SPEC 70002

600V ROYAL® SOOW Power Cord Non-UL/CSA with Black Jacket 90°C. MSHA Approved

600 Volt, 90°C Flexible Cord. Heat, Moisture and Oil Resistant EPDM Rubber Insulation and Heat, Moisture and Oil Resistant Flexible CPE Jacket, Non-UL / Non-CSA.

...

Construction:

  1. Conductor:Class K flexible stranded bare copper per ASTM B3 and B174
  2. Insulation:Heat, moisture, and oil resistant EPDM
  3. Filler:Waxed paper fillers
  4. Jacket:Black Chlorinated Polyethylene (CPE) (other colors available upon request)

Applications and Features:

Southwire Royal® Non-UL/Non-CSA SOOW cord is designed for use with industrial equipment, heavy tools, battery chargers, portable lights and power extensions, suitable for outdoor applications. The cable is rated -40°C to 90°C, sunlight, water, oil, and weather resistant. Southwire Type SOOW Flexible Cords are permitted for use as specified by Article 400 and related articles of the 2023 National Electrical Code.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • MSHA flame test - P-07-KA190005-MSHA
  • RoHS-3 Complies with European Directive 2015/863
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • Federal Specification J-C-580B
  • Sample Print Legend:

    SOUTHWIRE® ROYAL® CORD X/C X AWG (X.XXmm2) SOOW 600V -40C TO 90C

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacityDC ResistanceInsul. ColorJacket Color
    AWG/KcmilNo.No.milmilinchlb/1000ftAmpΩ/1000ft
    5699728213345750.615218400.708BK,WEBK
    5580888313345750.645290350.708BK,WE,GNBK
    5580938413345750.715376280.708BK,WE,RD,GNBK
    55810585133451050.834492280.708BK,WE,RD,GN,OEBK
    56997362133451000.721337550.446BK,WEBK
    5580926313345900.726419450.446BK,WE,GNBK
    5580916413345850.803539360.446BK,WE,RD,GNBK
    55816165133451100.937702360.446BK,WE,RD,GN,OEBK
    5581374313345950.825590600.279BK,WE,GNBK
    55809044133451000.95762480.279BK,WE,RD,GNBK
    55813623168451151.09992800.166BK,WE,GNBK
    55808924168451301.291314640.166BK,WE,RD,GNBK
    56997625168451201.3731654640.166BK,WE,RD,GN,OEBK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *DC ResistanceInsul. ColorJacket Color
    AWG/KcmilNo.No.mmmmmmkg/kmAmpΩ/km
    569972821331.141.9115.62324402.32BK,WEBK
    558088831331.141.9116.38432352.32BK,WE,GNBK
    558093841331.141.9118.16560282.32BK,WE,RD,GNBK
    558105851331.142.6721.18732282.32BK,WE,RD,GN,OEBK
    569973621331.142.5418.31502551.46BK,WEBK
    558092631331.142.2918.44624451.46BK,WE,GNBK
    558091641331.142.1620.40802361.46BK,WE,RD,GNBK
    558161651331.142.7923.801045361.46BK,WE,RD,GN,OEBK
    558137431331.142.4120.96878600.92BK,WE,GNBK
    558090441331.142.5424.131134480.92BK,WE,RD,GNBK
    558136231681.142.9227.691476800.54BK,WE,GNBK
    558089241681.143.3032.771955640.54BK,WE,RD,GNBK
    569976251681.143.0534.872461640.54BK,WE,RD,GN,OEBK
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.

    Revision: 1.000.003

    Updated On: June 24, 2026, 8:29 p.m. UTC