SPEC 85025
Multi-Conductor CU 600 V FR-XLPE LCT Shielded Thermoplastic CPE-TP Jacket Control Cable Color Method 1 Table 2
Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

Construction:
- Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
- Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Shield:5 mils copper Longitudinally-Applied Corrugated Tape (LCT) shield
- Rip Cord:Rip cord for ease of jacket removal
- Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP)
Applications and Features:
Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
UL Listed
SOUTHWIRE {UL} E75755 XX AWG CU X/C FR-XLPE E2 CDRS SHIELDED TYPE TC CPE JACKET 600V YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Non UL Listed
SOUTHWIRE XX AWG CU X/C FR-XLPE E2 CDRS SHIELDED CPE JACKET 600V SUN RES DIR BUR YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | |||||
14 AWG | |||||||||||||||||||
6262700 | 14 | 4 | 7 | 0.07 | 30 | 45 | 0.506 | 84 | 170 | 2.631 | 3.17 | 6 | 12 | 16 | 20 | ||||
12 AWG | |||||||||||||||||||
661864 | 12 | 2 | 7 | 0.088 | 30 | 45 | 0.488 | 74 | 143 | 1.662 | 2.002 | 5.8 | 20 | 25 | 30 | ||||
6229500 | 12 | 4 | 7 | 0.088 | 30 | 60 | 0.575 | 120 | 225 | 1.662 | 2.002 | 6.9 | 16 | 20 | 24 | ||||
6229480 | 12 | 7 | 7 | 0.088 | 30 | 60 | 0.661 | 187 | 324 | 1.662 | 2.002 | 7.9 | 14 | 17 | 21 | ||||
6229530 | 12 | 12 | 7 | 0.088 | 30 | 80 | 0.872 | 299 | 529 | 1.662 | 2.002 | 10.4 | 10 | 12 | 15 | ||||
10 AWG | |||||||||||||||||||
6229460 | 10 | 2 | 7 | 0.113 | 30 | 60 | 0.566 | 103 | 198 | 1.04 | 1.253 | 6.7 | 30 | 35 | 40 | ||||
6229430 | 10 | 4 | 7 | 0.113 | 30 | 60 | 0.632 | 173 | 293 | 1.04 | 1.253 | 7.5 | 24 | 28 | 32 | ||||
6068590 | 10 | 4 | 7 | 0.113 | 30 | 60 | 0.644 | 162 | 295 | 1.04 | 1.253 | 7.7 | 24 | 28 | 32 | ||||
662216 | 10 | 5 | 7 | 0.113 | 30 | 60 | 0.685 | 206 | 344 | 1.04 | 1.253 | 8.2 | 24 | 28 | 32 | ||||
622209 | 10 | 7 | 7 | 0.113 | 30 | 60 | 0.737 | 276 | 436 | 1.04 | 1.253 | 8.8 | 21 | 24 | 28 | ||||
662217 | 10 | 12 | 7 | 0.113 | 30 | 80 | 0.971 | 455 | 722 | 1.04 | 1.253 | 11.6 | 15 | 17 | 20 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
^ UL Listed part number
^ UL Listed part number
Revision: 3.0.00C