SPEC 22061

1/C CU 600V RW90 SIMpull®

Copper Conductor, 600V, 90°C MAX - 40°C MIN, 1/0 AWG to 1000 KCMIL. Sizes 350 kcmil & Larger FT4 Rated. All Sizes and Colors Are Sunlight Resistant.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) SIMpull®

Applications and Features:

Single copper conductor with low temperature, moisture resisting XLPE (cross linked polyethylene) insulation. Standard sizes 1/0 AWG and larger utilize SIMpull ® technology. All sizes are Sunlight Resistant in all colors and packaging. This product meets the current RoHS requirements. No lead is added or used in manufacturing.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA SUN RES - for Sunlight Resistant rating
  • IEEE 1202/FT4 Flame Test (70,000 BTU/hr) 350kcmil and Larger
  • Sample Print Legend:

    SOUTHWIRE{R} XXXX KCMIL NOLUBE{R} SIMpull RW90{TM} LL90458 {CSA} (XXXX.XX{mm2}) CU RW90 XLPE 600 VOLTS (-40{D}C) SR - MADE UNDER US PATENT NOS 7411129 & 7557301-RW90 XXXX KCMIL {MMM/DD/YYYY} - OPERATOR NAME SEQUENTIAL METER MARKS SEQ METERS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftAmp
    9517491217300.153250.6322.0020.05430
    9517561017300.175380.7521.2530.05040
    951764817450.238640.91320.7860.05255
    951772617450.274971.02090.4950.05175
    951780417450.3211491.23330.3100.04895
    951798217450.3792311.55300.1950.045130
    9518061119550.4382921.76690.1540.046145
    9518141/0119550.4783631.98440.1220.044170
    9518222/0119550.5204522.010640.0970.043195
    9518303/0119550.5705642.213420.0780.042225
    9518484/0119550.6267072.516920.0620.041260
    951855250137650.6808282.720000.0530.041290
    951871350137650.79911553.128000.0390.040350
    951897500137650.90416183.640000.0290.039430
    951905600161801.03619675.148000.0250.039475
    951913750161801.13824425.660000.0220.038535
    9519211000161801.28732326.480000.0180.037615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. NumberStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C†
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmAmp
    95174912170.763.893715.241426.570.177230
    95175610170.764.445717.782314.110.164040
    9517648171.146.059522.865872.580.170655
    9517726171.146.9614425.409301.620.167375
    9517804171.148.1522230.4814821.020.157595
    9517982171.149.6334438.1023590.640.1476130
    95180611191.4011.1343543.1829770.510.1509145
    9518141/01191.4012.1454048.2637560.400.1444170
    9518222/01191.4013.2167350.8047350.320.1411195
    9518303/01191.4014.4883955.8859720.260.1378225
    9518484/01191.4015.90105263.5075290.200.1345260
    9518552501371.6517.27123268.5889000.170.1345290
    9518713501371.6520.29171978.74124600.130.1312350
    9518975001371.6522.96240891.44178000.100.1280430
    9519056001612.0326.312927129.54213600.080.1280475
    9519137501612.0328.913634142.24267000.070.1247535
    95192110001612.0332.694810162.56356000.060.1214615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:39 p.m. UTC