SPEC 85030

Multi-Conductor CU 600 V Shielded PE/PVC Insulation PVC Jacket Control Cable Color Method 1 Table 1

Control Cable 600 Volt Copper Conductors, Polyethylene Polyvinyl Chloride (PE/PVC) Insulation Shielded Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Polyethylene (PE) and Polyvinyl Chloride (PVC)
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Shielding:5 mil copper Helically-Applied Tape shield
  6. Rip Cord:Rip cord for ease of jacket removal
  7. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C for normal operation in wet and dry locations, 90°C for emergency overload, and 150°C for short circuit conditions.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA CSA marking is available upon request
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    SOUTHWIRE XX AWG X/C PE/PVC CDRS 600V SHIELDED PVC JKT SUN. RES. DIRECT BURIAL {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    TBA18270.04625450.28844696.6698.2770.0362-14BK
    60678518370.04615450.31415536.6698.2770.0362.2-14BK
    60678918770.04615450.418581166.6698.2770.0362.9-10BK
    606790181270.04615600.566921946.6698.2770.0364-7BK
    14 AWG
    60676714770.07120600.5551202202.6313.2650.0583.91418BK
    618969141270.07120600.7071953402.6313.2650.0584.91012BK
    12 AWG
    61872112270.08920450.421641151.6622.0630.0542.92530BK
    61872212370.08920450.446861471.6622.0630.0543.12530BK
    61872312470.08920450.4841091821.6622.0630.0543.42024BK
    61872412770.08920600.6091772911.6622.0630.0544.31821BK
    617106121270.08920600.7772964531.6622.0630.0545.41215BK
    10 AWG
    60676810270.11320450.472921591.041.2910.053.33540BK
    61916210370.11320450.5011262011.041.2910.053.53540BK
    61710510470.11320600.5731612531.041.2910.0542832BK
    62088110470.11320600.5781622591.041.2910.0542832BK
    60676910570.11320600.6281983091.041.2910.054.42832BK
    61896810770.11320600.6772714031.041.2910.054.72428BK
    62229610770.11320600.6812653981.041.2910.054.82428BK
    60677010970.11320600.7893455061.041.2910.055.52428BK
    606771101270.11320800.9294486831.041.2910.056.51820BK
    8 AWG
    6067738270.14245600.6861422750.6530.810.0524.85055BK
    6203018370.14245600.7291963530.6530.810.0525.15055BK
    6073978570.14245800.9163155590.6530.810.0526.44044BK
    6 AWG
    6067746270.17845600.7982103680.4110.510.0515.66575BK
    TBA6370.17870600.8133495210.4110.510.0515.76575BK
    6263046470.17845800.9743826640.4110.510.0516.85260BK
    6008996570.17845801.0514767840.4110.510.0517.45260BK
    2 AWG
    6622382270.28345801.0384807470.1620.2010.0457.3115130BK
    TBA2370.28370801.0875610280.1620.2010.0457.6115130BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.