SPEC 45010

TCU 600V NLEPR Insulation Thermoset LSZH-TS Jacket. RHH/RHW-2 Silicone Free

Power Cable 600Volt Single Conductor Tinned Copper, No Lead Ethylene Propylene Rubber (NL-EPR) insulation RHH/RHW-2 USE-2 Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded tinned copper per ASTM B3 and ASTM B33
  2. Binder Tape:Mylar Tape
  3. Insulation:No Lead Ethylene Propylene Rubber (NL-EPR) Type RHH/RHW-2 USE-2
  4. Overall Jacket:Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Silicone-Free Jacket

Applications and Features:

Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • CT USE Sizes 1/0 AWG and Larger
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (500kcmil & Larger)
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XXX KCMIL TINNED CU TYPE RHH OR RHW-2 OR USE-2 XX MILS NL-EPR XX MILS SOLONON{R} ST1 LS FOR CT USE SUN RES 600V
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorMin. Avg. Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ftlb/1000ft
    TBA870.14145150.3475094
    TBA670.17745300.42381145
    TBA470.22545300.471128202
    TBA270.28245300.558204307
    TBA1190.32255450.648258397
    TBA1/0190.36155450.687325475
    TBA2/0190.40555450.731410572
    TBA3/0190.45655450.782518694
    TBA4/0190.51255450.878653880
    TBA250370.55865650.9847711061
    TBA350370.66165651.08710811409
    674244500370.78965651.08915431798
    TBA600610.86580651.32118532290
    TBA750610.96880651.42423162793
    TBA1000611.11780651.57330883624
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    TBA81.31320.6530.7860.052405055
    TBA61.62090.4110.4950.051556575
    TBA41.83330.2580.3100.048708595
    TBA22.25300.1620.1950.04595115130
    TBA12.56690.1280.1540.046110130145
    TBA1/02.78440.1020.1220.044125150170
    TBA2/02.910640.0810.0970.043145175195
    TBA3/03.113420.0640.0780.042165200225
    TBA4/03.516920.0510.0620.041195230260
    TBA2503.920000.0430.0530.041215255290
    TBA3505.428000.0310.0390.040260310350
    6742445005.440000.0220.0290.039320380430
    TBA6006.648000.0180.0250.039350420475
    TBA7507.160000.0140.0220.038400475535
    TBA10007.880000.0110.0180.037455545615
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Inductive Reactance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.003

    Updated On: Sept. 23, 2023, 3:07 p.m. UTC