SPEC 45028

CU 600V Power Drop Cable

600V Flexible CU THHN Power Cable TC-ER

...

Construction:

  1. Conductor:Flexible stranded bare copper per ASTM B3, B172 and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer
    Color Code: 2/C Black, Red, with Green Ground. 3/C Black, Red, Blue with Green Ground
  3. Grounding Conductor:Flexible stranded bare copper per ASTM B3, B172 and B174
  4. Filler:Polypropylene fillers as necessary for a round assembly
  5. Binder:Mylar tape
  6. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket.

Applications and Features:

Southwire's 600 Volt Power Drop Cables conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays (TC-ER per NEC 336.10), direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC Article 501 and 502. Southwire's 600 Volt Power Drop Cable is ideal for use in power feed drop applications.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 509 Bus Drop Cable
  • UL 758 Standard for Appliance Wiring Material Style 20886
  • UL 1063 Machine Tool Wiring (MTW)
  • UL 1277 TC-ER
  • UL 2277 Type WTTC
  • CSA C22.2 No. 75 Thermoplastic Insulated Wires and Cables
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • Sample Print Legend:

    SOUTHWIRE (UL) E75755 XXX AWG (XX.XXmm2) 3/C TYPE TC-ER THHN OR THWN-2 CDRS GW 1 X AWG X 600V 90C WET/DRY SUN RES DIR BUR FT4 OR MTW OR WTTC 1000V OR AWM 20886 105C 1000V --- CE RoHS-2 Made in USA [YEAR] [SEQ FT MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODCopper WeightApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    648947◊632730.198301 x 8600.756304461BK
    648942◊434130.235401 x 8800.957447700BK
    647275◊2/0313300.4501 x 2801.45114781981BK
    647280◊373.739310.71601 x 21102.05535394478BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    648947◊6336290.4190.520.0516575
    648942◊433.810010.2630.3260.0488595
    647275◊2/037.331940.0850.1050.043175195
    647280◊373.7312.389680.0340.0430.04323365
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 1.000.003

    Updated On: June 12, 2025, 12:38 p.m. UTC