SPEC 45263
AL 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Type TC-ER Power Cable 600Volt Three Conductor Aluminum, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
- Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE® {UL} XXX AWG AL 3 CDRS TYPE TC-ER THHN OR THWN-2 CDRS AL GW 1 X X AWG 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {YYYY}
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Aluminum Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |||
| TBA | 8 | 3 | 7 | 0.134 | 35 | 1 x 8 | 60 | 0.567 | 66 | 152 | BK |
| 671383 | 6 | 3 | 7 | 0.169 | 30 | 1 x 8 | 60 | 0.663 | 91 | 218 | BK |
| TBA | 4 | 3 | 7 | 0.213 | 50 | 1 x 6 | 60 | 0.802 | 144 | 294 | BK |
| 675613 | 2 | 3 | 6 | 0.268 | 40 | 1 x 6 | 80 | 0.959 | 214 | 515 | BK |
| 675618 | 1 | 3 | 8 | 0.299 | 50 | 1 x 6 | 80 | 1.065 | 264 | 607 | BK |
| 588023 | 1 | 3 | 8 | 0.299 | 50 | 1 x 4 | 80 | 1.104 | 279 | 599 | BK |
| 675620 | 1/0 | 3 | 10 | 0.336 | 50 | 1 x 4 | 80 | 1.145 | 341 | 711 | BK |
| 675622 | 2/0 | 3 | 12 | 0.376 | 50 | 1 x 3 | 80 | 1.231 | 430 | 828 | BK |
| 672161 | 2/0 | 3 | 12 | 0.376 | 50 | 1 x 2 | 80 | 1.294 | 429 | 851 | BK |
| 675624 | 3/0 | 3 | 15 | 0.423 | 50 | 1 x 4 | 80 | 1.333 | 519 | 950 | BK |
| 673253 | 4/0 | 3 | 19 | 0.475 | 50 | 1 x 2 | 80 | 1.445 | 667 | 1115 | BK |
| 578218 | 4/0 | 3 | 3 | 0.475 | 50 | 1 x 2 | 80 | 1.445 | 667 | 1115 | BK |
| 675626 | 250 | 3 | 22 | 0.52 | 60 | 1 x 2 | 80 | 1.59 | 777 | 1316 | BK |
| TBA | 300 | 3 | 37 | 0.57 | 70 | 1 x 2 | 110 | 1.76 | 910 | 1473 | BK |
| TBA | 350 | 3 | 37 | 0.616 | 70 | 1 x 2 | 110 | 1.859 | 1051 | 1651 | BK |
| 678099 | 500 | 3 | 34 | 0.736 | 60 | 1 x 1 | 110 | 2.116 | 1507 | 2360 | BK |
| 599317 | 600 | 3 | 41 | 0.813 | 70 | 1 x 4/0 | 110 | 2.318 | 1914 | 2869 | BK |
| 673497 | 600 | 3 | 41 | 0.813 | 70 | 1 x 600 | 110 | 2.498 | 2284 | 3298 | BK |
| 677400 | 750 | 3 | 58 | 0.908 | 70 | 1 x 3/0 | 110 | 2.536 | 2301 | 3425 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| TBA | 8 | 3 | 2.3 | 297 | 1.071 | 1.334 | 0.052 | 40 | 45 |
| 671383 | 6 | 3 | 2.7 | 472 | 0.674 | 0.84 | 0.051 | 50 | 55 |
| TBA | 4 | 3 | 3.2 | 751 | 0.424 | 0.528 | 0.048 | 65 | 75 |
| 675613 | 2 | 3 | 3.8 | 1194 | 0.266 | 0.331 | 0.045 | 90 | 100 |
| 675618 | 1 | 3 | 5.3 | 1506 | 0.211 | 0.263 | 0.046 | 100 | 115 |
| 588023 | 1 | 3 | 5.5 | 1506 | 0.211 | 0.263 | 0.046 | 100 | 115 |
| 675620 | 1/0 | 3 | 5.7 | 1900 | 0.167 | 0.208 | 0.044 | 120 | 135 |
| 675622 | 2/0 | 3 | 6.2 | 2395 | 0.133 | 0.166 | 0.043 | 135 | 150 |
| 672161 | 2/0 | 3 | 6.5 | 2395 | 0.133 | 0.166 | 0.043 | 135 | 150 |
| 675624 | 3/0 | 3 | 6.7 | 3020 | 0.105 | 0.131 | 0.042 | 155 | 175 |
| 673253 | 4/0 | 3 | 7.2 | 3808 | 0.084 | 0.105 | 0.041 | 180 | 205 |
| 578218 | 4/0 | 3 | 7.2 | 3808 | 0.084 | 0.105 | 0.041 | 180 | 205 |
| 675626 | 250 | 3 | 8 | 4500 | 0.07 | 0.087 | 0.041 | 205 | 230 |
| TBA | 300 | 3 | 8.8 | 5400 | 0.059 | 0.071 | 0.041 | 230 | 260 |
| TBA | 350 | 3 | 9.3 | 6300 | 0.051 | 0.064 | 0.04 | 250 | 280 |
| 678099 | 500 | 3 | 12.7 | 9000 | 0.036 | 0.045 | 0.039 | 310 | 350 |
| 599317 | 600 | 3 | 13.9 | 10800 | 0.03 | 0.038 | 0.039 | 340 | 385 |
| 673497 | 600 | 3 | 15 | 10800 | 0.03 | 0.038 | 0.039 | 340 | 385 |
| 677400 | 750 | 3 | 15.2 | 13500 | 0.023 | 0.03 | 0.038 | 385 | 435 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.007
Updated On: Oct. 5, 2026, 4:10 p.m. UTC

