SPEC 45010
TCU 600V NLEPR Insulation Thermoset LSZH-TS Jacket. RHH/RHW-2 Silicone Free
Power Cable 600Volt Single Conductor Tinned Copper, No Lead Ethylene Propylene Rubber (NL-EPR) insulation RHH/RHW-2 USE-2 Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket

Construction:
- Conductor:Class B compressed stranded tinned copper per ASTM B3 and ASTM B33
- Binder Tape:Mylar Tape
- Insulation:No Lead Ethylene Propylene Rubber (NL-EPR) Type RHH/RHW-2 USE-2
- Overall Jacket:Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Silicone-Free Jacket
Applications and Features:
Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XXX KCMIL TINNED CU TYPE RHH OR RHW-2 OR USE-2 XX MILS NL-EPR XX MILS SOLONON{R} ST1 LS FOR CT USE SUN RES 600V
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | mil | mil | inch | lb/1000ft | lb/1000ft | |
TBA | 8 | 7 | 40 | 15 | 0.251 | 50 | 68 |
TBA | 6 | 7 | 45 | 30 | 0.327 | 81 | 114 |
TBA | 4 | 7 | 45 | 30 | 0.375 | 128 | 167 |
TBA | 2 | 7 | 45 | 30 | 0.432 | 204 | 251 |
TBA | 1 | 19 | 55 | 45 | 0.522 | 258 | 333 |
TBA | 1/0 | 19 | 55 | 45 | 0.561 | 325 | 407 |
TBA | 2/0 | 19 | 55 | 45 | 0.605 | 410 | 500 |
TBA | 3/0 | 19 | 55 | 45 | 0.656 | 518 | 618 |
TBA | 4/0 | 19 | 55 | 45 | 0.712 | 653 | 763 |
TBA | 250 | 37 | 65 | 65 | 0.818 | 771 | 933 |
TBA | 350 | 37 | 65 | 65 | 0.921 | 1081 | 1268 |
674244 | 500 | 37 | 65 | 65 | 1.089 | 1543 | 1798 |
TBA | 600 | 61 | 80 | 65 | 1.155 | 1853 | 2116 |
TBA | 750 | 61 | 80 | 65 | 1.258 | 2316 | 2606 |
TBA | 1000 | 61 | 80 | 65 | 1.407 | 3088 | 3416 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
TBA | 8 | 1.0 | 132 | 0.653 | 0.786 | 0.052 | 40 | 50 | 55 |
TBA | 6 | 1.3 | 209 | 0.411 | 0.495 | 0.051 | 55 | 65 | 75 |
TBA | 4 | 1.5 | 333 | 0.258 | 0.310 | 0.048 | 70 | 85 | 95 |
TBA | 2 | 1.7 | 530 | 0.162 | 0.195 | 0.045 | 95 | 115 | 130 |
TBA | 1 | 2.0 | 669 | 0.128 | 0.154 | 0.046 | 110 | 130 | 145 |
TBA | 1/0 | 2.2 | 844 | 0.102 | 0.122 | 0.044 | 125 | 150 | 170 |
TBA | 2/0 | 2.4 | 1064 | 0.081 | 0.097 | 0.043 | 145 | 175 | 195 |
TBA | 3/0 | 2.6 | 1342 | 0.064 | 0.078 | 0.042 | 165 | 200 | 225 |
TBA | 4/0 | 2.8 | 1692 | 0.051 | 0.062 | 0.041 | 195 | 230 | 260 |
TBA | 250 | 3.2 | 2000 | 0.043 | 0.053 | 0.041 | 215 | 255 | 290 |
TBA | 350 | 3.6 | 2800 | 0.031 | 0.039 | 0.040 | 260 | 310 | 350 |
674244 | 500 | 5.4 | 4000 | 0.022 | 0.029 | 0.039 | 320 | 380 | 430 |
TBA | 600 | 5.7 | 4800 | 0.018 | 0.025 | 0.039 | 350 | 420 | 475 |
TBA | 750 | 6.2 | 6000 | 0.014 | 0.022 | 0.038 | 400 | 475 | 535 |
TBA | 1000 | 7.0 | 8000 | 0.011 | 0.018 | 0.037 | 455 | 545 | 615 |
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
Revision: 3.0.00C