SPEC 81265

35kV AL 100% EPR (EAM) LCT LLDPE

Single Conductor, 345 Mils Ethylene Propylene Rubber (EPR) / Ethylene Alkene Copolymer (EAM), 100% Insulation Level, Longitudinally Corrugated Tape Shield, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Moisture blocked class B compressed Aluminum ASTM B231 1350 ¾ hard H16/H26 ( Non Moisture Blocked Optional )
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:345 Mils Ethylene Propylene Rubber (EPR) / Ethylene Alkene Copolymer (EAM) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Tape Shield:10 mils Longitudinally Corrugated Tape Shield
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, black with red extruded stripes; PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 35kV cables are suited for use in wet and dry areas, conduits, ducts, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation. 140°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Rural Utility Standard RUS 1728F-U1 or 1728.204 (Electric standards and specifications for materials and construction)
  • UL 1072 Listed as MV 90 When Specified
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] AL 35000 VOLTS EPR INSULATION 345 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/Kcmilinchinchmilinchmilinchlb/1000ftinchlb
    TBA1/0 (Solid)0.3241.0523451.132801.39287016.7633
    TBA1/0 (19)0.3511.0793451.159801.41989417.0633
    TBA2/0 (19)0.3951.1233451.203801.46395917.6798
    TBA3/0 (19)0.4431.1713451.251801.511103318.11006
    TBA4/0 (19)0.4981.2263451.306801.566112318.81269
    TBA250 (37)0.5581.2943451.374801.634122219.61500
    TBA350 (37)0.6611.3973451.4771101.797151221.62100
    TBA500 (37)0.7891.5253451.6051101.925177223.13000
    TBA750 (61)0.9681.7143451.7941102.114220825.44500
    663041#1000 (61)1.1171.8573451.9371102.257271927.16000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    # Solid Black Jacket
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence ImpedancePositive Sequence ImpedanceShort Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (Solid)0.1020.1280.0550.0550.36363.10.403 + j0.1620.129 + j0.0564405160195
    1/0 (19)0.1670.2110.0530.0540.38066.00.481 + j0.1570.212 + j0.0544497160195
    2/0 (19)0.1330.1670.0490.0520.40670.60.431 + j0.1480.168 + j0.0524646185220
    3/0 (19)0.1050.1320.0460.0500.43575.60.389 + j0.1390.133 + j0.0504808210250
    4/0 (19)0.0840.1050.0430.0480.46881.30.354 + j0.1310.106 + j0.0494994235280
    250 (37)0.0710.0900.0390.0460.50888.30.330 + j0.1210.091 + j0.0475225
    350 (37)0.0500.0650.0350.0450.56898.70.293 + j0.1090.067 + j0.0455573315370
    500 (37)0.0350.0460.0310.0420.643111.70.260 + j0.0960.048 + j0.0436007380435
    750 (61)0.0240.0330.0260.0400.751130.50.228 + j0.0810.035 + j0.0406646480545
    1000 (61)0.0180.0260.0230.0380.843146.50.209 + j0.0720.028 + j0.0387131550625
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/Kcmilmmmmmmmmmmmmkg/kmmmnewton
    TBA1/0 (Solid)8.2326.728.7628.752.0335.361295424.182817
    TBA1/0 (19)8.9227.418.7629.442.0336.041330431.802817
    TBA2/0 (19)10.0328.528.7630.562.0337.161427447.043551
    TBA3/0 (19)11.2529.748.7631.782.0338.381537459.744477
    TBA4/0 (19)12.6531.148.7633.172.0339.781671477.525647
    TBA250 (37)14.1732.878.7634.902.0341.501819497.846675
    TBA350 (37)16.7935.488.7637.522.7945.642250548.649345
    TBA500 (37)20.0438.738.7640.772.7948.892637586.7413350
    TBA750 (61)24.5943.548.7645.572.7953.703286645.1620025
    663041#1000 (61)28.3747.178.7649.202.7957.334046688.3426700
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    # Solid Black Jacket
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (Solid)0.33460.420.01680.18041.191207.02100.403 + j0.1620.129 + j0.0564405160195
    1/0 (19)0.54790.690.01620.17721.247216.53540.481 + j0.1570.212 + j0.0544497160195
    2/0 (19)0.43640.550.01490.17061.332231.62730.431 + j0.1480.168 + j0.0524646185220
    3/0 (19)0.34450.430.01400.16401.427248.03150.389 + j0.1390.133 + j0.0504808210250
    4/0 (19)0.27560.340.01310.15751.535266.73230.354 + j0.1310.106 + j0.0494994235280
    250 (37)0.23290.300.01190.15091.667289.69820.330 + j0.1210.091 + j0.0475225
    350 (37)0.16400.210.01070.14761.864323.81890.293 + j0.1090.067 + j0.0455573315370
    500 (37)0.11480.150.00940.13782.110366.46980.260 + j0.0960.048 + j0.0436007380435
    750 (61)0.07870.110.00790.13122.464428.14960.228 + j0.0810.035 + j0.0406646480545
    1000 (61)0.05910.090.00700.12472.766480.64300.209 + j0.0720.028 + j0.0387131550625
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.

    Revision: 1.000.002

    Updated On: Nov. 7, 2024, 8 p.m. UTC