SPEC 60365

Armorlite® Type MC THHN/THWN Aluminum Conductor Feeder Cable 277/480V Colors

Aluminum THHN/THWN-2 Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Bare AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B801or ASTM B836
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Bare aluminum ground
  4. Filler:Fillers as needed
  5. Binder:Mylar tape
  6. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Feeder cable is suitable for use as follows:
  • Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Suitable for power and lighting circuits.
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Installation in cable tray and approved raceways, or as aerial cable on a messenger.
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(E)
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
  • Type THHN/THWN rated 90ºC Dry/ 75ºC Wet
  • Anti-short bushings are not required for use with MC cable per NEC and UL

  • Southwire Armorlite® Type MC Feeder Cable - meets or exceeds the following requirements:
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

  • Color Code
  • 3/C: Brown, Orange, Yellow
  • 4/C: Brown, Orange, Yellow, Gray
  • Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS Compliant Lead-Free, Silicone-Free
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made 600V products.
  • REACH - European Community Regulation
  • Sample Print Legend:

    E96627 {UL} TYPE MC AWG XX THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ft
    5654271/03BRN/ORG/YE0.33619601x41.240614
    5633702/03BRN/ORG/GR0.37619601x41.276705
    5654292/03BRN/ORG/YE0.37619601x41.276705
    5628113/03BRN/ORG/YE0.42219601x41.377833
    5627084/03BRN/ORG/YE0.47419601x21.591087
    5615872503BRN/ORG/YE0.52035701x2/01.7351336
    5628162503BRN/ORG/YE0.52035701x11.7311292
    5628183003BRN/ORG/YE0.56935701x11.8431474
    5630523503BRN/ORG/YE0.61535701x11.9421651
    5627044003BRN/ORG/YE0.65935701x3/02.0351911
    5627065003BRN/ORG/YE0.73535701x2/02.2012226
    5733666003BRN/ORG/YE0.81258801x4002.6622916
    5630467503BRN/ORG/YE0.90858801x1/02.6203121
    5633651/04BRN/ORG/YE0.33619601x41.304778
    5633742/04BRN/ORG/YE0.37619601x41.400918
    5598943/04BRN/ORG/YE0.42219601x41.6141168
    5598964/04BRN/ORG/YE0.47419601x21.7391414
    5599042504BRN/ORG/YE0.52035701x11.9011678
    5599073004BRN/ORG/YE0.56935701x12.0221933
    5599093504BRN/ORG/YE0.61535701x1/02.1332183
    5599114004BRN/ORG/YE0.65935701x3/02.2372491
    5599155004BRN/ORG/YE0.73535701x3/02.4232948
    5599176004BRN/ORG/YE0.81258801x3/02.6423508
    5598696004BRN/ORG/YE0.81258801x4002.7813752
    5599197504BRN/ORG/YE0.90858801x3/02.8914227
    5934507504BRN/ORG/YE0.90858801x3503.1964452
    5598669004BRN/ORG/YE0.99958801x2503.1485062
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors. Does not include ground
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin. Bend Radius*Max Pull TensionDC Resistance at 25°CAC Resistance at 75°CAllowable Ampacity Raceway 60°CAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesLbsΩ/1000ftΩ/1000ftAmpAmpAmp
    565427◊1/08.619000.1680.201100120135
    563370◊2/08.923950.1330.160115135150
    565429◊2/08.923950.1330.160115135150
    562811◊3/09.630200.1050.126130155175
    562708◊4/011.138080.0840.100150180205
    561587◊25012.145000.0710.086170205230
    562816◊25012.145000.0710.086170205230
    562818◊30012.954000.0590.071195230260
    563052◊35013.563000.0500.062210250280
    562704◊40014.272000.0440.054225270305
    562706◊50015.490000.0350.044260310350
    573366◊60018.6108000.0290.037285340385
    563046◊75018.3135000.0240.031320385435
    563365◊1/09.125340.1680.2018096108
    563374◊2/09.831940.1330.16092108120
    559894◊3/011.240270.1050.126104124140
    559896◊4/012.150780.0840.100120144164
    559904◊25013.360000.0710.086136164184
    559907◊30014.172000.0590.071156184208
    559909◊35014.984000.0500.062168200224
    559911◊40015.696000.0440.054180216244
    559915◊50016.9120000.0350.044208248280
    559917◊60018.4144000.0290.037228272308
    559869◊60019.4144000.0290.037228272308
    559919◊75020.2180000.0240.031256308348
    59345075022.3180000.0240.031256308348
    559866◊90022.0216000.0200.027284340384
    Ampacities have been adjusted for more than Three Current-Carrying Conductors
    Ampacities based upon 2023 NEC Table 310.16. Also, see NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 3.0.00C