80105

Max Storm™ Overhead Conductor – ZTACSR/TW/MA5

...

Construction:

  1. Core:Stranded ultra-high-strength steel core with a zinc-5% aluminum-mischmetal alloy coating for corrosion protection
  2. Stranding:Thermal-resistant aluminum-zirconium (Al-Zr) trapezoidal-shaped wires with 60% conductivity

Applications and Features:

Max Storm™ overhead conductor is a shaped-wire, compact, thermal-resistant aluminum-alloy conductor reinforced with an ultra-high-strength steel core. The Al-Zr strands provide elevated-temperature capability while retaining strength, and the MA5 core supports higher stringing tensions and demanding mechanical loads.

The trapezoidal-wire construction reduces conductor diameter relative to comparable round-wire constructions, helping reduce ice accumulation and wind loading. Max Storm is designed for transmission lines where extreme ice, high wind, long spans, or clearance preservation govern conductor and structure design.

The combination of thermal-resistant Al-Zr strands, compact geometry, and an ultra-high-strength mischmetal-coated core provides high-temperature capacity together with mechanical ruggedness for system-hardening applications.

Continuous operating temperature - 210°C
Emergency operating temperature - 240°C

Specifications:

  • ASTM B500 Standard Specification for Metallic Coated or Aluminum-Clad Stranded Steel Core for Use in Overhead Electrical Conductors
  • ASTM B779 Standard Specification for Shaped Wire Compact Concentric-Lay-Stranded Aluminum Conductors, Steel-Reinforced (ACSR/TW)
  • ASTM B941 Standard Specification for Heat Resistant Aluminum-Zirconium Alloy Wire for Electrical Purposes
  • ASTM B958 Standard Specification for Extra-High-Strength and Ultra-High-Strength Class A Zinc–5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Use in Overhead Electrical Conductors
  • Area Equal to Standard ACSR Conductor - Weights, Measurements, Electrical and Engineering Data
    Stock NumberCode WordConductor SizeType No.StrandingCross-Sectional AreaLayers of Al-ZrDiameterWeightRated Breaking StrengthDC Resistance @ 20°C
    Steel StrandsSteel CoreComplete Conductor
    Al-ZrTotalAl-ZrTotal
    kcmilAl-Zr/Stin²in²inininlb/1000 ftlb/1000 ftlbΩ/mile
    TBAPartridge/TW/Max Storm266.81614/70.20950.243620.07880.23640.595250.6366.014,0000.3422
    TBAMerlin/TW/Max Storm336.4614/10.26420.278920.13670.13670.630315.3364.99,5800.2746
    TBALinnet/TW/Max Storm336.41616/70.26420.307220.08840.26520.659316.1461.717,7000.2713
    TBAOriole/TW/Max Storm336.42316/70.26420.325920.10590.31770.692317.6526.522,2000.2701
    TBAIbis/TW/Max Storm397.51620/70.31220.363020.09610.28830.725373.5545.520,4000.2296
    TBALark/TW/Max Storm397.52316/70.31220.385020.11510.34530.740375.3621.826,0000.2286
    TBAFlicker/TW/Max Storm477.01318/70.37460.423220.09400.28200.776447.7612.221,0000.1920
    TBAHawk/TW/Max Storm477.01618/70.37460.435620.10530.31590.790448.1654.624,3000.1914
    TBAHen/TW/Max Storm477.02320/70.37460.462020.12610.37830.820450.3746.230,8000.1905
    TBAParakeet/TW/Max Storm556.51318/70.43710.493720.10150.30450.840522.4714.024,5000.1646
    TBADove/TW/Max Storm556.51620/70.43710.508320.11380.34140.850522.9763.928,3000.1640
    TBAEagle/TW/Max Storm556.52320/70.43710.539120.13620.40860.870525.5870.836,0000.1633
    TBASquab/TW/Max Storm605.01620/70.47520.552520.11860.35580.885568.5830.230,8000.1509
    TBATeal/TW/Max Storm605.02320/190.47520.583520.08520.42600.916571.3938.739,1000.1503
    TBASwift/TW/Max Storm636.0327/10.49950.513430.13290.13290.850598.4645.314,5000.1463
    TBARook/TW/Max Storm636.01320/70.49950.564220.10850.32550.893597.0816.028,0000.1440
    TBAGrosbeak/TW/Max Storm636.01620/70.49950.580820.12160.36480.909597.6872.832,0000.1435
    TBAScoter/TW/Max Storm636.02322/70.49950.616020.14560.43680.942600.5994.940,6000.1429
    TBAEgret/TW/Max Storm636.02322/190.49950.613520.08740.43700.942600.5987.241,1000.1430
    TBAStarling/TW/Max Storm715.51620/70.56200.653520.12900.38700.958672.3982.135,7000.1276
    TBARedwing/TW/Max Storm715.52320/190.56200.690020.09260.46300.994675.6111044,7000.1271
    TBATern/TW/Max Storm795.0720/70.62440.667620.08860.26580.960745.2891.525,2000.1160
    TBAPuffin/TW/Max Storm795.01018/70.62440.685720.10560.31680.980745.9953.429,5000.1156
    TBACondor/TW/Max Storm795.01320/70.62440.705320.12130.36390.993746.3102034,3000.1152
    TBADrake/TW/Max Storm795.01620/70.62440.726120.13600.40801.010747.0109139,7000.1148
    TBAMallard/TW/Max Storm795.02322/190.62440.766820.09770.48851.050750.6123449,8000.1144
    TBACanary/TW/Max Storm900.01320/70.70690.798520.12910.38731.055844.9115538,9000.1018
    TBAPhoenix/TW/Max Storm954.0530/70.74930.787830.08370.25111.044897.7102826,6000.0972
    TBARail/TW/Max Storm954.0732/70.74930.801130.09710.29131.061898.6107429,7000.0971
    TBACardinal/TW/Max Storm954.01320/70.74930.846420.13290.39871.080895.5122441,2000.0960
    TBACanvasback/TW/Max Storm954.02324/190.74930.920120.10700.53501.149900.8148059,7000.0953
    TBASnowbird/TW/Max Storm1033.5530/70.81170.853530.08720.26161.089972.5111428,4000.0898
    TBAOrtolan/TW/Max Storm1033.5734/70.81170.867830.10100.30301.102973.4116332,2000.0896
    TBACurlew/TW/Max Storm1033.51322/70.81170.916920.13830.41491.131970.1132644,6000.0886
    TBAAvocet/TW/Max Storm1113.0530/70.87410.919030.09040.27121.1301047119930,2000.0834
    TBABluejay/TW/Max Storm1113.0734/70.87410.934630.10490.31471.1431048125334,7000.0832
    TBAFinch/TW/Max Storm1113.01338/190.87410.985030.08620.43101.1901051142748,1000.0828
    TBAOxbird/TW/Max Storm1192.5530/70.93660.984830.09360.28081.1701122128532,3000.0778
    TBABunting/TW/Max Storm1192.5734/70.93661.001330.10850.32551.1811123134236,7000.0777
    TBAGrackle/TW/Max Storm1192.51338/190.93661.055330.08920.44601.2251126152951,5000.0773
    TBAScissortail/TW/Max Storm1272.0530/70.99901.050430.09670.29011.2031197137134,5000.0729
    TBABittern/TW/Max Storm1272.0738/70.99901.068130.11210.33631.2241198143239,6000.0728
    TBAPheasant/TW/Max Storm1272.01339/190.99901.125630.09210.46051.2601201163153,7000.0725
    TBADipper/TW/Max Storm1351.5736/71.06151.134830.11550.34651.2561273152141,6000.0686
    TBAMartin/TW/Max Storm1351.51342/191.06151.195930.09490.47451.3001276173257,1000.0682
    TBABobolink/TW/Max Storm1431.0736/71.12391.201630.11890.35671.2901348161144,0000.0647
    TBAPlover/TW/Max Storm1431.01340/191.12391.266330.09770.48851.3371351183459,9000.0644
    TBALapwing/TW/Max Storm1590.0736/71.24881.335130.12530.37591.3581498179048,5000.0583
    TBAFalcon/TW/Max Storm1590.01342/191.24881.407130.10300.51501.4101501203866,6000.0580
    TBAChukar/TW/Max Storm1780.0838/191.39801.512030.08740.43701.4451674206159,5000.0519
    TBABluebird/TW/Max Storm2156.0864/191.69331.831140.09610.48051.6082045251271,1000.0432

    Diameter Equal to Standard ACSR Conductor - Weights, Measurements, Electrical and Engineering Data
    Stock NumberCode WordConductor SizeType No.StrandingACSR with Equal DiameterCross-Sectional AreaLayers of Al-ZrDiameterWeightRated Breaking StrengthDC Resistance @ 20°C
    Steel StrandsSteel CoreComplete Conductor
    Code WordSizeStrandingAl-ZrTotalAl-ZrTotal
    kcmilAl-Zr/StkcmilAl-Zr/Stin²in²inininlb/1000 ftlb/1000 ftlbΩ/mile
    TBAMonongahela/TW/Max Storm405.1614/1Merlin336.418/10.31820.336320.15200.15200.680379.7440.711,6000.2279
    TBACalumet/TW/Max Storm565.31620/7Hawk477.026/70.44400.516220.11460.34380.860531.2775.628,8000.1615
    TBAMohawk/TW/Max Storm571.71318/7Flicker477.024/70.44900.507320.10300.30900.850536.6734.025,2000.1602
    TBAOswego/TW/Max Storm664.81620/7Dove556.526/70.52210.607220.12440.37320.927624.6912.733,5000.1373
    TBAMystic/TW/Max Storm666.61320/7Parakeet556.524/70.52350.591420.11110.33330.913625.7855.629,4000.1374
    TBAWabash/TW/Max Storm762.81620/7Grosbeak636.026/70.59910.696520.13310.39930.990716.7104638,1000.1197
    TBAMaumee/TW/Max Storm768.21320/7Rook636.024/70.60330.681820.11950.35850.977721.0986.833,6000.1192
    TBANechako/TW/Max Storm768.9327/1Swift636.036/10.60390.622030.15200.15200.930723.5784.517,5000.1210
    TBAFraser/TW/Max Storm946.71034/7Puffin795.022/70.74350.816730.11540.34621.077892.5114035,2000.0976
    TBAKettle/TW/Max Storm957.2732/7Tern795.045/70.75180.803830.09730.29191.060901.6107829,8000.0968
    TBASuwannee/TW/Max Storm959.61622/7Drake795.026/70.75370.876220.14930.44791.110901.7131647,3000.0951
    TBAColumbia/TW/Max Storm966.21322/7Condor795.054/70.75890.857320.13380.40141.092907.0124041,7000.0948
    TBAGenesee/TW/Max Storm1158.0734/7Rail954.045/70.90950.973430.10780.32341.1651091130736,3000.0800
    TBAHudson/TW/Max Storm1158.41324/7Cardinal954.054/70.90981.028120.14670.44011.1961087148849,5000.0791
    TBACheyenne/TW/Max Storm1168.1530/7Phoenix954.042/70.91740.964530.09260.27781.1551099125931,6000.0794
    TBAYukon/TW/Max Storm1233.61338/19Curlew1033.554/70.96891.092530.09100.45501.2451165158452,3000.0747
    TBANelson/TW/Max Storm1257.1736/7Ortolan1033.545/70.98731.055630.11150.33451.2131184141538,7000.0737
    TBACatawba/TW/Max Storm1272.0530/7Snowbird1033.542/70.99901.050430.09670.29011.2031197137134,5000.0729
    TBAThames/TW/Max Storm1334.61338/19Finch1113.054/191.04821.181230.09440.47201.2901260171155,9000.0691
    TBAMackenzie/TW/Max Storm1359.7738/7Bluejay1113.045/71.06791.141830.11590.34771.2601281153141,8000.0681
    TBATruckee/TW/Max Storm1372.5530/7Avocet1113.042/71.07801.133430.10040.30121.2481292148037,2000.0676
    TBAMerrimack/TW/Max Storm1433.61339/19Grackle1192.554/191.12591.268630.09780.48901.3401354183860,1000.0643
    TBAMiramichi/TW/Max Storm1455.3736/7Bunting1192.545/71.14301.222230.12000.36001.3021371163944,4000.0637
    TBASt. Croix/TW/Max Storm1467.8533/7Oxbird1192.542/71.15281.212430.10410.31231.2921381158339,9000.0632
    TBARio Grande/TW/Max Storm1533.31338/19Pheasant1272.054/191.20431.357130.10120.50601.3801448196664,3000.0601
    TBAPotomac/TW/Max Storm1557.4736/7Bittern1272.045/71.22321.307930.12410.37231.3501467175447,5000.0595
    TBAPlatte/TW/Max Storm1569.0533/7Scissortail1272.042/71.23231.295730.10740.32221.3341476169142,5000.0591
    TBAPecos/TW/Max Storm1622.01339/19Martin1351.554/191.27391.442830.10640.53201.4201531210469,9000.0568
    TBASchuylkill/TW/Max Storm1657.4736/7Dipper1351.545/71.30171.391830.12800.38401.3861561186650,6000.0559
    TBAJames/TW/Max Storm1730.61339/19Plover1431.054/191.35921.531630.10750.53751.4701634221972,5000.0533
    TBAPee Dee/TW/Max Storm1758.6738/7Bobolink1431.045/71.38121.476830.13190.39571.4301656198053,7000.0527
    TBACumberland/TW/Max Storm1926.91342/19Falcon1590.054/191.51341.705030.11330.56651.5501819246980,7000.0478
    TBAAthabaska/TW/Max Storm1949.6744/7Lapwing1590.045/71.53121.637730.13920.41761.5041836219759,7000.0475
    TBAPowder/TW/Max Storm2153.8864/19Chukar1780.084/191.69161.829440.09610.48051.5962043251071,0000.0432
    TBASantee/TW/Max Storm2627.3864/19Bluebird2156.084/192.06352.231840.10620.53101.7612492306385,8000.0354

    Revision: 1.000.002