SPEC 22060

SIMpull ® THHN THWN-2 MTW / c(UL) T90 Nylon TWN75

Copper Conductor, 600V, Thermoplastic-Insulated Cable, All Sizes Rated TWN75

...

Construction:

  1. Conductor:Solid per ASTM B3 or Combination unilay-stranded copper conductors per ASTM B787.
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath
  3. Jacket:Polyvinyl Chloride PVC jacket utilizing SIMpull® Technology.

Applications and Features:

SIMpull® THHN,THWN-2,MTW-(UL)-suitablefordrylocationsnotexceeding90°C.ForGasolineandOilResistantII applications not to exceed 75°C. MTW (UL) - suitable for dry locations not exceeding 90°C. For wet locations, Gasoline and Oil Resistant II applications not to exceed 60°C. T90 Nylon c(UL) - cables are primarily intended for installation in conduit (raceways) as exposed wiring in dry locations not exceeding 90°C. TWN75 c(UL) - suitable for wet or dry locations at not more than 75°C. The maximum voltage rating for all intended applications is 600 volts. Minimum installation handling temperature is limited to -25°C. Minimum operating temperature limited to -40°C.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • Sample Print Legend:

    SOUTHWIRE SIMpull{TM} E51583 {UL} (XX AWG) XX.X{mm2} CU TYPE MTW OR THWN-2 OR THHN OR GASOLINE AND OIL RESISTANT II OR AWM 600 VOLTS VW-1 --- {CSA} T90 NYLON OR TWN75 600 VOLTS FT1 {NOM}-ANCE 90{D}C - (X AWG) ---RoHS PAT www.patentSW.com
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ftlb/1000ft
    50766514Solid0.0641550.1061215
    49577012Solid0.0801550.1221923
    48462610Solid0.1012050.1533137
    47200114190.0701550.1131216
    47205012190.0881550.1322024
    47210010190.1132050.1653238
    4721598190.1413060.2175063
    4722096190.1773060.2538195
    4722584190.2254070.322128153
    4846673190.2524070.350162190
    6723862190.2824070.382204235
    6840841190.3225080.439258301
    4719791/0190.3615080.480326374
    4719873/0190.4565080.574518579
    6778204/0190.5125080.630655723
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    507665140.4322.6313.1700.058152025
    495770120.4521.6622.0020.054202530
    484626100.6831.0401.2530.050303540
    472001140.4322.6313.1700.058152025
    472050120.5521.6622.0020.054202530
    472100100.6831.0401.2530.050303540
    47215980.81320.6530.7860.052405055
    47220961.02090.4110.4950.051556575
    47225841.23330.2580.3100.048708595
    48466731.44200.2050.2460.04785100115
    67238621.55300.1620.1950.04595115130
    68408411.76690.1280.1540.046110130145
    4719791/01.98440.1020.1220.044125150170
    4719873/02.213420.0640.0780.042165200225
    6778204/02.516920.0510.0620.041195230260
    † Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 3.0.00C