SPEC 44020

DLO TCU 2000V EPDM Insulation Thermoset CPE Jacket. RHH/RHW-2/RW90 MSHA Approved.

UL Listed as 2kV Heavy Duty Flexible Power Cable (HDFPC) DLO, Rated 90°C Dry or Wet. 2kV Type RHH/RHW-2 Flexible Power Cable Rated for Dry or Wet. CSA Listed as 2kV Type RW90. Composite Thermoset Wall EPDM Insulation Thermoset CPE Jacket. Silicone-Free. MSHA Approved

...

Construction:

  1. Conductor:Flexible Stranded Rope-Lay Class I Tinned Copper per ASTM B33 and B172 (As Applicable)
  2. Binder Tape:Mylar Tape
  3. Insulation:Black Thermoset Ethylene Propylene Diene Monomer (EPDM)
  4. Jacket:Thermoset Chlorinated Polyethylene (CPE). Other colors available (see table below)

Applications and Features:

HDFPC-DLO is a 2kV flexible power cable with a variety of possible applications such as but not limited to: Drilling rigs, railroad and transit car wiring, mining and other industrial equipment, and as flexible motor leads and wind turbine applications. The cable is suited for use in wet and dry areas, conduits, ducts, troughs, trays, and where superior electrical properties are desired. HDFPC-DLO is oil, heat, flame, abrasion, and sunlight resistant. Approved for use per the NEC® as Type RHH/RHW-2 and per the CE Code as 2kV Type RW90. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. Sizes 1/0 and Larger Rated For CT Use.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors (As Applicable)
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • UL 2806 Heavy Duty Flexible Power Cable (HDFPC-DLO)
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • MSHA Approved
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    Sizes 12 AWG and 10 AWG
    {SQFTG} SOUTHWIRE® ROYAL® XX AWG (XXmm2) E30117 (UL) TYPE RHH/RHW-2 90°C DRY 90°C WET 2KV (-40°C) PRI PRII SR --- EPR/CPE DLO --- P-07-KA100013-MSHA---RoHS

    Sizes 8 AWG to 1 AWG
    SOUTHWIRE® ROYAL® XX AWG (XX{mm2}) E30117 {UL} TYPE HDFPC EPR/CPE 2KV DL0 90°C DRY 90°C WET OR TYPE RHH/RHW-2 90°C DRY 90°C WET 2KV -40°C PRI PRII SR VW-1 -- {CSA} 156205 RW90 90°C DRY 90°C WET 2KV -40°C PRI PRII FT1 SR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Sizes 1/0 AWG and larger
    {SQFTG} SOUTHWIRE® ROYAL® XX AWG XX STRAND CLASS XX (XX{mm2}) E30117 {UL} TYPE HDFPC EPR/CPE 2KV DLO 90°C DRY 90°C WET OR TYPE RHH/RHW-2 90°C DRY 90°C WET 2KV -40°C PRI PRII SR FOR CT USE FT4 -- {CSA} 156205 RW90 90°C DRY 90°C WET TC-ER 2KV -40C° PRI PRII FT1 FT4 SR
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. StrandsDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightJacket Color
    AWG/KcmilNo.inchmilmilinchlb/1000ft
    66544612190.09145150.21036RD
    66546512190.09145150.21036BN
    66546612190.09145150.21036OE
    66546712190.09145150.21036YW
    57125312190.09145150.21036BK
    66546812190.09145150.21036GN
    66546910190.12555250.26558RD
    66547010190.12555250.26558BN
    66547110190.12555250.26558OE
    66547210190.12555250.26558YW
    56005710190.12555250.26558BK
    66547310190.12555250.26558GN
    1670148410.14555300.33092RD
    6654748410.14555300.33092BN
    6654758410.14555300.33092OE
    6654768410.14555300.33092YW
    6654778410.14555300.33092GN
    6654786650.18650300.370127RD
    6654796650.18650300.370127BN
    6654806650.18650300.370127OE
    6654816650.18650300.370127YW
    1670156650.18650300.370127BK
    6654826650.18650300.370127GN
    66548341050.23560350.440196BN
    66548441050.23560350.440196OE
    66548541050.23560350.440196YW
    16701741050.23560350.440196BK
    65362741050.23560350.440196GN
    13823821610.29060350.500282BN
    13823921610.29060350.500282OE
    13824021610.29060350.500282YW
    16701921610.29060350.500282BK
    13824121610.29060350.500282GN
    16702012100.33085600.635400BK
    13828212100.33085600.635400RD
    13828312100.33085600.635400BN
    13828712100.33085600.635400OE
    13828812100.33085600.635400YW
    13828912100.33085600.635400GN
    1382421/02660.37975550.645450RD
    1382431/02660.37975550.645450BN
    1382441/02660.37975550.645450OE
    1382451/02660.37975550.645450YW
    1670211/02660.37975550.645450BK
    1382461/02660.37975550.645450GN
    1382472/03420.40080500.690566BN
    1382482/03420.40080500.690566OE
    1382492/03420.40080500.690566YW
    1670222/03420.40080500.690566BK
    1382512/03420.40080500.690566GN
    5620643/04180.48080550.760676BK
    1382523/04180.48080550.760676RD
    1382533/04180.48080550.760676BN
    1382543/04180.48080550.760676OE
    1382553/04180.48080550.760676YW
    1670233/04180.48080550.760676BK
    1382563/04180.48080550.760676GN
    1382574/05320.53080600.815815BN
    1382584/05320.53080600.815815OE
    1382594/05320.53080600.815815YW
    1670244/05320.53080600.815815BK
    1382604/05320.53080600.815815GN
    641176262.26460.56580600.845974RD
    665452262.26460.56580600.845974BN
    665453262.26460.56580600.845974OE
    665454262.26460.56580600.845974YW
    167026262.26460.56580600.845974BK
    665455262.26460.56580600.845974GN
    665456313.37790.65090700.9801139RD
    665457313.37790.65090700.9801139BN
    665458313.37790.65090700.9801139OE
    665459313.37790.65090700.9801139YW
    167027313.37790.65090700.9801139BK
    665460313.37790.65090700.9801139GN
    655203373.79310.70195701.0401343RD
    678900373.79310.70195701.0401343BN
    576729373.79310.70195701.0401343OE
    678901373.79310.70195701.0401343YW
    167029373.79310.70195701.0401343BK
    678902373.79310.70195701.0401343GN
    167030444.411210.78290651.1051654BK
    678975444.411210.78290651.1051654RD
    665461444.411210.78290651.1051654BN
    665462444.411210.78290651.1051654OE
    665463444.411210.78290651.1051654YW
    665464444.411210.78290651.1051654GN
    138211535.313300.843105751.2121889BN
    138212535.313300.843105751.2121889OE
    138213535.313300.843105751.2121889YW
    167031535.313300.843105751.2121889BK
    677552535.313300.843105751.2121889GN
    138229646.416280.890115801.2902292RD
    138215646.416280.890115801.2902292BN
    138216646.416280.890115801.2902292OE
    138217646.416280.890115801.2902292YW
    167032646.416280.890115801.2902292BK
    138218646.416280.890115801.2902292GN
    640980777.719240.966120901.4052727BN
    640981777.719240.966120901.4052727OE
    640982777.719240.966120901.4052727YW
    167033777.719240.966120901.4052727BK
    138219777.719240.966120901.4052727GN
    640983 777.719240.966120901.4052727GY
    138220111127451.168115951.6404161RD
    138221111127451.168115951.6404161BN
    138222111127451.168115951.6404161OE
    138223111127451.168115951.6404161YW
    167035111127451.168115951.6404161BK
    138224111127451.168115951.6404161GN
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMax Pull TensionMin Bending RadiusAllowable Ampacity In Air 75°CAllowable Ampacity In Air 90°CAllowable Ampacity In Raceway At 75°CAllowable Ampacity In Raceway At 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftlbinchAmpAmpAmpAmp
    121.7742.3010.054520.835402530
    121.7742.3010.054520.835402530
    121.7742.3010.054520.835402530
    121.7742.3010.054520.835402530
    121.7742.3010.054520.835402530
    121.7742.3010.054520.835402530
    101.0811.3020.050831.150553540
    101.0811.3020.050831.150553540
    101.0811.3020.050831.150553540
    101.0811.3020.050831.150553540
    101.0811.3020.050831.150553540
    101.0811.3020.050831.150553540
    80.6790.8180.0521321.370805055
    80.6790.8180.0521321.370805055
    80.6790.8180.0521321.370805055
    80.6790.8180.0521321.370805055
    80.6790.8180.0521321.370805055
    60.4350.5240.0512091.5951056575
    60.4350.5240.0512091.5951056575
    60.4350.5240.0512091.5951056575
    60.4350.5240.0512091.5951056575
    60.4350.5240.0512091.5951056575
    60.4350.5240.0512091.5951056575
    40.2740.3300.0483331.81251408595
    40.2740.3300.0483331.81251408595
    40.2740.3300.0483331.81251408595
    40.2740.3300.0483331.81251408595
    40.2740.3300.0483331.81251408595
    20.1720.2070.0455302.0170190115130
    20.1720.2070.0455302.0170190115130
    20.1720.2070.0455302.0170190115130
    20.1720.2070.0455302.0170190115130
    20.1720.2070.0455302.0170190115130
    10.1430.1860.0466702.5195220130145
    10.1430.1860.0466702.5195220130145
    10.1430.1860.0466702.5195220130145
    10.1430.1860.0466702.5195220130145
    10.1430.1860.0466702.5195220130145
    10.1430.1860.0466702.5195220130145
    1/00.1090.1310.0448442.6230260150170
    1/00.1090.1310.0448442.6230260150170
    1/00.1090.1310.0448442.6230260150170
    1/00.1090.1310.0448442.6230260150170
    1/00.1090.1310.0448442.6230260150170
    1/00.1090.1310.0448442.6230260150170
    2/00.0870.1040.04310642.8265300175195
    2/00.0870.1040.04310642.8265300175195
    2/00.0870.1040.04310642.8265300175195
    2/00.0870.1040.04310642.8265300175195
    2/00.0870.1040.04310642.8265300175195
    3/00.0690.0830.04213423.0310350200225
    3/00.0690.0830.04213423.0310350200225
    3/00.0690.0830.04213423.0310350200225
    3/00.0690.0830.04213423.0310350200225
    3/00.0690.0830.04213423.0310350200225
    3/00.0690.0830.04213423.0310350200225
    3/00.0690.0830.04213423.0310350200225
    4/00.0550.0670.04116923.3360405230260
    4/00.0550.0670.04116923.3360405230260
    4/00.0550.0670.04116923.3360405230260
    4/00.0550.0670.04116923.3360405230260
    4/00.0550.0670.04116923.3360405230260
    262.20.0260.0330.03120973.4415466264301
    262.20.0260.0330.03120973.4415466264301
    262.20.0260.0330.03120973.4415466264301
    262.20.0260.0330.03120973.4415466264301
    262.20.0260.0330.03120973.4415466264301
    262.20.0260.0330.03120973.4415466264301
    313.30.0390.0480.03125063.9460518298332
    313.30.0390.0480.03125063.9460518298332
    313.30.0390.0480.03125063.9460518298332
    313.30.0390.0480.03125063.9460518298332
    313.30.0390.0480.03125063.9460518298332
    313.30.0390.0480.03125063.9460518298332
    373.70.0330.0420.03129895.2524592323365
    373.70.0330.0420.03129895.2524592323365
    373.70.0330.0420.03129895.2524592323365
    373.70.0330.0420.03129895.2524592323365
    373.70.0330.0420.03129895.2524592323365
    373.70.0330.0420.03129895.2524592323365
    444.40.0260.0400.02935555.5578652358405
    444.40.0260.0400.02935555.5578652358405
    444.40.0260.0400.02935555.5578652358405
    444.40.0260.0400.02935555.5578652358405
    444.40.0260.0400.02935555.5578652358405
    444.40.0260.0400.02935555.5578652358405
    535.30.0210.0280.03042826.1644730394446
    535.30.0210.0280.03042826.1644730394446
    535.30.0210.0280.03042826.1644730394446
    535.30.0210.0280.03042826.1644730394446
    535.30.0210.0280.03042826.1644730394446
    646.40.0180.0250.03051716.5720812439496
    646.40.0180.0250.03051716.5720812439496
    646.40.0180.0250.03051716.5720812439496
    646.40.0180.0250.03051716.5720812439496
    646.40.0180.0250.03051716.5720812439496
    646.40.0180.0250.03051716.5720812439496
    777.70.0160.0240.03062217.0801905483543
    777.70.0160.0240.03062217.0801905483543
    777.70.0160.0240.03062217.0801905483543
    777.70.0160.0240.03062217.0801905483543
    777.70.0160.0240.03062217.0801905483543
    777.70.0160.0240.03062217.0801905483543
    11110.0110.0160.02988888.29931119570648
    11110.0110.0160.02988888.29931119570648
    11110.0110.0160.02988888.29931119570648
    11110.0110.0160.02988888.29931119570648
    11110.0110.0160.02988888.29931119570648
    11110.0110.0160.02988888.29931119570648
    * Ampacities in raceway are based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities for non-standard sizes were extrapolated
    * Ampacities in air are based upon 2023 NEC Table 310.17. Ampacities for non-standard sizes were extrapolated
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * #12 and #10 AWG are not approved for CSA RW90

    Other Insulation Colors

    Cond. SizeBlackRedBrownOrangeYellowGreenGray
    AWG/kcmilBlackRedBrownOrangeYellowGreenGray
    12571253665446665465665466665467665468 
    10560057665469665470665471665472665473 
    8TBA167014665474665475665476665477 
    6167015665478665479665480665481665482 
    4167017167017665483665484665485653627 
    2167019167019138238138239138240138241 
    1167020138282138283138287138288138289 
    1/0167021138242138243138244138245138246 
    2/0167022167022138247138248138249138251 
    3/0167023138252138253138254138255138256 
    4/0167024167024138257138258138259138260 
    262.6167026641176665452665453665454665455 
    313.3167027665456665457665458665459665460 
    373.7167029655203678900576729678901678902 
    444.4167030678975665461665462665463665464 
    535.3167031167031138211138212138213677552 
    646.4167032138229138215138216138217138218 
    777.7167033167033640980640981640982138219640983
    1111167035138220138221138222138223138224

    Revision: 1.000.019

    Updated On: July 27, 2024, 4:03 a.m. UTC