SPEC 81242

35kV AL 100% TRXLPE One-Third Neutral LLDPE

Single Conductor, 345 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Moisture blocked class B compressed Aluminum ASTM B231 1350 ¾ hard H16/H26 ( Non Moisture Blocked Optional )
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; Supersmooth conductor shield optional; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:345 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, black with red extruded stripes; PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 35kV cables are suited for use in wet and dry areas, conduits, ducts, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation. 130°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Rural Utility Standard RUS 1728F-U1 or 1728.204 (Electric standards and specifications for materials and construction)
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA 68.5: -40ºC and MV 90ºC optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] AL 35000 VOLTS TRXLPE INSULATION 345 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    TBA1/0 (SOLID)0.3251.0533451.1736x140.54501.4018599.8633
    615150^1/0 (19)0.3621.0723451.1826x140.54501.417869.9633
    6207261/0 (19)0.3621.0723451.1826x140.54501.417869.9633
    6278792/0 (19)0.3951.1153451.2257x140.463501.45385510.2798
    TBA3/0 (19)0.4431.1713451.2919x140.36501.519105710.61006
    615151^4/0 (19)0.4981.2183451.32811x140.295501.556105210.91269
    626296^^^4/0 (19)0.4981.2183451.32811x140.295501.556105210.91269
    2548154/0 (19)0.4981.2183451.32811x140.295501.556105210.91269
    584524^^350 (37)0.6611.3913451.50118x140.18751.783146312.52100
    619322350 (37)0.6611.3913451.50118x140.18751.783146212.52100
    625222500 (37)0.7891.5193451.62925x140.13751.911178313.43000
    620816^^500 (37)0.7891.5193451.62916x120.128751.945183813.63000
    626322^500 (37)0.7891.5193451.62916x120.128751.945183813.63000
    614633500 (37)0.7891.5193451.62916x120.128751.945183713.63000
    257724750 (61)0.9681.7083451.84824x120.085752.164244315.14500
    6146341000 (61)1.1171.8573451.99720x100.064752.355302316.56000
    6173681250 (91)1.252.0013452.14125x100.051752.5356217.57500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ HiDri Plus® - Water Blocking Powder
    ^^ HiDri Plus® - Water Blocking Powder. All Black Jacket
    ^^^ HiDri Plus® - Water Blocking Powder, UL listed MV-90 Rated
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence ImpedancePositive Sequence ImpedanceShort Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (SOLID)0.1020.140.0720.0550.285.60.473+j0.2770.141+j0.0582095160195
    1/0 (19)0.1670.2290.0670.0530.36.10.562+j0.2780.230+j0.0592095160195
    1/0 (19)0.1670.2290.0670.0530.36.10.562+j0.2780.230+j0.0592095160195
    2/0 (19)0.1330.1820.0640.0520.316.30.497+j0.2320.183+j0.0572444185220
    3/0 (19)0.1050.1440.0610.050.336.70.421+j0.1700.146+j0.0553142210250
    4/0 (19)0.0840.1150.0560.0480.367.30.359+j0.1300.117+j0.0533840235285
    4/0 (19)0.0840.1150.0560.0480.367.30.359+j0.1300.117+j0.0533840235285
    4/0 (19)0.0840.1150.0560.0480.367.30.359+j0.1300.117+j0.0533840235285
    350 (37)0.0510.070.0460.0450.448.90.235+j0.0680.073+j0.0506284315370
    350 (37)0.0510.070.0460.0450.448.90.235+j0.0680.073+j0.0506284315370
    500 (37)0.0360.050.0410.0420.5100.173+j0.0470.054+j0.0478727380445
    500 (37)0.0360.050.0410.0420.5100.172+j0.0470.054+j0.0478865380445
    500 (37)0.0360.050.0410.0420.5100.172+j0.0470.054+j0.0478865380445
    500 (37)0.0360.050.0410.0420.5100.172+j0.0470.054+j0.0478865380445
    750 (61)0.0230.0330.0350.040.5811.70.116+j0.0320.039+j0.04413298470530
    1000 (61)0.0170.0250.0310.0390.6513.10.088+j0.0260.033+j0.04117615530585
    1250 (91)0.0140.0220.0290.0380.714.20.073+j0.0230.031+j0.03922019
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    TBA1/0 (SOLID)8.2526.758.7629.796x141.771.2735.591278248.922817
    615150^1/0 (19)9.1927.238.7630.026x141.771.2735.811170251.462817
    6207261/0 (19)9.1927.238.7630.026x141.771.2735.811170251.462817
    6278792/0 (19)10.0328.328.7631.127x141.521.2736.911272259.083551
    TBA3/0 (19)11.2529.748.7632.799x141.181.2738.581573269.244477
    615151^4/0 (19)12.6530.948.7633.7311x140.971.2739.521566276.865647
    626296^^^4/0 (19)12.6530.948.7633.7311x140.971.2739.521566276.865647
    2548154/0 (19)12.6530.948.7633.7311x140.971.2739.521566276.865647
    584524^^350 (37)16.7935.338.7638.1318x140.591.9145.292177317.509345
    619322350 (37)16.7935.338.7638.1318x140.591.9145.292176317.509345
    625222500 (37)20.0438.588.7641.3825x140.431.9148.542653340.3613350
    620816^^500 (37)20.0438.588.7641.3816x120.421.9149.402735345.4413350
    626322^500 (37)20.0438.588.7641.3816x120.421.9149.402735345.4413350
    614633500 (37)20.0438.588.7641.3816x120.421.9149.402734345.4413350
    257724750 (61)24.5943.388.7646.9424x120.281.9154.973636383.5420025
    6146341000 (61)28.3747.178.7650.7220x100.211.9159.824499419.1026700
    6173681250 (91)31.7550.838.7654.3825x100.171.9163.505301444.5033375
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    ^ HiDri Plus® - Water Blocking Powder
    ^^ HiDri Plus® - Water Blocking Powder. All Black Jacket
    ^^^ HiDri Plus® - Water Blocking Powder, UL listed MV-90 Rated
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1/0 (SOLID)0.33460.460.02190.18040.91918.37270.473+j0.2770.141+j0.0582095160195
    1/0 (19)0.54790.750.02040.17390.98420.01310.562+j0.2780.230+j0.0592095160195
    1/0 (19)0.54790.750.02040.17390.98420.01310.562+j0.2780.230+j0.0592095160195
    2/0 (19)0.43640.600.01950.17061.01720.66930.497+j0.2320.183+j0.0572444185220
    3/0 (19)0.34450.470.01860.16401.08321.98160.421+j0.1700.146+j0.0553142210250
    4/0 (19)0.27560.380.01710.15751.18123.95010.359+j0.1300.117+j0.0533840235285
    4/0 (19)0.27560.380.01710.15751.18123.95010.359+j0.1300.117+j0.0533840235285
    4/0 (19)0.27560.380.01710.15751.18123.95010.359+j0.1300.117+j0.0533840235285
    350 (37)0.16730.230.01400.14761.44429.19950.235+j0.0680.073+j0.0506284315370
    350 (37)0.16730.230.01400.14761.44429.19950.235+j0.0680.073+j0.0506284315370
    500 (37)0.11810.160.01250.13781.64032.80840.173+j0.0470.054+j0.0478727380445
    500 (37)0.11810.160.01250.13781.64032.80840.172+j0.0470.054+j0.0478865380445
    500 (37)0.11810.160.01250.13781.64032.80840.172+j0.0470.054+j0.0478865380445
    500 (37)0.11810.160.01250.13781.64032.80840.172+j0.0470.054+j0.0478865380445
    750 (61)0.07550.110.01070.13121.90338.38580.116+j0.0320.039+j0.04413298470530
    1000 (61)0.05580.080.00940.12802.13342.97900.088+j0.0260.033+j0.04117615530585
    1250 (91)0.04590.070.00880.12472.29746.58790.073+j0.0230.031+j0.03922019
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.

    Revision: 1.000.004

    Updated On: Aug. 10, 2025, 11:33 p.m. UTC

    Concentric Neutral Calculator