SPEC 22060

SIMpull ® THHN THWN-2 MTW / c(UL) T90 Nylon TWN75

Copper Conductor, 600V, Thermoplastic-Insulated Cable, All Sizes Rated TWN75

...

Construction:

  1. Conductor:Solid per ASTM B3 or Combination unilay-stranded copper conductors per ASTM B787.
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath
  3. Jacket:Polyvinyl Chloride PVC jacket utilizing SIMpull® Technology.

Applications and Features:

SIMpull® THHN,THWN-2,MTW-(UL)-suitablefordrylocationsnotexceeding90°C.ForGasolineandOilResistantII applications not to exceed 75°C. MTW (UL) - suitable for dry locations not exceeding 90°C. For wet locations, Gasoline and Oil Resistant II applications not to exceed 60°C. T90 Nylon c(UL) - cables are primarily intended for installation in conduit (raceways) as exposed wiring in dry locations not exceeding 90°C. TWN75 c(UL) - suitable for wet or dry locations at not more than 75°C. The maximum voltage rating for all intended applications is 600 volts. Minimum installation handling temperature is limited to -25°C. Minimum operating temperature limited to -40°C.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • Sample Print Legend:

    SOUTHWIRE SIMpull{TM} E51583 {UL} (XX AWG) XX.X{mm2} CU TYPE MTW OR THWN-2 OR THHN OR GASOLINE AND OIL RESISTANT II OR AWM 600 VOLTS VW-1 --- {CSA} T90 NYLON OR TWN75 600 VOLTS FT1 {NOM}-ANCE 90{D}C - (X AWG) ---RoHS PAT www.patentSW.com
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ftlb/1000ft
    507665141Solid0.0641550.1061215
    495770121Solid0.0801550.1221923
    484626101Solid0.1012050.1533137
    472001141190.0701550.1131216
    472050121190.0881550.1322024
    472100101190.1132050.1653238
    47215981190.1413060.2175063
    47220961190.1773060.2538195
    47225841190.2254070.322128153
    48466731190.2524070.350162190
    67238621190.2824070.382204235
    68408411190.3225080.439258301
    4719791/01190.3615080.480326374
    4719873/01190.4565080.574518579
    6778204/01190.5125080.630655723
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    5076651410.4322.6313.1700.058152025
    4957701210.4521.6622.0020.054202530
    4846261010.6831.0401.2530.050303540
    4720011410.4322.6313.1700.058152025
    4720501210.5521.6622.0020.054202530
    4721001010.6831.0401.2530.050303540
    472159810.81320.6530.7860.052405055
    472209611.02090.4110.4950.051556575
    472258411.23330.2580.3100.048708595
    484667311.44200.2050.2460.04785100115
    672386211.55300.1620.1950.04595115130
    684084111.76690.1280.1540.046110130145
    4719791/011.98440.1020.1220.044125150170
    4719873/012.213420.0640.0780.042165200225
    6778204/012.516920.0510.0620.041195230260
    † Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    † Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.