SPEC 45411

CU 2000V XLPE Insulation. RHH/RHW-2 PV

Single Conductor Photovoltaic (Type PV) Power Cable 2000 Volt Copper Conductor XLPE Insulation. Sizes 14 AWG through 1000 Kcmil. Heat, Moisture, Sunlight Resistant RoHS. 90°C

...

Construction:

  1. Conductor:Stranded bare copper per ASTM B3 and ASTM B8 or ASTM B787
  2. Insulation:Cross Linked Polyethylene (XLPE). Colors available upon request.

Applications and Features:

Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 4703 Standard for Photovoltaic Wire
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • VW-1 Vertical-Wire Flame Test (Optional)
  • Sample Print Legend:

    Non VW-1 Rated:
    {SQFTG} SOUTHWIRE E316464 {UL} PV WIRE XX AWG or KCMIL (XX.X{MM2}) CU 2000V 90°C WET OR DRY -40°C SUN RES DIRECT BURIAL OR RHH-RHW-2 2000V --- RoHS

    VW-1 Rated:
    {SQFTG} SOUTHWIRE E316464 {UL} PV WIRE XX AWG (XX.X{MM2}) CU 2000V 90°C WET OR DRY (-40°C) SUN RES DIRECT BURIAL VW-1 OR RHW-2 2000V---RoHS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessDiameter Over InsulationApprox. ODCopper WeightApprox. WeightJacket Color
    AWG/KcmilNo. of Strandsinchmilinchinchlb/1000ftlb/1000ft
    59796114190.073750.2230.2241329BK
    59795812190.089750.2390.2432039BK
    57996210190.113750.2630.2633253BK
    5690378190.142850.3120.3135179BK
    5690396190.178850.3480.34981114BK
    5690404190.225850.3950.396129168BK
    1389832190.283850.4530.456205250BK
    TBA1190.3221050.5320.532258337BK
    5690431/0190.3621050.5720.57326397BK
    5690442/0190.4051050.6150.614411489BK
    5690453/0190.4561050.6660.664518604BK
    5690474/0190.5121050.7220.72655751BK
    679559250370.5581200.7980.782772879BK
    653096300370.6111200.8510.8519261052BK
    590138350370.6611200.9010.90110811215BK
    587813400370.7061200.9460.94612351378BK
    578324500370.7891201.0291.00615441685BK
    672530600610.8661351.1361.13618532042BK
    588931750610.9681351.2381.23823162524BK
    4572001000611.1171351.3871.38730873324BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *VW-1 Rated
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    597961140.92.6313.2650.0582025
    5979581211.6622.0630.0542530
    579962101.11.041.2910.053540
    56903781.30.6530.810.0525055
    56903961.40.4110.510.0516575
    56904041.60.2580.320.0488595
    13898321.80.1620.2010.045115130
    TBA12.10.1280.1590.046130145
    5690431/02.30.1020.1270.044150170
    5690442/02.50.0820.1020.043175195
    5690453/02.70.0640.0790.042200225
    5690474/02.90.0510.0630.041230260
    6795592503.10.0430.0530.041255290
    6530963003.40.0360.0450.041285320
    5901383503.60.0310.0390.04310350
    5878134003.80.0270.0350.04335380
    57832450050.0210.0270.039380430
    6725306005.70.0180.0240.039420475
    5889317506.20.0140.0190.038475535
    45720010006.90.0110.0160.037545615
    Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Stock Code Colors

    SizeBlackWhiteRedGreenGreen/Yellow
    AWG/kcmilBlackWhiteRedGreenGreen/Yellow
    14597961
    12597958596376596377
    10579962583665583687
    2138983
    1/0569043677562
    2/0569044
    3/0569045
    4/0569047
    250679559
    300653096599400599401
    350590138
    400587813
    500578324
    600672530
    750588931457948
    1000457200

    Stock Code Colors (VW-1)

    SizeBlackWhiteRedGreenGreen/Yellow
    AWG/kcmilBlackWhiteRedGreenGreen/Yellow
    10568110577645
    8569037585080589110
    6569039671956585840
    4569040673880653094
    2TBA