SPEC 45263

AL 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600Volt Three Conductor Aluminum, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 4
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® {UL} XXX AWG AL 3 CDRS TYPE TC-ER THHN OR THWN-2 CDRS AL GW 1 X X AWG 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODAluminum WeightApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    TBA8370.134351 x 8600.56766152BK
    6713836370.169301 x 8600.66391218BK
    TBA4370.213501 x 6600.802144294BK
    6756132360.268401 x 6800.959214515BK
    6756181380.299501 x 6801.065264607BK
    5880231380.299501 x 4801.104279599BK
    6756201/03100.336501 x 4801.145341711BK
    6756222/03120.376501 x 3801.231430828BK
    6721612/03120.376501 x 2801.294429851BK
    6756243/03150.423501 x 4801.333519950BK
    6732534/03190.475501 x 2801.4456671115BK
    5782184/0330.475501 x 2801.4456671115BK
    6756262503220.52601 x 2801.597771316BK
    TBA3003370.57701 x 21101.769101473BK
    TBA3503370.616701 x 21101.85910511651BK
    6780995003340.736601 x 11102.11615072360BK
    5993176003410.813701 x 4/01102.31819142869BK
    6734976003410.813701 x 6001102.49822843298BK
    6774007503580.908701 x 3/01102.53623013425BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    TBA832.32971.0711.3340.0524045
    671383632.74720.6740.840.0515055
    TBA433.27510.4240.5280.0486575
    675613233.811940.2660.3310.04590100
    675618135.315060.2110.2630.046100115
    588023135.515060.2110.2630.046100115
    6756201/035.719000.1670.2080.044120135
    6756222/036.223950.1330.1660.043135150
    6721612/036.523950.1330.1660.043135150
    6756243/036.730200.1050.1310.042155175
    6732534/037.238080.0840.1050.041180205
    5782184/037.238080.0840.1050.041180205
    6756262503845000.070.0870.041205230
    TBA30038.854000.0590.0710.041230260
    TBA35039.363000.0510.0640.04250280
    678099500312.790000.0360.0450.039310350
    599317600313.9108000.030.0380.039340385
    673497600315108000.030.0380.039340385
    677400750315.2135000.0230.030.038385435
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 1.000.007

    Updated On: Oct. 5, 2026, 4:10 p.m. UTC