SPEC 45261
CU 600/1000V EPR Insulation LSZH-TP Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Type TC-ER Power Cable 600Volt Four Conductor Copper, Ethylene Propylene Rubber (EPR) insulation XHHW-2 Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket with 1 Bare CU Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Ethylene Propylene Rubber (EPR) Type XHHW-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE® {UL} XXX KCMIL CU 4 CDRS TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU SOLONON® 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | ||
673535 | 2 | 4 | 7 | 0.282 | 45 | 1 x 6 | 80 | 1.078 | 909 | 1234 |
TBA | 1 | 4 | 19 | 0.322 | 55 | 1 x 6 | 80 | 1.207 | 1123 | 1437 |
TBA | 1/0 | 4 | 19 | 0.361 | 55 | 1 x 6 | 80 | 1.302 | 1395 | 1738 |
TBA | 4/0 | 4 | 19 | 0.512 | 55 | 1 x 4 | 110 | 1.727 | 2764 | 3320 |
TBA | 250 | 4 | 37 | 0.558 | 65 | 1 x 4 | 110 | 1.887 | 3244 | 3896 |
673550 | 350 | 4 | 37 | 0.661 | 65 | 1 x 3 | 110 | 2.187 | 4530 | 5552 |
TBA | 500 | 4 | 37 | 0.789 | 65 | 1 x 2 | 110 | 2.446 | 6436 | 7307 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
673535 | 2 | 4 | 5.4 | 1698 | 0.162 | 0.195 | 0.045 | 92 | 104 |
TBA | 1 | 4 | 6.0 | 2142 | 0.128 | 0.154 | 0.046 | 104 | 116 |
TBA | 1/0 | 4 | 6.5 | 2703 | 0.102 | 0.122 | 0.044 | 120 | 136 |
TBA | 4/0 | 4 | 8.6 | 5416 | 0.051 | 0.062 | 0.041 | 184 | 208 |
TBA | 250 | 4 | 9.4 | 6400 | 0.043 | 0.053 | 0.041 | 204 | 232 |
673550 | 350 | 4 | 13.1 | 8960 | 0.031 | 0.039 | 0.040 | 248 | 280 |
TBA | 500 | 4 | 14.7 | 12800 | 0.022 | 0.029 | 0.039 | 304 | 344 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
Revision: 1.000.003
Updated On: Dec. 31, 2024, 11:07 p.m. UTC