SPEC 45261
CU 600/1000V EPR Insulation LSZH-TP Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Type TC-ER Power Cable 600 or 1000 Volt Four Conductor Copper, Ethylene Propylene Rubber (EPR) insulation XHHW-2 Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket with 1 Bare CU Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Ethylene Propylene Rubber (EPR) Type XHHW-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE® {UL} XXX KCMIL CU 4 CDRS TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU SOLONON® 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |||
| 673535 | 2 | 4 | 7 | 0.283 | 45 | 1 x 6 | 80 | 1.083 | 910 | 1221 | BK |
| TBA | 1 | 4 | 19 | 0.322 | 55 | 1 x 6 | 80 | 1.211 | 1123 | 1430 | BK |
| TBA | 1/0 | 4 | 19 | 0.362 | 55 | 1 x 6 | 80 | 1.308 | 1398 | 1735 | BK |
| TBA | 4/0 | 4 | 19 | 0.512 | 55 | 1 x 4 | 110 | 1.731 | 2767 | 3303 | BK |
| TBA | 250 | 4 | 37 | 0.558 | 65 | 1 x 4 | 110 | 1.891 | 3247 | 3881 | BK |
| 673550 | 350 | 4 | 37 | 0.661 | 65 | 1 x 3 | 110 | 2.103 | 4530 | 5393 | BK |
| TBA | 500 | 4 | 37 | 0.789 | 65 | 1 x 2 | 110 | 2.45 | 6442 | 7291 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| 673535 | 2 | 4 | 5.4 | 2123 | 0.162 | 0.201 | 0.045 | 92 | 104 |
| TBA | 1 | 4 | 6.1 | 2678 | 0.128 | 0.159 | 0.046 | 104 | 116 |
| TBA | 1/0 | 4 | 6.5 | 3379 | 0.102 | 0.127 | 0.044 | 120 | 136 |
| TBA | 4/0 | 4 | 8.7 | 6771 | 0.051 | 0.063 | 0.041 | 184 | 208 |
| TBA | 250 | 4 | 9.5 | 8000 | 0.043 | 0.053 | 0.041 | 204 | 232 |
| 673550 | 350 | 4 | 12.6 | 11200 | 0.031 | 0.039 | 0.04 | 248 | 280 |
| TBA | 500 | 4 | 14.7 | 16000 | 0.021 | 0.027 | 0.039 | 304 | 344 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
Revision: 1.000.004
Updated On: April 14, 2025, 10:09 p.m. UTC


