SPEC 70080
600V SEOPRENE® SEOOW Power Cord Non-UL/CSA with Black Jacket 105°C. Silicone-Free. MSHA Approved
600 Volt, 105°C Flexible Cord. Premium Oil Resistance, Sunlight, Water Resistance and Flame Retardant. Non UL / Non CSA Listed.

Construction:
- Conductor:Class K stranded bare copper per ASTM B-174
- Insulation:Heat, moisture and oil resistant TPE
- Filler:Non-wicking polypropylene fillers, with a tissue-paper separator wrapped around the assembly
- Jacket:Black TPE (other colors available upon request)
Applications and Features:
Southwire Type SEOOW Flexible Cords are permitted for indoor and outdoor temporary power uses, portable industrial machinery and compressors. Type SEOOW Cords are suitable for use in temperatures between -50°C to maximum 105°C wet or dry.
Specifications:
Sample Print Legend:
SOUTHWIRE{R} SEOPRENE{R} CORD X/C X AWG (X.XX{mm2}) SEOOW 600V -50{D}C TO 105{D}C WATER RESISTAN
Packaging:
Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Cond. Strands | Insul. Thickness | Jacket Thickness | Approx. OD | Approx. Weight | Ampacity | DC Resistance | Insul. Color | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | No. | mil | mil | inch | lb/1000ft | Amp | Ω/1000ft | |||
| 550449 | 8 | 3 | 96 | 45 | 90 | 0.701 | 325 | 35 | 0.708 | BK,WE,GN | BK |
| 550450 | 8 | 4 | 96 | 45 | 100 | 0.783 | 418 | 28 | 0.708 | BK,WE,RD,GN | BK |
| 551140 | 8 | 5 | 96 | 45 | 100 | 0.851 | 499 | 28 | 0.708 | BK,WE,RD,GN,OE | BK |
| 550556 | 6 | 3 | 96 | 45 | 100 | 0.818 | 461 | 45 | 0.446 | BK,WE,GN | BK |
| 550405 | 6 | 4 | 96 | 45 | 100 | 0.892 | 580 | 36 | 0.446 | BK,WE,RD,GN | BK |
| 598330 | 6 | 5 | 96 | 45 | 110 | 0.992 | 714 | 36 | 0.446 | BK,WE,RD,GN,OE | BK |
| 598331 | 4 | 3 | 96 | 45 | 110 | 0.913 | 608 | 60 | 0.279 | BK,WE,GN | BK |
| 550404 | 4 | 4 | 96 | 45 | 125 | 1.027 | 801 | 48 | 0.279 | BK,WE,RD,GN | BK |
| 553942 | 2 | 3 | 119 | 45 | 125 | 1.158 | 1030 | 80 | 0.167 | BK,WE,GN | BK |
| 550473 | 2 | 4 | 119 | 45 | 125 | 1.26 | 1302 | 64 | 0.167 | BK,WE,RD,GN | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Cond. Number | Cond. Strands | Insul. Thickness | Jacket Thickness | Approx. OD | Approx. Weight | Ampacity * | DC Resistance | Insul. Color | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | No. | mm | mm | mm | kg/km | Amp | Ω/km | |||
| 550449 | 8 | 3 | 96 | 1.14 | 2.29 | 17.81 | 484 | 35 | 2.32 | BK,WE,GN | BK |
| 550450 | 8 | 4 | 96 | 1.14 | 2.54 | 19.89 | 622 | 28 | 2.32 | BK,WE,RD,GN | BK |
| 551140 | 8 | 5 | 96 | 1.14 | 2.54 | 21.62 | 743 | 28 | 2.32 | BK,WE,RD,GN,OE | BK |
| 550556 | 6 | 3 | 96 | 1.14 | 2.54 | 20.78 | 686 | 45 | 1.46 | BK,WE,GN | BK |
| 550405 | 6 | 4 | 96 | 1.14 | 2.54 | 22.66 | 863 | 36 | 1.46 | BK,WE,RD,GN | BK |
| 598330 | 6 | 5 | 96 | 1.14 | 2.79 | 25.20 | 1063 | 36 | 1.46 | BK,WE,RD,GN,OE | BK |
| 598331 | 4 | 3 | 96 | 1.14 | 2.79 | 23.19 | 905 | 60 | 0.92 | BK,WE,GN | BK |
| 550404 | 4 | 4 | 96 | 1.14 | 3.18 | 26.09 | 1192 | 48 | 0.92 | BK,WE,RD,GN | BK |
| 553942 | 2 | 3 | 119 | 1.14 | 3.18 | 29.41 | 1533 | 80 | 0.55 | BK,WE,GN | BK |
| 550473 | 2 | 4 | 119 | 1.14 | 3.18 | 32.00 | 1938 | 64 | 0.55 | BK,WE,RD,GN | BK |
* Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.