SPEC 46302
CU Compressed 15kV NLEPR Insulation 133% IL Black SIM-PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial
Type MV-105 Single Conductor Copper, 220 Mil No Lead Ethylene Propylene Rubber (NL-EPR) Lead-Free EAM 133% Insulation Level, Tape Shield, SIMpull Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and B8 (tinned copper optional per ASTM B33)
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:15kV, 133% insulation level, 220 mil No Lead Ethylene Propylene Rubber (NL-EPR) / No-Lead Ethylene Alkene Copolymer (EAM)
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Overall Jacket:SIMpull® Polyvinyl Chloride (PVC)
Applications and Features:
Southwire’s 15kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), aerially supported by a messenger and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -40°C for cold bend and cold impact and marked with "LTGG" when CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lb/ft maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemicals, oils and acids and are flame retardant. Cable Tray CT rated 1/0 AWG and larger.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE SIMpull® POWER CABLE {UL} XXX AWG CU 220 MILS NL-EPR 15KV 133% INS LEVEL 25%TS MV-105 FOR CT USE SUN RES {NESC} -- {CSA} XXX AWG CU 5.59mm (220 mils) NL-EPR 15KV 133% INS LEVEL 25%TS MV68.10 SR 105{D}C FT4 -25°C LTDD -- PAT www.patentSW.com -- RoHS
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Diameter Over Insulation | Diameter Over Insulation Shield | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Max Pull Tension | Min Bending Radius | Conduit Size |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | inch | inch | mil | inch | lb/1000ft | lb/1000ft | lb | inch | inch | |
953638◊ | 2 | 7 | 0.282 | 0.755 | 0.815 | 80 | 0.995 | 271 | 640 | 530 | 11.9 | 3.0 |
955104 | 1 | 19 | 0.322 | 0.800 | 0.860 | 80 | 1.040 | 328 | 722 | 669 | 12.4 | 3.0 |
955989◊ | 1/0 | 19 | 0.361 | 0.840 | 0.900 | 80 | 1.080 | 398 | 816 | 844 | 12.9 | 3.0 |
955997◊ | 2/0 | 19 | 0.405 | 0.884 | 0.944 | 80 | 1.124 | 487 | 929 | 1064 | 13.4 | 3.5 |
956003 | 3/0 | 19 | 0.456 | 0.934 | 0.994 | 80 | 1.174 | 597 | 1069 | 1342 | 14.0 | 3.5 |
956011◊ | 4/0 | 19 | 0.512 | 0.990 | 1.050 | 80 | 1.230 | 738 | 1242 | 1692 | 14.7 | 3.5 |
956029◊ | 250 | 37 | 0.558 | 1.044 | 1.104 | 80 | 1.284 | 860 | 1398 | 2000 | 15.4 | 4.0 |
956037◊ | 350 | 37 | 0.661 | 1.147 | 1.207 | 80 | 1.387 | 1177 | 1775 | 2800 | 16.6 | 4.0 |
956045◊ | 500 | 37 | 0.766 | 1.252 | 1.312 | 80 | 1.492 | 1648 | 2307 | 4000 | 17.9 | 4.5 |
139631** | 500 | 37 | 0.789 | 1.275 | 1.335 | 80 | 1.515 | 1648 | 2322 | 4000 | 18.2 | 4.5 |
643755◊ | 600 | 61 | 0.865 | 1.362 | 1.422 | 80 | 1.602 | 1964 | 2694 | 4800 | 19.2 | 4.5 |
956052◊ | 750 | 61 | 0.968 | 1.464 | 1.524 | 110 | 1.764 | 2435 | 3323 | 6000 | 21.1 | 5.0 |
956060◊ | 1000 | 61 | 1.117 | 1.613 | 1.673 | 110 | 1.913 | 3218 | 4202 | 8000 | 22.9 | 5.5 |
581886 | 1250 | 91 | 1.250 | 1.780 | 1.840 | 110 | 2.080 | 4002 | 5118 | 10000 | 24.9 | 6.0 |
567443 | 1500 | 91 | 1.370 | 1.930 | 1.990 | 110 | 2.230 | 4785 | 6006 | 12000 | 26.7 | |
550811 | 2000 | 127 | 1.583 | 2.143 | 2.203 | 110 | 2.443 | 6345 | 7716 | 16000 | 29.3 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Conduit size based on 3 phase 40% fill-factor without ground
** Tinned Copper
** Tinned Copper
Table 2 – Electrical and Engineering Data
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90/105°C | Allowable Ampacity In Air 90/105°C |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
2 | 0.162 | 0.204 | 0.051 | 0.051 | 0.346 + j0.234 | 0.024 + j0.037 | 2571 | 155/165 | 195/215 |
1 | 0.128 | 0.162 | 0.047 | 0.049 | 0.353 + j0.248 | 0.024 + j0.036 | 2695 | 175/185 | 225/250 |
1/0 | 0.102 | 0.128 | 0.043 | 0.047 | 0.353 + j0.248 | 0.024 + j0.036 | 2816 | 200/215 | 260/290 |
2/0 | 0.081 | 0.102 | 0.040 | 0.045 | 0.353 + j0.248 | 0.024 + j0.036 | 2952 | 230/245 | 300/335 |
3/0 | 0.064 | 0.081 | 0.037 | 0.043 | 0.353 + j0.248 | 0.024 + j0.036 | 3110 | 260/275 | 345/385 |
4/0 | 0.051 | 0.065 | 0.034 | 0.042 | 0.353 + j0.248 | 0.024 + j0.036 | 3284 | 295/315 | 400/445 |
250 | 0.043 | 0.056 | 0.032 | 0.041 | 0.354 + j0.255 | 0.020 + j0.031 | 3451 | 325/345 | 445/495 |
350 | 0.031 | 0.041 | 0.028 | 0.039 | 0.354 + j0.255 | 0.020 + j0.031 | 3770 | 390/415 | 550/610 |
500 | 0.022 | 0.030 | 0.025 | 0.037 | 0.354 + j0.255 | 0.020 + j0.031 | 4167 | 465/500 | 685/765 |
500 | 0.022 | 0.030 | 0.025 | 0.037 | 0.354 + j0.255 | 0.020 + j0.031 | 4167 | 465/500 | 685/765 |
600 | 0.018 | 0.026 | 0.023 | 0.036 | 0.365 + j0.269 | 0.027 + j0.036 | 4433 | 505/544 | 765/855 |
750 | 0.014 | 0.023 | 0.021 | 0.035 | 0.355 + j0.242 | 0.031 + j0.041 | 4752 | 565/610 | 885/990 |
1000 | 0.011 | 0.019 | 0.019 | 0.034 | 0.355 + j0.242 | 0.031 + j0.042 | 5214 | 640/690 | 1060/1185 |
1250 | 0.009 | 0.018 | 0.017 | 0.033 | 0.449 + j0.302 | 0.102 + j0.05 | 5638 | 715/770 | 1210/1350 |
1500 | 0.007 | 0.017 | 0.016 | 0.032 | 0.498 + j0.463 | 0.128 + j0.041 | 6010 | 815/880 | 1345/1500 |
2000 | 0.005 | 0.017 | 0.014 | 0.031 | 0.458 + j0.337 | 0.103 + j0.05 | 6670 | 940/1010 | 1575/1755 |
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.
Revision: 1.000.018
Updated On: Oct. 3, 2025, 5:48 p.m. UTC