SPEC 22061

1/C CU 600V RW90 SIMpull®

Copper Conductor, 600V, 90°C MAX - 40°C MIN, 1/0 AWG to 1000 KCMIL. Sizes 350 kcmil & Larger FT4 Rated. All Sizes and Colors Are Sunlight Resistant.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) SIMpull®

Applications and Features:

Single copper conductor with low temperature, moisture resisting XLPE (cross linked polyethylene) insulation. Standard sizes 1/0 AWG and larger utilize SIMpull ® technology. All sizes are Sunlight Resistant in all colors and packaging. This product meets the current RoHS requirements. No lead is added or used in manufacturing.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA SUN RES - for Sunlight Resistant rating
  • IEEE 1202/FT4 Flame Test (70,000 BTU/hr) 350kcmil and Larger
  • Sample Print Legend:

    SOUTHWIRE® XXXX KCMIL NOLUBE® SIMpull RW90{TM} LL90458 {CSA} (XXXX.XX{mm2}) CU RW90 XLPE 600 VOLTS (-40°C) SR - MADE UNDER US PATENT NOS 7411129 & 7557301-RW90 XXXX KCMIL {MMM/DD/YYYY} - OPERATOR NAME SEQUENTIAL METER MARKS SEQ METERS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    951749127300.153250.6321.6622.0020.05430
    951756107300.175380.7521.0401.2530.05040
    95176487450.238640.91320.6530.7860.05255
    95177267450.274971.02090.4110.4950.05175
    95178047450.3211491.23330.2580.3100.04895
    95179827450.3792311.55300.1620.1950.045130
    951806119550.4382921.76690.1280.1540.046145
    9518141/019550.4783631.98440.1020.1220.044170
    9518222/019550.5204522.010640.0810.0970.043195
    9518303/019550.5705642.213420.0640.0780.042225
    9518484/019550.6267072.516920.0510.0620.041260
    95185525037650.6808282.720000.0430.0530.041290
    95187135037650.79911553.128000.0310.0390.040350
    95189750037650.90416183.640000.0220.0290.039430
    95190560061801.03619675.148000.0180.0250.039475
    95191375061801.13824425.660000.0140.0220.038535
    951921100061801.28732326.480000.0110.0180.037615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    9517491270.763.893715.241425.456.570.177230
    9517561070.764.445717.782313.414.110.164040
    951764871.146.059522.865872.142.580.170655
    951772671.146.9614425.409301.351.620.167375
    951780471.148.1522230.4814820.851.020.157595
    951798271.149.6334438.1023590.530.640.1476130
    9518061191.4011.1343543.1829770.420.510.1509145
    9518141/0191.4012.1454048.2637560.330.400.1444170
    9518222/0191.4013.2167350.8047350.270.320.1411195
    9518303/0191.4014.4883955.8859720.210.260.1378225
    9518484/0191.4015.90105263.5075290.170.200.1345260
    951855250371.6517.27123268.5889000.140.170.1345290
    951871350371.6520.29171978.74124600.100.130.1312350
    951897500371.6522.96240891.44178000.070.100.1280430
    951905600612.0326.312927129.54213600.060.080.1280475
    951913750612.0328.913634142.24267000.050.070.1247535
    9519211000612.0332.694810162.56356000.040.060.1214615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.

    Revision: 1.000.000

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC