SPEC 70080

600V SEOPRENE® SEOOW Power Cord Non-UL/CSA with Black Jacket 105°C. Silicone-Free. MSHA Approved

600 Volt, 105°C Flexible Cord. Premium Oil Resistance, Sunlight, Water Resistance and Flame Retardant. Non UL / Non CSA Listed.

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant TPE
  3. Filler:Non-wicking polypropylene fillers, with a tissue-paper separator wrapped around the assembly
  4. Jacket:Black TPE (other colors available upon request)

Applications and Features:

Southwire Type SEOOW Flexible Cords are permitted for indoor and outdoor temporary power uses, portable industrial machinery and compressors. Type SEOOW Cords are suitable for use in temperatures between -50°C to maximum 105°C wet or dry.

Specifications:

  • MSHA Approved
  • RoHS-3 Complies with European Directive 2015/863
  • Sample Print Legend:

    SOUTHWIRE{R} SEOPRENE{R} CORD X/C X AWG (X.XX{mm2}) SEOOW 600V -50{D}C TO 105{D}C WATER RESISTAN

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacityDC ResistanceInsul. ColorJacket Color
    AWG/KcmilNo.No.milmilinchlb/1000ftAmpΩ/1000ft
    550449839645900.701325350.708BK,WE,GNBK
    5504508496451000.783418280.708BK,WE,RD,GNBK
    5511408596451000.851499280.708BK,WE,RD,GN,OEBK
    5505566396451000.818461450.446BK,WE,GNBK
    5504056496451000.892580360.446BK,WE,RD,GNBK
    5983306596451100.992714360.446BK,WE,RD,GN,OEBK
    5983314396451100.913608600.279BK,WE,GNBK
    5504044496451251.027801480.279BK,WE,RD,GNBK
    55394223119451251.1581030800.167BK,WE,GNBK
    55047324119451251.261302640.167BK,WE,RD,GNBK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *DC ResistanceInsul. ColorJacket Color
    AWG/KcmilNo.No.mmmmmmkg/kmAmpΩ/km
    55044983961.142.2917.81484352.32BK,WE,GNBK
    55045084961.142.5419.89622282.32BK,WE,RD,GNBK
    55114085961.142.5421.62743282.32BK,WE,RD,GN,OEBK
    55055663961.142.5420.78686451.46BK,WE,GNBK
    55040564961.142.5422.66863361.46BK,WE,RD,GNBK
    59833065961.142.7925.201063361.46BK,WE,RD,GN,OEBK
    59833143961.142.7923.19905600.92BK,WE,GNBK
    55040444961.143.1826.091192480.92BK,WE,RD,GNBK
    553942231191.143.1829.411533800.55BK,WE,GNBK
    550473241191.143.1832.001938640.55BK,WE,RD,GNBK
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.

    Revision: 1.000.004

    Updated On: April 15, 2025, 6:51 p.m. UTC