SPEC 85025

Multi-Conductor CU 600 V FR-XLPE LCT Shielded Thermoplastic CPE-TP Jacket Control Cable Color Method 1 Table 2

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Shield:5 mils copper Longitudinally-Applied Corrugated Tape (LCT) shield
  6. Rip Cord:Rip cord for ease of jacket removal
  7. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP)

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE {UL} E75755 XX AWG CU X/C FR-XLPE E2 CDRS SHIELDED TYPE TC CPE JACKET 600V YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG CU X/C FR-XLPE E2 CDRS SHIELDED CPE JACKET 600V SUN RES DIR BUR YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CMin Bending RadiusAllowable Ampacity At 60°CAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    14 AWG
    TBA14270.07030450.452481072.6313.1705.4152025
    TBA14370.07030450.472621282.6313.1705.7152025
    TBA14470.07030450.506781382.6313.1706.1121620
    626270^14470.07030450.514841742.6313.1706.2121620
    TBA14570.07030600.573931772.6313.1706.9121620
    TBA14670.07030600.6121102042.6313.1707.3121620
    TBA14770.07030600.6121232222.6313.1707.3101417
    TBA14870.07030600.6521392482.6313.1707.8101417
    TBA14970.07030600.6911562742.6313.1708.3101417
    TBA141070.07030600.7421723012.6313.1708.971012
    TBA141270.07030600.7622003412.6313.1709.171012
    TBA141570.07030800.8742444422.6313.17010.571012
    TBA141970.07030800.9122995232.6313.17010.971012
    TBA142070.07030800.9523155502.6313.17011.471012
    TBA142570.07030801.0423866602.6313.17012.56911
    TBA143070.07030801.0954557622.6313.17013.16911
    TBA143770.07030801.1725529052.6313.17014.16810
    12 AWG
    66186412270.08830450.488741431.6622.0025.9202530
    TBA12370.08830450.511891631.6622.0026.1202530
    622950^12470.08830600.5751202251.6622.0026.9162024
    TBA12570.08830600.6211362301.6622.0027.5162024
    622948^12770.08830600.6611873241.6622.0027.9141721
    TBA12670.08830600.6661602651.6622.0028.0162024
    TBA12870.08830600.7112043271.6622.0028.5141721
    TBA12970.08830600.7562293631.6622.0029.1141721
    TBA121070.08830600.8142544001.6622.0029.8101215
    622953^121270.08830800.8722995291.6622.00210.5101215
    TBA121570.08830800.9593655901.6622.00211.5101215
    TBA121970.08830801.0024507051.6622.00212.0101215
    TBA122070.08830801.0474747421.6622.00212.6101215
    TBA122570.08830801.1505858981.6622.00213.891113
    TBA123070.08830801.21069210431.6622.00214.591113
    TBA123770.08830801.29884112471.6622.00215.681012
    10 AWG
    622946^10270.11330600.5661031981.0401.2536.8303540
    622943^10470.11330600.6321732931.0401.2537.6242832
    606859^10470.11330600.6521623001.0401.2537.8242832
    66221610570.11330600.6852063441.0401.2538.2242832
    62220910770.11330600.7512764461.0401.2539.0212428
    662217101270.11330800.9714557221.0401.25311.7151720
    TBA10370.11330600.5951292331.0401.2537.1303540
    TBA10670.11330600.7412393611.0401.2538.9242832
    TBA10870.11330600.7943074501.0401.2539.5212428
    TBA10970.11330800.8863455351.0401.25310.6212428
    TBA101070.11330800.9543835911.0401.25311.4151720
    TBA101570.11330801.0765558171.0401.25312.9151720
    TBA101970.11330801.1276899871.0401.25313.5151720
    TBA102070.11330801.18072510391.0401.25314.2151720
    TBA102570.11330801.30089812661.0401.25315.6131518
    TBA103070.11330801.370106614801.0401.25316.4131518
    TBA103770.11330801.473130017791.0401.25317.7121416
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    † Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:41 p.m. UTC